INSTALLATION AND OPERATION MANUAL

HE3XINH

NOTE: Disconnect Switch and 24V Transformer Standard

RISK OF FIRE, ELECTRIC SHOCK, OR INJURY.   

OBSERVE ALL CODES AND THE FOLLOWING:

1.  Before servicing or cleaning the unit, switch power 

off at disconnect switch or service panel and lock-

out/tag-out to prevent power from being switched on 

accidentally. More than one disconnect switch may be 

required to de-energize the equipment for servicing.

2.  This installation manual shows the suggested 

installation method. Additional measures may be 

required by local codes and standards.

3.  Installation work and electrical wiring must be 

done  by  qualified  professional(s)  in  accordance 

with all applicable codes, standards and licensing 

requirements.

4.  Any structural alterations necessary for installation 

must comply with all applicable building, health, and 

safety code requirements.  

5.  This unit must be grounded.

6. 

Sufficient  air  is  needed  for  proper  combustion  and 

exhausting of gases through the flue (chimney) of fuel 

burning equipment that might be installed in the area 

affected by this equipment. If this unit is exhausting 

air from a space in which chimney-vented fuel 

burning equipment is located, take steps to assure 

that combustion air supply is not affected. Follow the 

heating equipment manufacturer’s requirements and 

the combustion air supply requirements of applicable 

codes and standards.

7.  Use the unit only in the manner intended by the 

manufacturer. If you have questions, contact the 

manufacturer.

8.  This unit is intended for general ventilating only. Do 

not use to exhaust hazardous or explosive materials 

and vapors. Do not connect this unit to range hoods, 

fume hoods or collection systems for toxics.

9.  When cutting or drilling into wall or ceiling, do not  

damage electrical wiring and other hidden utilities.

10. If installed indoors this unit must be properly ducted 

to the outdoors.

To avoid motor bearing damage and noisy and/or 

unbalanced impellers, keep drywall spray, construction 

dust, etc., out of unit.

Do not remove or disable the wiring interconnection between the 

Overload Relays and the Contactors. Without this interconnection 

the motor(s) will not be protected against overload.

In  2012,  these  ERVs  may  be  ordered  with  new  factory-

installed features including Isolation Dampers and Variable 

Frequency  Drives.  Consult  the  supplemental  Installation 

and Operation Manual(s) for these features if supplied.

Summary of Contents for HE3XINH

Page 1: ...xhausting of gases through the flue chimney of fuel burning equipment that might be installed in the area affected by this equipment If this unit is exhausting air from a space in which chimney vented...

Page 2: ...hange core The fresh air inlet should be at least 10 away from chimneys furnace and water heater exhausts and other sources of carbon monoxide humidity or other contamination Do not locate the fresh a...

Page 3: ...g air handling system it may be necessary to check for balance with and without the main air handling blower in operation In some facilities a slight positive or negative pressure in the building is d...

Page 4: ...OR OUTDOOR IN INDOOR 1 5 MODEL HE 3X 20 16 17 UNUSED IN HE 3X MODELS 24 L LISTED N NON LISTED OPTION 4 OTHERS T TR TRANSFORMER WITH ISOLATION RELAY NONE W WHITE PAINT C CUSTOM PAINT X CUSTOM UNIT 1 2...

Page 5: ...needed HE3XINH Airflow Performance Motor HP Blower RPM Turns Open External Static Pressure in w g 0 00 0 25 0 50 0 75 1 00 1 25 1 50 SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP 2 1...

Page 6: ...cap from pressure port before inserting tubing Insure tubing is well seated in pressure ports NOTE The tubing should extend in the pressure port approx 1 inch Cross Core Static Pressure Measurement I...

Page 7: ...INSTALL PROVIDED JUMPER BETWEEN TERMINALS 2 3 UNIT CONTROL USING CLASS II 24VAC POWER FROM ANOTHER POWER SOURCE 24VAC POWER AVAILABLE AT TERMINALS 1 2 DO NOT INSTALL JUMPER BETWEEN TERMINALS 2 3 HE3X...

Page 8: ...the control terminals of this unit 5 Unit is not equipped to receive analog signals such as 1 10vdc or 4 20mA 6 Unit is not equipped to communicate directly with Building Management Systems such as B...

Page 9: ...onnect Terminals 2 3 Connect Switch between Terminals 1 4 UNIT INTERNAL CONTROL WIRING SIMPLIFIED A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY UNIT INTERNAL CONTROL WIRING SIMPLIFIE...

Page 10: ...HE3XINHMan_Jan12 indd Revised 01 2012 www renewaire com Page 10 HE3XINH Replacement Parts A CORES B FILTERS C BLOWER DOOR D TURN LATCH E DISCONNECT SWITCH F TRANSFORMER G ISOLATION RELAY H OVERLOAD RE...

Page 11: ...o continuing product development specifications are subject to change without notice 2012 RenewAire LLC 134785_005 HE3XINHMan_Jan12 indd Revised 01 2012 www renewaire com Page 11 THIS PAGE INTENTIONAL...

Page 12: ...Blowers every time you change the filters Confirm bearings are still secure to blower shaft It should not be possible to move the blower shaft back and forth along its length Confirm blower wheel is n...

Reviews: