35
Example:
Quinta 45, total length 10 m, 2 bends 90°.
80 mm: 10 m + 2 x 2 = 14 m < 16 m:
flue OK
.
Note: If the design parameters are outside the values shown in the above table or
there is any doubt over the flue system, please contact our technical department for
calculation to be undertaken.
7.3.6 Different pressure zones
Fig. 09
Different pressure zones
04W4H7900004
Bird guard
Flue outlet
Air inlet
The Remeha Quinta boilers (twin connection only) are capable of operating with the air
inlet and flue outlet in different pressure zones (CLV System).
There are some restrictions to the flue/air inlet lengths and max height differences
which have been detailed in
Fig. 09.
Maximum total length of air inlet and flue gas outlet pipework (L) as detailed in table
below (calculation based on using 1 x 90 bend).
Quinta 45
80 mm
Quinta 65
100 mm
max eq. Length
m
28
18
eq. Length bend 45°
m
1.2
1.4
eq. Length bend 90°
m
4
4.9
Table 15
Calculation data different pressure zones