HE3XINH Electrical Specifications

NOTE: Proper Wiring Size Selection and Wiring Installation 

are the Responsibility of the Electrical Contractor.

Blower & contactor voltages are specified with order and set at 

factory.

Brake Horsepower at various Blower RPM, Motor Rating, and ESP 

combinations are available on Spec Sheet or from factory.

Electrical Options and Ratings are identified on the Unit Label 

(located near electrical box). Find the complete Unit Model 

Number in the lower left corner of the Unit Label.

Danger of Electrical Shock when servicing an installed 

unit.

ALWAYS DISCONNECT POWER SOURCE BEFORE 

SERVICING! More than one disconnect switch may be 

required. 

Proper Wiring Size Selection and Wiring Installation 

are the Responsibility of the Electrical Contractor.

Measuring Airflow

Equipment Required

• 

A magnehelic gauge or other device capable of measuring 0 

to 1.5 in. water of differential pressure.

• 

2 pieces of natural rubber latex tubing, 1/8” ID, 1/16” Wall 

works the best. NOTE: Be sure to remove cap from pressure 

port before inserting tubing. Insure tubing is well seated 

in pressure ports. NOTE: The tubing should extend in the 

pressure port approx. 1 inch.

Cross Core Static Pressure Measurement Instructions

• 

The individual differential static pressures (DSP) can be 

measured using the installed pressure ports located in the 

front of the units core access doors. NOTE: These ports 

have been carefully located on the unit as to give you the 

most accurate airflow measurement. NOTE: Do not relocate 

pressure ports. 

• 

To read SCFM of Fresh Air (FA) install the “high” pressure side 

(+) of your measuring device to the Outside Air (OA) port and 

the “low” pressure side (-) to the Fresh Air (FA) port.

• 

To read SCFM of Room Air (RA) install the “high” pressure 

side (+) of your measuring device to the Room Air (RA) port 

and the “low” pressure side (-) to the Exhaust Air (EA) port.

• 

Use the reading displayed on your measurement device to 

cross reference the CFM output using the conversion chart. 

NOTE: Be sure to replace cap into pressure port when air 

flow measuring is completed.

OA

RA

EA

FA

E-Box

Pressure Points (4)

HE3XINH

Differential Static Across Core DSP vs. CFM

HE3XINH

DSP 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00 1.10

Fresh Air

 (FA)

CFM 850 1180 1510 1830 2160 2490 2820 3140 3470 3800

Room Air

 (RA)

CFM 910 1260 1610 1960 2310 2670 3020 3370 3720 4070

The  proper  operating  airflow  range  for  this  model  is  750  - 

3300 CFM.

Summary of Contents for HE3XINH

Page 1: ...xhausting of gases through the flue chimney of fuel burning equipment that might be installed in the area affected by this equipment If this unit is exhausting air from a space in which chimney vented...

Page 2: ...hange core The fresh air inlet should be at least 10 away from chimneys furnace and water heater exhausts and other sources of carbon monoxide humidity or other contamination Do not locate the fresh a...

Page 3: ...g air handling system it may be necessary to check for balance with and without the main air handling blower in operation In some facilities a slight positive or negative pressure in the building is d...

Page 4: ...OR OUTDOOR IN INDOOR 1 5 MODEL HE 3X 20 16 17 UNUSED IN HE 3X MODELS 24 L LISTED N NON LISTED OPTION 4 OTHERS T TR TRANSFORMER WITH ISOLATION RELAY NONE W WHITE PAINT C CUSTOM PAINT X CUSTOM UNIT 1 2...

Page 5: ...needed HE3XINH Airflow Performance Motor HP Blower RPM Turns Open External Static Pressure in w g 0 00 0 25 0 50 0 75 1 00 1 25 1 50 SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP SCFM BHP 2 1...

Page 6: ...cap from pressure port before inserting tubing Insure tubing is well seated in pressure ports NOTE The tubing should extend in the pressure port approx 1 inch Cross Core Static Pressure Measurement I...

Page 7: ...INSTALL PROVIDED JUMPER BETWEEN TERMINALS 2 3 UNIT CONTROL USING CLASS II 24VAC POWER FROM ANOTHER POWER SOURCE 24VAC POWER AVAILABLE AT TERMINALS 1 2 DO NOT INSTALL JUMPER BETWEEN TERMINALS 2 3 HE3X...

Page 8: ...the control terminals of this unit 5 Unit is not equipped to receive analog signals such as 1 10vdc or 4 20mA 6 Unit is not equipped to communicate directly with Building Management Systems such as B...

Page 9: ...onnect Terminals 2 3 Connect Switch between Terminals 1 4 UNIT INTERNAL CONTROL WIRING SIMPLIFIED A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY UNIT INTERNAL CONTROL WIRING SIMPLIFIE...

Page 10: ...HE3XINHMan_Jan12 indd Revised 01 2012 www renewaire com Page 10 HE3XINH Replacement Parts A CORES B FILTERS C BLOWER DOOR D TURN LATCH E DISCONNECT SWITCH F TRANSFORMER G ISOLATION RELAY H OVERLOAD RE...

Page 11: ...o continuing product development specifications are subject to change without notice 2012 RenewAire LLC 134785_005 HE3XINHMan_Jan12 indd Revised 01 2012 www renewaire com Page 11 THIS PAGE INTENTIONAL...

Page 12: ...Blowers every time you change the filters Confirm bearings are still secure to blower shaft It should not be possible to move the blower shaft back and forth along its length Confirm blower wheel is n...

Reviews: