background image

Timer buttons 
T-ON / T-OFF

 

The unit is programmed to automatically switch on or off with this button. By pressing the T-
ON / T-OFF button, the timer is activated and the time display disappears. The timer sym-
bol ON or OFF time blinks. By pressing the TEMP UP/DN button, the desired timer on or off 
time is set. Once the setting is made, the respective timer button has to be pressed again. 
The display of the indoor unit is lit up. 
If the programmed time is reached, the unit automatically switches on or off. If the indoor 
unit automatically switches on, the last mode, temperature and fan speed setting is acti-
vated. 
To disable the timer on or off function prior to its activation time, press the CANCEL button. 
The display of the indoor unit is not lit up. 

Functional process 

T-ON button 
Delayed start 

SWING button

 

The oscillating function of the air outlet fins is set with this button. To directly position the air 
outlet fins, this button must be pressed again. The swing function improves the air distribu-
tion in the room. 

Functional process 

SWING 

SWING 

SLEEPING button

 

With this button, a program is activated that increases the target temperature by 1°C after 
one hour and 2°C after two hours when the unit is in cooling mode.

 

In heating mode, the 

target temperature is decreased by 1°C after one hour and by 2°C after two hours. The dis-
play of the indoor unit is not lit up. 

Functional process 

SLEEPING 

SLEEPING 

Heating mode

 

In heating mode, you can heat the room in spring and autumn. The selected room tempera-
ture is set in 1°C increments with the TEMP UP/DN button. If the room temperature falls 1°
C below the selected target temperature, the indoor unit begins to heat the room air. If the 
room temperature exceeds the set room temperature by approx. 0.5°C, the control mecha-
nism switches heating mode off. To protect the compressor, the control mechanism only 
reactivates heating mode after 3 minutes have elapsed. 

Functional process 

HEATING MODE 

MODE 

T-OFF button 
Delayed stop 

T-ON 

TEMP UP/DN 

Delayed 
start 

T-ON 

T-OFF 

TEMP UP/DN 

T-OFF 

Delayed 
stop 

Summary of Contents for RXW 350

Page 1: ...REMKO powerful like a bear REMKO RXW 350 480 Wall units Edition GB R05 Operation Technology Spare Parts...

Page 2: ......

Page 3: ...nel 13 Installation 13 Electrical Connection 15 Wiring Diagram 15 Condensation Connection 15 Prior to Initial Operation 16 Initial Operation 16 Customer Service and Guarantee 17 Environment and Recycl...

Page 4: ...ate the unit exclusively within the permissible op erating ranges Observe surrounding temperatures Make sure that the unit is kept at a safe distance from flammable objects Ensure that no foreign obje...

Page 5: ...lect the operating mode The indoor unit has 5 modes Automatic In this mode the unit operates in cooling or heat ing mode Cooling In this mode the warm room air is cooled down to the desired temperatur...

Page 6: ...the display no longer blinks CLOCK button Functional process CLOCK CLOCK By pressing the ON OFF button the air conditioning unit is switched on and off The settings and setting values programmed befor...

Page 7: ...rature The desired room temperature is set in 1 C increments with the TEMP UP DN button If the temperature is 1 C above the set target temperature the indoor unit begins to cool the room air If the ro...

Page 8: ...is button must be pressed again The swing function improves the air distribu tion in the room Functional process SWING SWING SLEEPING button With this button a program is activated that increases the...

Page 9: ...med see CLOCK button RESET button Functional process RESET 5 sec Clock setting Shown on the display Malfunctions are shown as a code on the display of the indoor unit After the malfunction has been fi...

Page 10: ...ecured against being inadvertently switched on System Structure The indoor unit is connected to the outdoor unit with re frigerant pipes Outdoor unit Refrigerant pipes Outdoors Indoors Condenser fan S...

Page 11: ...the unit to start Polarity of batteries incorrect after replacement Is the polarity correct Insert batteries with the correct polarity Transmission distance too great reception blocked Is there a tran...

Page 12: ...lectr nominal current consumption cooling A 4 91 6 91 Electr nominal current consumption heating A 4 99 Refrigerant connection injection pipe Inches mm 1 4 6 35 Refrigerant connection suction pipe Inc...

Page 13: ...ust meet the relevant re quirements The power supply is only connected to the outdoor unit The control line to the indoor unit should be placed together with the refrigerant pipe Make sure that the el...

Page 14: ...When assembling the unit observe the bending radii of the refrigerant pipes and never bend the hose in the same place twice This may cause the pipe to become brittle or crack 4 Remove the preinstalle...

Page 15: ...fin exchanger of the indoor unit during cooling operation because tempera tures below the dew point are reached The indoor unit is equipped with a condensate collector and a condensation hose for the...

Page 16: ...a tion must be performed using the certificate and must be documented Following initial operation the operator must be trained in its operation and the initial operation log given to him Prior to Init...

Page 17: ...the guarantee becomes null and void Customer Service and Guarantee For the guarantee to be valid the purchaser or his cus tomer must completely fill out the guarantee certificate enclosed with all un...

Page 18: ...ation Name Street Postal code country city Telephone Fax Test of cooling cycle Result Visual check Setup of outdoor unit and indoor unit 5 good 4 poor Heat exchanger insulation pipes 5 good 4 poor Ele...

Page 19: ......

Page 20: ...REMKO GmbH Co KG Air Conditioning and Heating Technology D 32791 Lage Im Seelenkamp 12 D 32777 Lage P O Box 1827 Phone 49 52 32 606 0 Fax 49 52 32 606 260 E mail export remko de Internet www remko de...

Reviews: