HE3XINH Electrical Specifications
NOTE: Proper Wiring Size Selection and Wiring Installation
are the Responsibility of the Electrical Contractor.
Blower & contactor voltages are specified with order and set at
factory.
Brake Horsepower at various Blower RPM, Motor Rating, and ESP
combinations are available on Spec Sheet or from factory.
Electrical Options and Ratings are identified on the Unit Label
(located near electrical box). Find the complete Unit Model
Number in the lower left corner of the Unit Label.
Danger of Electrical Shock when servicing an installed
unit.
ALWAYS DISCONNECT POWER SOURCE BEFORE
SERVICING! More than one disconnect switch may be
required.
Proper Wiring Size Selection and Wiring Installation
are the Responsibility of the Electrical Contractor.
Measuring Airflow
Equipment Required
•
A magnehelic gauge or other device capable of measuring 0
to 1.5 in. water of differential pressure.
•
2 pieces of natural rubber latex tubing, 1/8” ID, 1/16” Wall
works the best. NOTE: Be sure to remove cap from pressure
port before inserting tubing. Insure tubing is well seated
in pressure ports. NOTE: The tubing should extend in the
pressure port approx. 1 inch.
Cross Core Static Pressure Measurement Instructions
•
The individual differential static pressures (DSP) can be
measured using the installed pressure ports located in the
front of the units core access doors. NOTE: These ports
have been carefully located on the unit as to give you the
most accurate airflow measurement. NOTE: Do not relocate
pressure ports.
•
To read SCFM of Fresh Air (FA) install the “high” pressure side
(+) of your measuring device to the Outside Air (OA) port and
the “low” pressure side (-) to the Fresh Air (FA) port.
•
To read SCFM of Room Air (RA) install the “high” pressure
side (+) of your measuring device to the Room Air (RA) port
and the “low” pressure side (-) to the Exhaust Air (EA) port.
•
Use the reading displayed on your measurement device to
cross reference the CFM output using the conversion chart.
NOTE: Be sure to replace cap into pressure port when air
flow measuring is completed.
OA
RA
EA
FA
E-Box
Pressure Points (4)
HE3XINH
Differential Static Across Core DSP vs. CFM
HE3XINH
DSP 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10
Fresh Air
(FA)
CFM 850 1180 1510 1830 2160 2490 2820 3140 3470 3800
Room Air
(RA)
CFM 910 1260 1610 1960 2310 2670 3020 3370 3720 4070
The proper operating airflow range for this model is 750 -
3300 CFM.