Reliance Water Heaters RUF 100 199 Installation And Operation Manual Download Page 7

7

For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters installed 

in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by 

the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the 

area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

 

INSTALLATION OF CARBON MONOXIDE DETECTORS

  At the time of installation of the side wall horizontal vented gas 

fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm 

and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber 

or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each 

additional level of the dwelling, building or structure served by the sidewall horizontal vented gas fueled equipment. It shall 

be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard 

wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired 

carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall 

have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a battery 

operated carbon monoxide detector with an alarm shall be installed.

APPROVED CARBON MONOXIDE DETECTORS

  Each carbon monoxide detector as required in accordance with the above 

provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and CSA certified. 

SIGNAGE 

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum 

height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating 

appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, 

“GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

INSPECTION 

 The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the 

installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance 

with the provisions of 248 CMR 5.08(2)(a) 1 through 4. 

EXEMPTIONS

: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: 

1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 

as adopted by the Board; and 

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the 

dwelling, building, or structure used in whole or in part for residential purposes. 

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED

 When the manufacturer of Product  

Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with 

the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall 

include:

1. Detailed instructions for the installation of the venting system design or the venting system components; and

2. A complete parts list for the venting system design or venting system. 

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED

  When the manufacturer of 

a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, 

but identifies “special venting systems,” the following requirements shall be satisfied by the manufacturer:

1.  The  referenced  “special  venting  system”  instructions  shall  be  included  with  the  appliance  or  equipment  installation

 

 instructions; and 

2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a 

parts list and detailed installation instructions. 

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting 

instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or 

 

equipment at the completion of the installation. 

INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS

Summary of Contents for RUF 100 199

Page 1: ...RVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store...

Page 2: ...wed in all cases Authorities having jurisdiction should be consulted before installations are made In the absence of local codes the installation must comply with the current editions of the National...

Page 3: ...ch are not listed in this section WATER TEMPERATURE CONTROL TABLE OF CONTENTS ROUGH IN DIMENSIONS 2 FOREWORD 2 FEATURES 3 4 Water Temperature Control 3 High Limit Switch E C O 4 Dishwashing Machine Re...

Page 4: ...pa and 173 Kpa Flow pressures above 25 pounds per square inch 173 Kpa or below 15 pounds per square inch 103 Kpa will result in improperly sanitized dishes Where pressures are high a water pressure re...

Page 5: ...sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detec...

Page 6: ...ER ISOLATION PIPE HANGERS ARE USED THIS PREVENTS ANY VIBRATIONS FROM BEING TRANSMITTED INTO THE LIVING SPACES HARD WATER Where hard water conditions exist water softening or the threshold type of wate...

Page 7: ...tally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The st...

Page 8: ...INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS RECOMMENDED FIGURE 6 U S DIRECT VENT CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE...

Page 9: ...1 The intake vent terminal and the exhaust vent terminal must terminate on the same exterior wall and must be located at a minimum of 24 61cm from the vertical centerline of the exhaust vent terminal...

Page 10: ...the same side of roof 4 The center line of the intake vent termination and the center line of the exhaust vent termination must be no closer than 24 61cm 5 The intake vent terminal and the exhaust ve...

Page 11: ...r ABS cement to join PVC or CPVC pipe and fittings SAFETY PRECAUTION PRIMERS AND CEMENTS ARE EXTREMELY FLAMMABLE AND MUST NOT BE STORED OR USED NEAR HEAT OR OPEN FLAME ALSO USE ONLY IN A WELL VENTILAT...

Page 12: ...s that the electrical contacts on this air flow switch be open before it will allow the blower to come on BLOCKED OUTLET PROVER SWITCH SEE FIGURE 12 The Blocked Outlet Prover Switch is set up to shut...

Page 13: ...T BE READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING CONDITIONS INSTALL IN ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS REFER TO THE NATIONAL FUEL GAS CODE FIGURE 13 CONNECTION OF GAS PIPE...

Page 14: ...This heater is equipped with an approved temperature and pressure relief valve ASME ratings cover pressure relief CSA ratings cover release rate with temperature actuation FOR SAFE OPERATION OF THE WA...

Page 15: ...al Supply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit 3 This unit may never be connected to any existing heating system or component s previously...

Page 16: ...he desktop screen if there are no active fault or alert conditions An example of this screen is shown to the right The first temperature on this screen is the temperature of the water inside the tank...

Page 17: ...u DISPLAY ACTION From the Main Menu press Select to enter the Temperatures screen DISPLAY 2 Operating States In the main desktop screen there are some specific Operating States that are indicated on t...

Page 18: ...that can occur during operation These are Alerts and Faults Alerts This is a non safety related condition that the control has detected that may cause the water heater to operate in a less than optima...

Page 19: ...on about the water heater and the current status of specific conditions can be found INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIE...

Page 20: ...he unit is installed and filled with water and the inlet pressures confirmed simply turn the switch on and observe operation Cycle the unit off and on several times to ensure proper operation OPERATIN...

Page 21: ...45kpa Nominal Gas Supply Pressure 7 0 WC 1 74Kpa 11 0 WC 2 74Kpa Minimum Gas Supply Pressure 4 8 WC 1 18Kpa 8 5 WC 2 08 Kpa Manifold Pressure 0 WC OKpa 0 WC OKpa HIGH ALTITUDE INSTALLATIONS WARNING T...

Page 22: ...GAS TO APPLIANCE FOR YOUR SAFETY READ BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life OP...

Page 23: ...onnect switch 2 Close the cold water inlet valve to heater 3 Open a nearby hot water faucet to vent the system 4 Open the heater drain valve 5 If the heater is being drained for an extended shutdown i...

Page 24: ...sly it may be due to thermal expansion of water in a closed water supply system or it may be due to a faulty relief valve Thermal expansion is the normal response of water when it is heated In a close...

Page 25: ...OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED NOTE CONNECT RETURN LINE FROM HOT WATER CIRCULATING LOOP IF USED TO COLD WATER INLET LINE PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES I...

Page 26: ...PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW P...

Page 27: ...TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN...

Page 28: ...TH LOCAL CODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER...

Page 29: ...HOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 5 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Page 30: ...nits with the higher water flow may have a shortened life Dimensions shown are for minimum space occupied by the water heaters assemblies Space for the venting system and unit servicing must be added...

Page 31: ...er drain valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the heater and piping 3 If the outlet of the rel...

Page 32: ...at a positive manifold pressure reading of approximately 1 5 38 kPa W C is normal during the prepurge portion of the ignition cycle due to the location of the gas orifice MOTOR RUNS BURNER LIGHTS MOME...

Page 33: ...33 NOTES...

Page 34: ...34 NOTES...

Page 35: ...ranty shall be void and shall have no effect if the design or structure of the water heater is or is attempted to be modified or altered in any way including but not limited to by attaching non compan...

Page 36: ...36...

Reviews: