3.2 Technical data
Boiler type
Quinta 45
Quinta 65
General
Casing Colour
BS RAL
9016
Boiler control options (External input)
(Two wire control)
On/off, High/low,
Analog 0-10V
Communicating Modulation
Nominal output (80/60ºC)
kW
8.0 – 40.0
12.0 – 61.0
Nominal output (40/30ºC)
kW
8.9 – 43.0
13.3 – 65.0
Nominal input (GCV / Hs)
kW
9.1 – 45.7
13.6 – 68.8
Nominal input (NCV / Hi)
kW
8.2 – 41.2
12.2 – 62.0
Weight dry
kg
57
64
Noise level at 1 m from boiler
dB(A)
<48
Gas- and flue details
Min/Max Inlet pressure natural gas
mbar
17 – 30
17 – 30
Min/Max Inlet pressure propane
mbar
37 - 50
37 - 50
Gas consumption (natural gas)
m
3
/h
1.0 – 5.0
1.5 – 7.5
Gas consumption (propane)
m
3
/h
0.3 - 1.7
0.5 - 2.5
NO
x
-emission
mg/kWh
<45
NO
x
-emission (O
2
= 0%, dry)
ppm
<25
Residual fan duty
Pa
150
100
Mass flue rate
kg/h
14 - 69
21 - 104
Classification due to discharging flue gases
B23, C13, C33, C43, C53,
C63, C83
Water side
Maximum flow temperature
ºC
100 (110)
Operating flow temperature
ºC
20 - 90
Operating pressure min. (open vented)
bar
0.3
Operating pressure min. (pressurised)
bar
0.8
Operating pressure max.
bar
3.5
Water contents
ltr
5.5
6.5
Water resistance at 11 °C
∆
t
mbar
300
430
Water resistance at 20 °C
∆
t
mbar
90
130