Placement of the HE3XINH

The HE3XINH is designed for installation in a sheltered location, 

out of the weather. 

The preferred mounting location is sitting on a concrete floor.  Unit base 

may be bolted to floor. The concrete will isolate any blower vibration.

Select a location that is central to the inside duct runs, and close 

to both the exhaust duct (to the outside) and the fresh air duct 

(from the outside).
The 

exhaust outlet and outside air inlet

 on the outside of the building 

should be at least 

ten feet apart

 to avoid cross-contamination.

The exhaust outlet should not dump air into an enclosed space 

or any other structure. The inlets and outlets should be screened 

against insects and vermin and shielded from the weather to 

prevent the entry of rain or snow.
Install the ERV where you can open the door for cleaning the core and 

filter, and where you can get at the wiring for installation and service.

Duct Connections 

as Labeled

Alternate 

Duct Connections

EA

OA

FA

RA

EA

FA

OA

RA

RA = Room Air into unit

OA = Outside Air into unit

FA = Fresh Air to inside

EA = Exhaust Air to outside

NOTE

Airstreams always cross in 

the energy-exchange core.

The fresh air inlet should be at least 10’ away from 

chimneys, furnace and water heater exhausts, and 

other sources of carbon monoxide, humidity or other 

contamination. 

Do not locate the fresh air inlet where vehicles may 

be serviced or left idling. 

Never locate the fresh air inlet inside a structure.

Exhaust & Fresh Air Ducts

Between HE3XINH & Outside

Insulation

Ducts connecting the HE3XINH to the outside must be insulated, 

with sealed vapor barrier on both inside and outside of the 

insulation.

The exhaust outlet and fresh air inlet on the outside of the building 

should be at least ten feet apart to avoid cross-contamination. 

Wall caps should be designed to exclude animals and rain.  Wall 

caps should be sized for minimum pressure loss. To keep rain from 

being drawn in, the outside air intake should be large enough to 

keep inlet velocity below 500 feet per minute, (or as dictated by 

local practice).

Outside Wall Caps

Always insulate 

OA and EA Ducts.

RA

OA

OA

EA

EA

Best Practice is to separate OA and EA Wall Caps by 10' or more.

FA

Straight ducts at Blower Outlets

is preferred for best performance.

Insulate FA and RA Ducts if 

installed in unconditioned spaces

or for sound attenuation.

The HE3XINH weighs approximately 675 lbs. It is the 

installer’s responsibility to make sure that the screws 

or bolts used for securing the units are properly 

selected for the loads and substrates involved. Secure 

the HE3XINH so that it cannot fall or tip in the event 

of accident, structural failure or earthquake.

Summary of Contents for HE3XINH

Page 1: ...xhausting of gases through the flue chimney of fuel burning equipment that might be installed in the area affected by this equipment If this unit is exhausting air from a space in which chimney vented...

Page 2: ...hange core The fresh air inlet should be at least 10 away from chimneys furnace and water heater exhausts and other sources of carbon monoxide humidity or other contamination Do not locate the fresh a...

Page 3: ...g air handling system it may be necessary to check for balance with and without the main air handling blower in operation In some facilities a slight positive or negative pressure in the building is d...

Page 4: ...OR OUTDOOR IN INDOOR 1 5 MODEL HE 3X 20 16 17 UNUSED IN HE 3X MODELS 24 L LISTED N NON LISTED OPTION 4 OTHERS T TR TRANSFORMER WITH ISOLATION RELAY NONE W WHITE PAINT C CUSTOM PAINT X CUSTOM UNIT 1 2...

Page 5: ...needed HE3XINH Airflow Performance Motor HP Blower RPM Turns Open External Static Pressure in w g 0 00 0 25 0 50 0 75 1 00 1 25 1 50 SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP 2 1...

Page 6: ...cap from pressure port before inserting tubing Insure tubing is well seated in pressure ports NOTE The tubing should extend in the pressure port approx 1 inch Cross Core Static Pressure Measurement I...

Page 7: ...INSTALL PROVIDED JUMPER BETWEEN TERMINALS 2 3 UNIT CONTROL USING CLASS II 24VAC POWER FROM ANOTHER POWER SOURCE 24VAC POWER AVAILABLE AT TERMINALS 1 2 DO NOT INSTALL JUMPER BETWEEN TERMINALS 2 3 HE3X...

Page 8: ...the control terminals of this unit 5 Unit is not equipped to receive analog signals such as 1 10vdc or 4 20mA 6 Unit is not equipped to communicate directly with Building Management Systems such as B...

Page 9: ...onnect Terminals 2 3 Connect Switch between Terminals 1 4 UNIT INTERNAL CONTROL WIRING SIMPLIFIED A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY UNIT INTERNAL CONTROL WIRING SIMPLIFIE...

Page 10: ...HE3XINHMan_Jan12 indd Revised 01 2012 www renewaire com Page 10 HE3XINH Replacement Parts A CORES B FILTERS C BLOWER DOOR D TURN LATCH E DISCONNECT SWITCH F TRANSFORMER G ISOLATION RELAY H OVERLOAD RE...

Page 11: ...o continuing product development specifications are subject to change without notice 2012 RenewAire LLC 134785_005 HE3XINHMan_Jan12 indd Revised 01 2012 www renewaire com Page 11 THIS PAGE INTENTIONAL...

Page 12: ...Blowers every time you change the filters Confirm bearings are still secure to blower shaft It should not be possible to move the blower shaft back and forth along its length Confirm blower wheel is n...