background image

14 

Attaching the wall mount

 

The units must be attached with suitable screws and 
dowels. The attachment points are displayed in the fol-
lowing figure.

 

Lead-through options 

Prior to installation, take a look at the various options 
for lead-throughs of the refrigerant and condensation 
pipes and control lines (see figure below). 

1  Opening on the wall rear 

2  Opening through the wall right 

3  Opening through the wall left 

4  Opening on the wall left 

Assembling the indoor unit

 

Install the indoor unit as follows: 
1.  The required pipe diameters are provided in the 

"Technical Data” table of the outdoor unit. 

Only use refrigerant pipes with refrigerator quality.

 

2.  Decide which drainage option you want to use for 

the indoor unit and cut the refrigerant pipes accord-
ingly. 

Attachment points 

512 

215 

430 

45 

168 

Connecting the refrigerant pipes

 

 

 

RWK 260 

RWK 350 

RKS 435 H  

Injection pipe 

1/4“ (6.35) 

Suction pipe 

1/2“ (12.7) 

RKS 448 H  

Injection pipe 

1/4“ (6.35) 

Suction pipe 

1/2“ (12.7) 

13. Lay the refrigerant pipes from the indoor unit to the 

outdoor unit. 

14. Connect the refrigerant pipes to the outdoor unit as 

described in the operating instructions of the out-
door unit. 

3.  When assembling the unit, observe the bending radii 

of the refrigerant pipes and never bend the hose in 
the same place twice. 

This may cause the pipe to 

become brittle or crack

4.  Remove the preinstalled swivel nuts of the units. 
5.  Keep in mind that the indoor units have been filled 

with dry nitrogen as a sealant at the factory. 

 

The pressurised nitrogen is released when the 
swivel nuts are loosened.

 

6.  When assembling the unit, only use tools suitable 

for low temperature ranges. 

7.  Work with the pipes as described in the operating 

instructions of the outdoor units.  

8.  Insulate the installed refrigerant pipes including the 

connector against heat. 

9.  Only use insulation hoses sealed against diffusion 

that are suitable for this temperature range. 

10. If you have selected option 2 or 4 (opening through 

the wall), guide the condensation water and control 
line through the wall lead-through to the indoor unit. 

If you also need a condensation pump, it must be 
installed beforehand.

 

11. If, due to structural design conditions, it is not possi-

ble to guide the condensation pipe through as well, 
make sure that the condensation can drain freely at 
all times. 

12. Hang the indoor unit leaning slightly to the back in 

the previously assembled wall mount and press the 
bottom of the unit into the mount.   

Do not damage the pipes and ensure that they are 
in the correct position

Summary of Contents for RXW 350

Page 1: ...REMKO powerful like a bear REMKO RXW 350 480 Wall units Edition GB R05 Operation Technology Spare Parts...

Page 2: ......

Page 3: ...nel 13 Installation 13 Electrical Connection 15 Wiring Diagram 15 Condensation Connection 15 Prior to Initial Operation 16 Initial Operation 16 Customer Service and Guarantee 17 Environment and Recycl...

Page 4: ...ate the unit exclusively within the permissible op erating ranges Observe surrounding temperatures Make sure that the unit is kept at a safe distance from flammable objects Ensure that no foreign obje...

Page 5: ...lect the operating mode The indoor unit has 5 modes Automatic In this mode the unit operates in cooling or heat ing mode Cooling In this mode the warm room air is cooled down to the desired temperatur...

Page 6: ...the display no longer blinks CLOCK button Functional process CLOCK CLOCK By pressing the ON OFF button the air conditioning unit is switched on and off The settings and setting values programmed befor...

Page 7: ...rature The desired room temperature is set in 1 C increments with the TEMP UP DN button If the temperature is 1 C above the set target temperature the indoor unit begins to cool the room air If the ro...

Page 8: ...is button must be pressed again The swing function improves the air distribu tion in the room Functional process SWING SWING SLEEPING button With this button a program is activated that increases the...

Page 9: ...med see CLOCK button RESET button Functional process RESET 5 sec Clock setting Shown on the display Malfunctions are shown as a code on the display of the indoor unit After the malfunction has been fi...

Page 10: ...ecured against being inadvertently switched on System Structure The indoor unit is connected to the outdoor unit with re frigerant pipes Outdoor unit Refrigerant pipes Outdoors Indoors Condenser fan S...

Page 11: ...the unit to start Polarity of batteries incorrect after replacement Is the polarity correct Insert batteries with the correct polarity Transmission distance too great reception blocked Is there a tran...

Page 12: ...lectr nominal current consumption cooling A 4 91 6 91 Electr nominal current consumption heating A 4 99 Refrigerant connection injection pipe Inches mm 1 4 6 35 Refrigerant connection suction pipe Inc...

Page 13: ...ust meet the relevant re quirements The power supply is only connected to the outdoor unit The control line to the indoor unit should be placed together with the refrigerant pipe Make sure that the el...

Page 14: ...When assembling the unit observe the bending radii of the refrigerant pipes and never bend the hose in the same place twice This may cause the pipe to become brittle or crack 4 Remove the preinstalle...

Page 15: ...fin exchanger of the indoor unit during cooling operation because tempera tures below the dew point are reached The indoor unit is equipped with a condensate collector and a condensation hose for the...

Page 16: ...a tion must be performed using the certificate and must be documented Following initial operation the operator must be trained in its operation and the initial operation log given to him Prior to Init...

Page 17: ...the guarantee becomes null and void Customer Service and Guarantee For the guarantee to be valid the purchaser or his cus tomer must completely fill out the guarantee certificate enclosed with all un...

Page 18: ...ation Name Street Postal code country city Telephone Fax Test of cooling cycle Result Visual check Setup of outdoor unit and indoor unit 5 good 4 poor Heat exchanger insulation pipes 5 good 4 poor Ele...

Page 19: ......

Page 20: ...REMKO GmbH Co KG Air Conditioning and Heating Technology D 32791 Lage Im Seelenkamp 12 D 32777 Lage P O Box 1827 Phone 49 52 32 606 0 Fax 49 52 32 606 260 E mail export remko de Internet www remko de...

Reviews: