41
8 ELECTRICAL
INSTALLATION
8.1 General
The Remeha Quinta 45 and 65 is supplied as standard with electronic control and
flame ionisation safety controls with a specially designed microprocessor at the heart
of the control system.
8.2 Specifications
8.2.1 Electrical
supply
The Remeha Quinta 45 and 65 must have a permanent 230V-50Hz single phase sup-
ply rated at 6.3 Amps. The control unit is not phase / neutral sensitive.
8.2.2 Control
box
Manufacture:
Gasmodul
Model:
MCBA 1461 D
Supply voltage:
230 V/50 Hz
Electrical rating:
10 VA
Pre-purge time:
3 seconds
Post-purge time:
10 seconds
Safety time:
3 seconds
Anti-hunting time:
150 seconds
Pump run on (HTG):
1 - 15 minutes
Pump run on (DHW):
5 minutes
8.2.3 Fuse
specification
The boiler is protected by fuses:
- on the main power supply located in the euro connector socket rated at 6.3 amps
(slow acting). Spare fuse is supplied - located in the euro connector socket
- control circuit 230 Volt - located on the Gasmodul control box, ref. F1 rated at 2
amps (fast acting)
- control circuit 24 Volt dc- located on the Gasmodul control box, ref. F2 rated at 4
amps (slow acting)
Spare fuses are supplied - located on the Gasmodul control box cover.
7.6 Modular systems
The Quinta series of boilers are idealy suited for modular applications. Kits for up to 5
units are available from Broag. Please see separate leaflet for more details.