Continued
Item Display
Description
17
Temp. of suction pipe for indoor unit A (T
2B
A)
Current value. If the temperature is lower than
-9°C, the display shows "-9". If the temperature
is higher than 70°C, the display shows "70". If
no indoor unit is connected, the display shows
the following: “――”
18
Temp. of suction pipe for indoor unit B (T
2B
B)
19
Temp. of suction pipe for indoor unit C (T
2B
C)
20
Temp. of suction pipe for indoor unit D (T
2B
D)
21
Temp. of suction pipe for indoor unit E (T
2B
E)
22
Indoor unit A room temperature (T
1
A)
Current value. If the temperature is lower than
0°C, the display shows "0". If the temperature is
higher than 70°C, the display shows "70". If no
indoor unit is connected, the display shows the
following: “――”
23
Indoor unit B room temperature (T
1
B)
24
Indoor unit C room temperature (T
1
C)
25
Indoor unit D room temperature (T
1
D)
26
Indoor unit E room temperature (T
1
E)
27
Temp. of evaporator centre for ind. unit A (T
2
A)
Current value. If the temperature is lower than
-9°C, the display shows "-9". If the temperature
is higher than 70°C, the display shows "70". If
no indoor unit is connected, the display shows
the following: “――”
28
Temp. of evaporator centre for ind. unit B (T
2
B)
29
Temp. of evaporator centre for ind. unit C (T
2
C)
30
Temp. of evaporator centre for ind. unit D (T
2
D)
31
Temp. of evaporator centre for ind. unit E (T
2
E)
32
Temperature of condenser outlet (T3)
33
Temperature of condenser air inlet (T4)
34
Hot gas temperature in compressor outlet (T5)
The value that is displayed is between
30-129 °C. If the temperature is lower than
30°C, the display shows "30". If the temperature
is higher than 99°C, the display shows the value
without the "1". For example, if the display
shows "0.5", the measured temperature is
105°C.
35
Current consumption
The value that is displayed is a hexadecimal
number. For example, if the display shows the
value "Cd", the measured value is 205.
36
Current mains voltage
37
Degree of opening of injection valve A
Current value X 4. If the value is greater than
99, the display shows the 2nd and 3rd place of
the value. For example, if the display shows
"2.0", the degree of opening is 120x4=480
steps.)
38
Degree of opening of injection valve B
39
Degree of opening of injection valve C
40
Degree of opening of injection valve D
41
Degree of opening of injection valve E
42
Frequency limit
Not used
43
Average value for probe T2
(T2 total for all indoor units)/(total of all con-
nected indoor units)(in cooling mode:T2B, in
heating mode: T2)
44
Current speed of condenser fan motor
OFF:0, High:1, Medium:2, Medium/high:3 Low/
medium 4, Low/low:5
45
Previous error message
00 means no error messages have occurred
REMKO series SKT
34