6.
Output and bypass setting
Just connect the AC power (don't need to turn on the UPS) and the LCD will
light up with the welcome slogan (initial) screen. Then press the Down-key to
find the screen and then press Enter-key for setting. Once finished, please
disconnect the AC power and then reconnect power again to refresh the
setting.
Bypass Range Set
A. To protect the load, the function of
bypass auto-transfer is activated
only when the AC main voltage is
within the range of LO (low) and
HI(high). In this screen, press
Enter-key to enter the following
steps for LO/HI voltage setting.
B. The cursor (
→
) will pop up to
indicate the item newly
selected. Press Enter-key to get
the item of LO or HI range the
user want to adjust.
C. Use Up or Down-key to adjust the
voltage (changing 1V by every
press). LO (low rang):176V+/-
20V, HI(high range):253V+/-
20V).
D. Once the value is confirmed, press
Enter-key again to save the data.
19