The compressor starts a couple of minutes later 
due to the delayed start. 

Cooling operation test run 

Perform a test run for cooling operation as follows: 

1.  Switch the main switch or fuse on. 
2.  Adjust the target temperature on the indoor unit to a 

lower value than the existing room temperature us-
ing the remote control. 

3.  Switch the unit to cooling mode with the remote con-

trol. 

4.  Check that cold air is being expelled from the indoor 

unit and warm air from the outdoor unit. 

5.  During the test run, check all regulating, control and 

safety mechanisms to ensure that they are function-
ing and set properly. 

6.  Check the indoor unit’s control mechanisms using the 

functions described in the operating instructions.   

Timer, temperature settings, fan mode and dehu-
midifying mode as well as all other mode settings.

 

7. Measure overheating, outside, inside, outlet and 

evaporation temperatures and enter these values in 
the initial operation log. 

Only authorised personnel may come into contact with 
the cooling cycle. This ensures that refrigerant does not 
escape into the environment when the unit is being re-
paired. Both the refrigerant and the system parts are 
subject to special requirements for disposal. 
The refrigerant in use is a safety refrigerant. This means 
that, should damage occur, the quantities released will not 
cause injury to the respiratory systems of people and  
animals. 

Important information about recycling! 

Environment and Recycling 

*

 

Do not touch the liquid refrigerant as it can freeze the 
skin!

 

*

 

Operation/handling which does not comply with 
these instructions is prohibited!  
In cases of non-compliance, we assume no liability 
and the guarantee becomes null and void.

 

Customer Service 
and Guarantee

 

 

For the guarantee to be valid, the purchaser or his cus-
tomer must completely fill out the "

guarantee certificate

enclosed with all units and send it back to REMKO GmbH 
& Co. KG

 in a timeframe that coincides with purchase 

and initial operation. 
The units are repeatedly tested at the production site to 
ensure that they are working properly. If a malfunction 
occurs that cannot be eliminated by the operating per-
sonnel, please contact your dealer or contract partner. 

Proper use 

The indoor units have been designed and fitted exclu-
sively for operation with REMKO outdoor units belonging 
to the RKS series. 
The manufacturer assumes no liability for damage re-
sulting from non-compliance with manufacturer specifi-
cations and legal requirements, or if modifications are 
made to the units. 

Completing initial operation

 

1.  Remove the manometer and reattach all parts that 

were removed.  

Make sure that there are seals in the caps. 

2.  Complete the certificate for initial operation, famil-

iarise the operator with the system and give him the 
filled out certificate for initial operation. 

Heating operation test run 

Perform a test run for heating operation as follows: 
1.  Adjust the target temperature on the indoor unit to a 

higher value than the existing room temperature us-
ing the remote control. 

2.  Switch the unit to heating mode with the remote con-

trol. 

3.  Check that warm air is being expelled from the in-

door unit and cool air from the outdoor unit. 

4.  During the test run, check all regulating, control and 

safety mechanisms to ensure that they are function-
ing and set properly. 

5.  Check the indoor unit’s control mechanisms using the 

functions described in the operating instructions.   

Timer, temperature settings, fan mode and dehu-
midifying mode as well as all other mode settings.

 

Summary of Contents for RXW 350

Page 1: ...REMKO powerful like a bear REMKO RXW 350 480 Wall units Edition GB R05 Operation Technology Spare Parts...

Page 2: ......

Page 3: ...nel 13 Installation 13 Electrical Connection 15 Wiring Diagram 15 Condensation Connection 15 Prior to Initial Operation 16 Initial Operation 16 Customer Service and Guarantee 17 Environment and Recycl...

Page 4: ...ate the unit exclusively within the permissible op erating ranges Observe surrounding temperatures Make sure that the unit is kept at a safe distance from flammable objects Ensure that no foreign obje...

Page 5: ...lect the operating mode The indoor unit has 5 modes Automatic In this mode the unit operates in cooling or heat ing mode Cooling In this mode the warm room air is cooled down to the desired temperatur...

Page 6: ...the display no longer blinks CLOCK button Functional process CLOCK CLOCK By pressing the ON OFF button the air conditioning unit is switched on and off The settings and setting values programmed befor...

Page 7: ...rature The desired room temperature is set in 1 C increments with the TEMP UP DN button If the temperature is 1 C above the set target temperature the indoor unit begins to cool the room air If the ro...

Page 8: ...is button must be pressed again The swing function improves the air distribu tion in the room Functional process SWING SWING SLEEPING button With this button a program is activated that increases the...

Page 9: ...med see CLOCK button RESET button Functional process RESET 5 sec Clock setting Shown on the display Malfunctions are shown as a code on the display of the indoor unit After the malfunction has been fi...

Page 10: ...ecured against being inadvertently switched on System Structure The indoor unit is connected to the outdoor unit with re frigerant pipes Outdoor unit Refrigerant pipes Outdoors Indoors Condenser fan S...

Page 11: ...the unit to start Polarity of batteries incorrect after replacement Is the polarity correct Insert batteries with the correct polarity Transmission distance too great reception blocked Is there a tran...

Page 12: ...lectr nominal current consumption cooling A 4 91 6 91 Electr nominal current consumption heating A 4 99 Refrigerant connection injection pipe Inches mm 1 4 6 35 Refrigerant connection suction pipe Inc...

Page 13: ...ust meet the relevant re quirements The power supply is only connected to the outdoor unit The control line to the indoor unit should be placed together with the refrigerant pipe Make sure that the el...

Page 14: ...When assembling the unit observe the bending radii of the refrigerant pipes and never bend the hose in the same place twice This may cause the pipe to become brittle or crack 4 Remove the preinstalle...

Page 15: ...fin exchanger of the indoor unit during cooling operation because tempera tures below the dew point are reached The indoor unit is equipped with a condensate collector and a condensation hose for the...

Page 16: ...a tion must be performed using the certificate and must be documented Following initial operation the operator must be trained in its operation and the initial operation log given to him Prior to Init...

Page 17: ...the guarantee becomes null and void Customer Service and Guarantee For the guarantee to be valid the purchaser or his cus tomer must completely fill out the guarantee certificate enclosed with all un...

Page 18: ...ation Name Street Postal code country city Telephone Fax Test of cooling cycle Result Visual check Setup of outdoor unit and indoor unit 5 good 4 poor Heat exchanger insulation pipes 5 good 4 poor Ele...

Page 19: ......

Page 20: ...REMKO GmbH Co KG Air Conditioning and Heating Technology D 32791 Lage Im Seelenkamp 12 D 32777 Lage P O Box 1827 Phone 49 52 32 606 0 Fax 49 52 32 606 260 E mail export remko de Internet www remko de...

Reviews: