Error P6: Inverter board safety shut-down
(part 1)
Inverter board safety shut-
down
Check the voltage between
the inverter board's P and N
terminals. Is this between
277-366 VDC (SKT 520 AT)
or 277-410 VDC (larger ver-
sions)?
NO
See the second part of
this table on the next
page!
YES
Check the electrical con-
nection between the control
board and the inverter
board. Is this OK?
NO
Correct the connection. Error recti-
fied?
YES
Is the compressor's elec-
trical connection configured
correctly?
NO
NO
Correct the connection. Error recti-
fied?
YES
Replace the inverter board.
Is the unit working nor-
mally?
NO
YES
Problem rectified.
NO
Is the condenser fan motor
working properly?
NO
See troubleshooting for malfunction
E8
YES
Replace the control board.
Is the unit working nor-
mally?
YES
NO
Replace the compressor. Is
the unit working normally?
YES
REMKO series SKT