background image

HE3XINH               

Due to continuing product development, specifications are subject to change without notice.

               © 2012 RenewAire LLC

134785_005                      HE3XINHMan_Jan12.indd                      Revised 01/2012                       www.renewaire.com                      

Page 5

Operation

Principal of Operation

The HE3XINH has one basic purpose: to exhaust air from a 

structure and bring in fresh air from outside, while transferring 

heating or cooling energy from the exhaust air to the fresh air.

The HE3XINH is a very simple device, and will accomplish this 

purpose as long as the blowers for both airstreams are able to 

move air through the energy-exchange core.

Checking that Unit is Operating

Airflow

Airflow should be occurring in both airstreams. Sometimes the easiest 

place to confirm that air is moving is at the external wall caps.  

If  exact  airflow  is  critical,  it  may  be  desirable  to  permanently 

install flow measuring stations and manometers. These also can be 

used to determine when filters should be cleaned or changed.

Use Static Taps in Doors to Measure Airflow Rates

See “Cross-Core Static Drop” in MEASURING AIRFLOW table. These 

may be used to directly measure airflow in the unit.

Energy Exchange

Precise determination of installed sensible energy exchange 

effectiveness requires careful measurement of temperatures and 

airflows in all four airstreams, and in practice is somewhat difficult.

It is possible to confirm that energy is being exchanged simply by 

feeling the ducts. If the Fresh Air duct from the unit into the room 

is closer to room temperature than to the outside temperature, 

energy is being recovered.

Operating Controls

A wide variety of control schemes may be selected by the 

engineer, installer, or owner to meet the ventilation needs of 

the facility. These may include timer clocks, occupancy sensors, 

dehumidistats (for cool-weather operation), carbon dioxide 

sensors, and others. DDC systems may also control the unit with 

external control by other. Most control schemes will operate the 

unit only when needed.

HE3XINH Airflow Performance

Motor 

HP

Blower 

RPM

Turns 

Open

External Static Pressure (in. w.g.)

0.00

0.25

0.50

0.75

1.00

1.25

1.50

SCFM

BHP

SCFM

BHP

SCFM

BHP

SCFM

BHP

SCFM

BHP

SCFM

BHP

SCFM

BHP

2

1189

4

2185

1.0

2095

0.9

1900

0.8

1580

0.6

800

0.4

1329

2

2440

1.4

2360

1.3

2220

1.2

2020

1.0

1640

0.8

850

0.4

1470

0

2700

1.9

2640

1.8

2520

1.6

2360

1.5

2150

1.8

1770

1.0

1110

0.6

(a)

1496

3

2905

2.4

2815

2.3

2675

2.1

2505

1.9

2340

1.8

2220

1.6

1655

1.2

1560

2

3030

2.7

2945

2.6

2825

2.5

2655

2.3

2445

2.1

2325

1.9

1990

1.6

1656

0.5

3040

3.0

2875

2.8

2720

2.6

2575

2.4

2380

2.2

1688

0

2950

2.9

2800

2.8

2650

2.6

2490

3.0

(b)

1686

3

3300

3.5

3225

3.4

3015

3.2

2855

3.0

2800

2.8

2645

2.6

2470

2.4

1764

1.5

3290

3.8

3145

3.5

2995

3.3

2850

3.1

2705

2.9

1843

0

3300

4.1

3175

3.8

3040

3.6

2900

3.4

(a) Sheaves for 3HP motors can be adjusted from 1688 RPMs at 0 turns to 1400 RPM at 4.5 turns.  Operating range shown is best for motor efficiency.

(b) Sheaves for 5HP motors can be adjusted from 1843 RPMs at 0 turns to 1503 RPM at 6.5 turns.  However, motor efficiency drops at lower loads.

Continuous Operation

Continuous operation is acceptable in virtually all conditions.  

Unit will not be damaged by continuous operation as long as 

air  flow  occurs.  Blower  motors  may  overheat  if  filters  become 

completely blocked due to lack of maintenance. Motors are 

thermally protected. With continuous operation, some external 

frosting may occur in very cold weather (see below).

Operation in Extreme Cold Weather

Unit is capable of operating at outside temperatures down to 

-10°F,  with  indoor  humidities  below  40%,  without  any  internal 

frosting. Unit can operate at more severe conditions occasionally 

with little or no impact on its performance. At lower humidities, 

it can operate at lower outside temperatures without freezing 

the energy-exchange core.

Some condensation or even frost may form on the outside or 

drip off of the case during very cold conditions, particularly if 

the unit runs continuously. Exterior condensation during extreme 

conditions can be reduced or prevented by periodically cycling 

the unit off for several minutes to allow the case to warm up.

Summary of Contents for HE3XINH

Page 1: ...xhausting of gases through the flue chimney of fuel burning equipment that might be installed in the area affected by this equipment If this unit is exhausting air from a space in which chimney vented...

Page 2: ...hange core The fresh air inlet should be at least 10 away from chimneys furnace and water heater exhausts and other sources of carbon monoxide humidity or other contamination Do not locate the fresh a...

Page 3: ...g air handling system it may be necessary to check for balance with and without the main air handling blower in operation In some facilities a slight positive or negative pressure in the building is d...

Page 4: ...OR OUTDOOR IN INDOOR 1 5 MODEL HE 3X 20 16 17 UNUSED IN HE 3X MODELS 24 L LISTED N NON LISTED OPTION 4 OTHERS T TR TRANSFORMER WITH ISOLATION RELAY NONE W WHITE PAINT C CUSTOM PAINT X CUSTOM UNIT 1 2...

Page 5: ...needed HE3XINH Airflow Performance Motor HP Blower RPM Turns Open External Static Pressure in w g 0 00 0 25 0 50 0 75 1 00 1 25 1 50 SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP 2 1...

Page 6: ...cap from pressure port before inserting tubing Insure tubing is well seated in pressure ports NOTE The tubing should extend in the pressure port approx 1 inch Cross Core Static Pressure Measurement I...

Page 7: ...INSTALL PROVIDED JUMPER BETWEEN TERMINALS 2 3 UNIT CONTROL USING CLASS II 24VAC POWER FROM ANOTHER POWER SOURCE 24VAC POWER AVAILABLE AT TERMINALS 1 2 DO NOT INSTALL JUMPER BETWEEN TERMINALS 2 3 HE3X...

Page 8: ...the control terminals of this unit 5 Unit is not equipped to receive analog signals such as 1 10vdc or 4 20mA 6 Unit is not equipped to communicate directly with Building Management Systems such as B...

Page 9: ...onnect Terminals 2 3 Connect Switch between Terminals 1 4 UNIT INTERNAL CONTROL WIRING SIMPLIFIED A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY UNIT INTERNAL CONTROL WIRING SIMPLIFIE...

Page 10: ...HE3XINHMan_Jan12 indd Revised 01 2012 www renewaire com Page 10 HE3XINH Replacement Parts A CORES B FILTERS C BLOWER DOOR D TURN LATCH E DISCONNECT SWITCH F TRANSFORMER G ISOLATION RELAY H OVERLOAD RE...

Page 11: ...o continuing product development specifications are subject to change without notice 2012 RenewAire LLC 134785_005 HE3XINHMan_Jan12 indd Revised 01 2012 www renewaire com Page 11 THIS PAGE INTENTIONAL...

Page 12: ...Blowers every time you change the filters Confirm bearings are still secure to blower shaft It should not be possible to move the blower shaft back and forth along its length Confirm blower wheel is n...

Reviews: