HE3XINH               

Due to continuing product development, specifications are subject to change without notice.

               © 2012 RenewAire LLC

134785_005                      HE3XINHMan_Jan12.indd                      Revised 01/2012                       www.renewaire.com                      

Page 9

E. 

Control System with 2 Non-powered Relay Contacts: Use 

this schematic if the external control system provides no 

voltage or current at its output contacts. Install jumper 

(provided) between terminals 2 & 3. Connect one side of 

each of the output contacts to Terminal 1. Connect the 

other side of the output contact to control the FA Blower 

to Terminal 4, and the output contacts to control the EA 

Blower to Terminal 5.

Control Wiring Schematics

NOTE: The simplified schematics below show only the relevant

portions of the low-voltage control circuit in the ERV unit and

representational external control approaches. See the 

complete unit schematics elsewhere in this manual.

C. 

Control Sending 24VAC “On” Signal (from an external 

power source) to ERV: Make sure jumper is NOT installed 

between Terminals 2 & 3. Now you safely can apply 24VAC 

to the Terminals 3 & 4 to operate the ERV’s Isolation Relay 

for OA/FA Blower. Install jumper (provided) between 

terminals 4 & 5 to operate the ERV’s Isolation Relay for 

the RA/EA Blower.  

D. 

Control operating on Unit’s 24VAC Power Supply: 24VAC 

power is available at the Terminals 1 & 2. CAUTION: 

external control system should not draw more than 8VA. 

Install jumper (provided) between terminals 2 & 3.

 

Connect the switched output of the Control to Terminal 

4 to operate the ERV’s Isolation Relay for OA/FA Blower. 

Install jumper (provided) between terminals 4 & 5 to 

operate the ERV’s Isolation Relay for the RA/EA Blower.  

F. 

Control System Sending two 24VAC “On” Signals from 

an external power source: Make sure the jumper is NOT 

installed between Terminals 2 & 3. Now you safely can 

apply one of the 24VAC signals to Terminals 3 & 4 to operate 

the ERV’s isolation relay for the Fresh Air Blower. Apply 

the second 24VAC signal to Terminals 3 & 5 to operate the 

ERV’s isolation relay for the Exhaust Blower (make sure the 

polarity of each wire connected to Terminal 3 is the same).

Make sure the control provides no voltage or current at its 

output terminals.

Supply only 24VAC (not VDC) from a Class II Power Source.

A. 

Single 2-wire Control, unpowered: Use schematic below 

if the control requires no power from the unit to operate 

and acts like a simple on/off switch. The control must not 

supply any power to the ERV unit. Install jumper (provided) 

between terminals 2 & 3. Connect the control’s contacts to 

terminals 1 & 4 to operate the ERV’s Isolation Relay for OA/

FA Blower. Install jumper (provided) between terminals 4 & 

5 to operate the ERV’s Isolation Relay for the RA/EA Blower.  

Supply only 24VAC (not VDC) from a Class II Power Source.

G.  Control System Operating Isolation Dampers with End 

Switches: Use Isolation Dampers with electrically separate 

end switches. The end switches are used to separately 

control the ERV unit’s Isolation Relays. This ensures that 

each damper is open before the respective blower starts up.

 

NOTE: Because the ERV’s Motor Starters will only be 

operating once the Dampers are open, the power draw 

of the Damper Actuators is allowed to be as much as 35VA 

while opening (including power draw of the external 

control system, if any). However, the power draw of the 

fully-opened (stalled) Actuators (and external control 

system if any) must be less than 8VA. (Most damper 

actuators have much lower power draws.)

B. 

Single 2-wire Control on separate Power Supply, no power 

present at Control Output: Wire as shown for the Single 

2-wire control (A. above). 

MPU

Connect Terminals 2 & 3

Connect Switch between Terminals 1 & 4

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

A SWITCH OR NON-POWERED 

CONTROL USING UNIT'S 24VAC POWER 

SUPPLY

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

24VAC FROM AN EXTERNAL SOURCE

Unit's 24VAC 

Power Supply

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

AN EXTERNAL CONTROL USING UNIT'S 

24VAC POWER SUPPLY

24VAC Available at Terminals 1 & 2

Unit's 24VAC 

Power Supply

Unit's 24VAC 

Power Supply

Connect Terminals 2 & 3

UNIT INTERNAL CONTROL WIRING

C

Isolation Relay Coil (Fresh Air)

(SIMPLIFIED)

A SWITCH OR NON-POWERED 

CONTROL USING UNIT'S 24VAC POWER 

SUPPLY

Unit's 24VAC 

Power Supply

C

Isolation Relay Coil (Exhaust Air)

UNIT INTERNAL CONTROL WIRING

C

Isolation Relay Coil (Fresh Air)

(SIMPLIFIED)

TWO EXTERNAL RELAY CONTACTS 

SUPPLYING 24VAC FROM AN 

EXTERNAL SOURCE

Unit's 24VAC 

Power Supply

C

Isolation Relay Coil (Exhaust Air)

C

Isolation Relay Coil (Fresh Air)

C

Isolation Relay Coil (Exhaust Air)

C

Isolation Relay Coil (Fresh Air)

C

Isolation Relay Coil (Exhaust Air)

C

Isolation Relay Coil (Fresh Air)

C

Isolation Relay Coil (Exhaust Air)

Connect Terminals 4 & 5

Connect Switch between Terminals 1 & 4

Connect Terminals 4 & 5

Connect Terminals 4 & 5

Connect Terminals 2 & 3

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

MPU

Connect Terminals 2 & 3

Connect Switch between Terminals 1 & 4

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

A SWITCH OR NON-POWERED 

CONTROL USING UNIT'S 24VAC POWER 

SUPPLY

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

24VAC FROM AN EXTERNAL SOURCE

Unit's 24VAC 

Power Supply

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

AN EXTERNAL CONTROL USING UNIT'S 

24VAC POWER SUPPLY

24VAC Available at Terminals 1 & 2

Unit's 24VAC 

Power Supply

Unit's 24VAC 

Power Supply

Connect Terminals 2 & 3

UNIT INTERNAL CONTROL WIRING

C

Isolation Relay Coil (Fresh Air)

(SIMPLIFIED)

A SWITCH OR NON-POWERED 

CONTROL USING UNIT'S 24VAC POWER 

SUPPLY

Unit's 24VAC 

Power Supply

C

Isolation Relay Coil (Exhaust Air)

UNIT INTERNAL CONTROL WIRING

C

Isolation Relay Coil (Fresh Air)

(SIMPLIFIED)

TWO EXTERNAL RELAY CONTACTS 

SUPPLYING 24VAC FROM AN 

EXTERNAL SOURCE

Unit's 24VAC 

Power Supply

C

Isolation Relay Coil (Exhaust Air)

C

Isolation Relay Coil (Fresh Air)

C

Isolation Relay Coil (Exhaust Air)

C

Isolation Relay Coil (Fresh Air)

C

Isolation Relay Coil (Exhaust Air)

C

Isolation Relay Coil (Fresh Air)

C

Isolation Relay Coil (Exhaust Air)

Connect Terminals 4 & 5

Connect Switch between Terminals 1 & 4

Connect Terminals 4 & 5

Connect Terminals 4 & 5

Connect Terminals 2 & 3

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

MPU

Connect Terminals 2 & 3

Connect Switch between Terminals 1 & 4

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

A SWITCH OR NON-POWERED 

CONTROL USING UNIT'S 24VAC POWER 

SUPPLY

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

24VAC FROM AN EXTERNAL SOURCE

Unit's 24VAC 

Power Supply

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

AN EXTERNAL CONTROL USING UNIT'S 

24VAC POWER SUPPLY

24VAC Available at Terminals 1 & 2

Unit's 24VAC 

Power Supply

Unit's 24VAC 

Power Supply

Connect Terminals 2 & 3

UNIT INTERNAL CONTROL WIRING

C

Isolation Relay Coil (Fresh Air)

(SIMPLIFIED)

A SWITCH OR NON-POWERED 

CONTROL USING UNIT'S 24VAC POWER 

SUPPLY

Unit's 24VAC 

Power Supply

C

Isolation Relay Coil (Exhaust Air)

UNIT INTERNAL CONTROL WIRING

C

Isolation Relay Coil (Fresh Air)

(SIMPLIFIED)

TWO EXTERNAL RELAY CONTACTS 

SUPPLYING 24VAC FROM AN 

EXTERNAL SOURCE

Unit's 24VAC 

Power Supply

C

Isolation Relay Coil (Exhaust Air)

C

Isolation Relay Coil (Fresh Air)

C

Isolation Relay Coil (Exhaust Air)

C

Isolation Relay Coil (Fresh Air)

C

Isolation Relay Coil (Exhaust Air)

C

Isolation Relay Coil (Fresh Air)

C

Isolation Relay Coil (Exhaust Air)

Connect Terminals 4 & 5

Connect Switch between Terminals 1 & 4

Connect Terminals 4 & 5

Connect Terminals 4 & 5

Connect Terminals 2 & 3

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

MPU

Connect Terminals 2 & 3

Connect Switch between Terminals 1 & 4

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

A SWITCH OR NON-POWERED 

CONTROL USING UNIT'S 24VAC POWER 

SUPPLY

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

24VAC FROM AN EXTERNAL SOURCE

Unit's 24VAC 

Power Supply

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

AN EXTERNAL CONTROL USING UNIT'S 

24VAC POWER SUPPLY

24VAC Available at Terminals 1 & 2

Unit's 24VAC 

Power Supply

Unit's 24VAC 

Power Supply

Connect Terminals 2 & 3

UNIT INTERNAL CONTROL WIRING

C

Isolation Relay Coil (Fresh Air)

(SIMPLIFIED)

A SWITCH OR NON-POWERED 

CONTROL USING UNIT'S 24VAC POWER 

SUPPLY

Unit's 24VAC 

Power Supply

C

Isolation Relay Coil (Exhaust Air)

UNIT INTERNAL CONTROL WIRING

C

Isolation Relay Coil (Fresh Air)

(SIMPLIFIED)

TWO EXTERNAL RELAY CONTACTS 

SUPPLYING 24VAC FROM AN 

EXTERNAL SOURCE

Unit's 24VAC 

Power Supply

C

Isolation Relay Coil (Exhaust Air)

C

Isolation Relay Coil (Fresh Air)

C

Isolation Relay Coil (Exhaust Air)

C

Isolation Relay Coil (Fresh Air)

C

Isolation Relay Coil (Exhaust Air)

C

Isolation Relay Coil (Fresh Air)

C

Isolation Relay Coil (Exhaust Air)

Connect Terminals 4 & 5

Connect Switch between Terminals 1 & 4

Connect Terminals 4 & 5

Connect Terminals 4 & 5

Connect Terminals 2 & 3

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

MPU

Connect Terminals 2 & 3

Connect Switch between Terminals 1 & 4

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

A SWITCH OR NON-POWERED 

CONTROL USING UNIT'S 24VAC POWER 

SUPPLY

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

24VAC FROM AN EXTERNAL SOURCE

Unit's 24VAC 

Power Supply

UNIT INTERNAL CONTROL WIRING

(SIMPLIFIED)

AN EXTERNAL CONTROL USING UNIT'S 

24VAC POWER SUPPLY

24VAC Available at Terminals 1 & 2

Unit's 24VAC 

Power Supply

Unit's 24VAC 

Power Supply

Connect Terminals 2 & 3

UNIT INTERNAL CONTROL WIRING

C

Isolation Relay Coil (Fresh Air)

(SIMPLIFIED)

A SWITCH OR NON-POWERED 

CONTROL USING UNIT'S 24VAC POWER 

SUPPLY

Unit's 24VAC 

Power Supply

C

Isolation Relay Coil (Exhaust Air)

UNIT INTERNAL CONTROL WIRING

C

Isolation Relay Coil (Fresh Air)

(SIMPLIFIED)

TWO EXTERNAL RELAY CONTACTS 

SUPPLYING 24VAC FROM AN 

EXTERNAL SOURCE

Unit's 24VAC 

Power Supply

C

Isolation Relay Coil (Exhaust Air)

C

Isolation Relay Coil (Fresh Air)

C

Isolation Relay Coil (Exhaust Air)

C

Isolation Relay Coil (Fresh Air)

C

Isolation Relay Coil (Exhaust Air)

C

Isolation Relay Coil (Fresh Air)

C

Isolation Relay Coil (Exhaust Air)

Connect Terminals 4 & 5

Connect Switch between Terminals 1 & 4

Connect Terminals 4 & 5

Connect Terminals 4 & 5

Connect Terminals 2 & 3

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

1

2

3

4

5

Summary of Contents for HE3XINH

Page 1: ...xhausting of gases through the flue chimney of fuel burning equipment that might be installed in the area affected by this equipment If this unit is exhausting air from a space in which chimney vented...

Page 2: ...hange core The fresh air inlet should be at least 10 away from chimneys furnace and water heater exhausts and other sources of carbon monoxide humidity or other contamination Do not locate the fresh a...

Page 3: ...g air handling system it may be necessary to check for balance with and without the main air handling blower in operation In some facilities a slight positive or negative pressure in the building is d...

Page 4: ...OR OUTDOOR IN INDOOR 1 5 MODEL HE 3X 20 16 17 UNUSED IN HE 3X MODELS 24 L LISTED N NON LISTED OPTION 4 OTHERS T TR TRANSFORMER WITH ISOLATION RELAY NONE W WHITE PAINT C CUSTOM PAINT X CUSTOM UNIT 1 2...

Page 5: ...needed HE3XINH Airflow Performance Motor HP Blower RPM Turns Open External Static Pressure in w g 0 00 0 25 0 50 0 75 1 00 1 25 1 50 SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP 2 1...

Page 6: ...cap from pressure port before inserting tubing Insure tubing is well seated in pressure ports NOTE The tubing should extend in the pressure port approx 1 inch Cross Core Static Pressure Measurement I...

Page 7: ...INSTALL PROVIDED JUMPER BETWEEN TERMINALS 2 3 UNIT CONTROL USING CLASS II 24VAC POWER FROM ANOTHER POWER SOURCE 24VAC POWER AVAILABLE AT TERMINALS 1 2 DO NOT INSTALL JUMPER BETWEEN TERMINALS 2 3 HE3X...

Page 8: ...the control terminals of this unit 5 Unit is not equipped to receive analog signals such as 1 10vdc or 4 20mA 6 Unit is not equipped to communicate directly with Building Management Systems such as B...

Page 9: ...onnect Terminals 2 3 Connect Switch between Terminals 1 4 UNIT INTERNAL CONTROL WIRING SIMPLIFIED A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY UNIT INTERNAL CONTROL WIRING SIMPLIFIE...

Page 10: ...HE3XINHMan_Jan12 indd Revised 01 2012 www renewaire com Page 10 HE3XINH Replacement Parts A CORES B FILTERS C BLOWER DOOR D TURN LATCH E DISCONNECT SWITCH F TRANSFORMER G ISOLATION RELAY H OVERLOAD RE...

Page 11: ...o continuing product development specifications are subject to change without notice 2012 RenewAire LLC 134785_005 HE3XINHMan_Jan12 indd Revised 01 2012 www renewaire com Page 11 THIS PAGE INTENTIONAL...

Page 12: ...Blowers every time you change the filters Confirm bearings are still secure to blower shaft It should not be possible to move the blower shaft back and forth along its length Confirm blower wheel is n...

Reviews: