Reliance Water Heaters RUF 100 199 Installation And Operation Manual Download Page 12

12

LOW GAS PRESSURE SWITCH

(SEE FIGURE 12)

The Low Gas Switch (LGS) is a single-pole, normally open pressure switch 

that will close its contacts when a rising pressure of 5.0 in. (1.25Kpa)  W.C. 

is encountered. The contacts will open when the pressure falls below the 

fixed  set  point  of  4.8"WC  (1.18Kpa)  for  natural  gas  models  and  8.5"WC 

(2.08Kpa) for propane models. The LGS monitors the gas supply pressure 

to the  heater. If the gas supply falls below 5.0 in. (1.25Kpa) W.C., the main 

burner is extinguished (if heater is running) or the heater will not start up.

ON/OFF SWITCH

The ON/OFF Switch is a single-pole, single-throw rocker switch. This switch 

provides 120V from the line source to the heater. 

 CAUTION

THE  WATER  HEATER  IS  POLARITY  SENSITIVE.  BEFORE APPLYING 

ELECTRICITY TO THIS HEATER BE CERTAIN THAT SUPPLY NEUTRAL 

WIRE TO GROUND CHECK INDICATES ZERO VOLTAGE.

HOT SURFACE IGNITER

The  Hot  Surface  Igniter  is  a  device  that  ignites  the  main  burner  by  high 

temperature (>1800°F or >982°C). When 120VAC is applied to the igniter, 

sufficient heat is generated to ignite the main burner. Although improvements 

have been made to strengthen the igniter, it is still fragile and care must be 

taken when handling the igniter to prevent breakage.

GAS PIPING

Contact your local gas service company to ensure that adequate gas service 

is available and to review applicable installation codes for your area.

Size the main gas line in accordance with Table 3. The figures shown are 

for straight lengths of pipe at 0.5" (125Pa) W.C. pressure drop, which is 

considered normal for low pressure systems Note that fittings such as elbows 

and tees will add to the pipe pressure drop.

 CAUTION

DO NOT USE FLEXIBLE GAS PIPING.

TABLE 3. MAXIMUM CAPACITY OF PIPE IN CUBIC FEET 

        OF GAS PER HOUR

(Based upon a Pressure Drop of 0.5") Water Column and 0.6 Specific 

Gravity Gas and max. gas pressure of 0.5 psig)

CONTROLS AND SWITCHES

All models are provided with four pressure switches. These switches are 

essential to the safe and proper operation of the unit. All switches are wired 

in series. The controller is set up to shut the unit down whenever there is a 

failure of any of the switches. It is important to understand the purpose of 

each switch. 

FIGURE 12.

BLOWER PROVER SWITCH

(SEE FIGURE 12)

The Blower Prover Switch is provided on the heater to verify that the fan 
is operating. It is a positive pressure switch whose electrical contacts are 
normally  open.  When  the  fan  increases  the  pressure  in  the  burner,  the 
pressure switch will allow the electrical contacts to close. The pressure switch 
is connected to the burner tap by a piece of tygon tubing. This tubing must 
be connected in order for the switch to change the electrical contacts. The 
controller requires that the electrical contacts on this air flow switch be open 
before it will allow the blower to come on.

BLOCKED OUTLET PROVER SWITCH 

(SEE FIGURE 12)

The Blocked Outlet Prover Switch is set up to shut the unit off when a build-up 
of positive pressure in the exhaust vent pipe occurs. This switch is a positive 
pressure switch that requires an increase in pressure to change the electrical 
contacts from normally closed to open. When this switch prevents the unit 
from igniting, most likely the exhaust is blocked by some means Check to 
see if the condensate is allowed to flow freely from the exhaust elbow and 
for obstructions in the exhaust venting and exhaust vent terminal. Also verify 
that there is no more than fifty equivalent feet (15.2 m)  of three inch PVC 
vent pipe on the exhaust.

BLOCKED INLET PROVER SWITCH 

(SEE FIGURE 12)

The Blocked Inlet Prover Switch is set up to shut the unit off when a build-up 
of negative pressure in the intake vent pipe occurs. This switch is a negative 
pressure switch that requires an increase in negative pressure to change the 
electrical contacts from normally closed to open. The switch is connected 
to the pressure tap on the PVC flange connected to the inlet of the blower. 
When this switch prevents the unit from igniting, most likely the intake is 
blocked by some means. Check to see if there is no more than fifty equivalent 
feet (15.2 m) of three inch PVC vent pipe on the intake. Also verify that the 
intake and intake vent terminal is free of obstructions that may prevent air 
from entering the unit.

   LENGTH   

 

 NORMAL IRON PIPE SIZES (INCHES) 

 

 

IN 

 

 

     INPUT IN THOUSANDS BTU/HR

 

 FEET

 

1/2"  3/4"  1"  1 1/4"  1 1/2"  2"  2 1/2" 

3" 

4"

 

10

 

175  360  680  1400  2100  3960  6300  11000  23000

 

20

 

120  250  485  950  1460  2750  4360  7700  15800

 

30

 

97  200  375  770 

1180  2200  3520  6250  12800

 

40

 

82  170  320  660 

990  1900  3000  5300  10900

 

50

 

73  151  285  580 

900  1680  2650  4750  9700

 

60

 

66  138  260  530 

810  1520  2400  4300  8800

 

70

 

61  125  240  490 

750  1400  2250  3900  8100

 

80

 

57  118  220  460 

690  1300  2050  3700  7500

 

90

 

53  110  205  430 

650  1220  1950  3450  7200

 

100

 

50  103  195  400 

620  1150  1850  3250  6700

 

125

 

44 

93  175  360 

550  1020  1650  2950  6000

 

150

 

40 

84  160  325 

500  950  1500  2650  5500

 

175

 

37 

77  145  300 

460  850  1370  2450  5000

 

200

 

35 

72  135  280 

430  800  1280  2280  4600

   LENGTH   

 

 NORMAL IRON PIPE SIZES (INCHES)

   IN 

 

 

                   INPUT IN KW

   METERS  1/2"  3/4"  1"  1 1/4"  1 1/2"  2"  2 1/2" 

3" 

4"

 

3.0

 

51  105  199  410 

615  1160  1845  3221  6735

 

6.1

 

35 

73  142  278 

428  805  1277  2255  4626

 

9.1

 

28 

59  110  225 

346  644  1031  1830  3748

 

12.2

 

24 

50 

94 

193 

290  556  878  1552  3192

 

15.2

 

21 

44 

83 

170 

264  492  776  1391  2840

 

18.3

 

19 

40 

76 

155 

237  445  703  1259  2577

 

21.3

 

18 

37 

70 

143 

220  410  659 

1142  2372

  24.4

 

17 

35 

64 

135 

202  381  600  1083  2196

 

27.4

 

16 

32 

60 

126 

190  357  571  1010  2108

 

30.5

 

15 

30 

57 

117 

182  337  542 

952  1962

 

38.1

 

13 

27 

51 

105 

161  299  483 

864  1757

 

45.7

 

12 

25 

47 

95 

146  278  439 

776  1610

 

53.3

 

11 

23 

42 

88 

135  249  401 

717  1464

 

61.0

 

10 

21 

40 

82 

126  234  375 

688  1347

Summary of Contents for RUF 100 199

Page 1: ...RVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store...

Page 2: ...wed in all cases Authorities having jurisdiction should be consulted before installations are made In the absence of local codes the installation must comply with the current editions of the National...

Page 3: ...ch are not listed in this section WATER TEMPERATURE CONTROL TABLE OF CONTENTS ROUGH IN DIMENSIONS 2 FOREWORD 2 FEATURES 3 4 Water Temperature Control 3 High Limit Switch E C O 4 Dishwashing Machine Re...

Page 4: ...pa and 173 Kpa Flow pressures above 25 pounds per square inch 173 Kpa or below 15 pounds per square inch 103 Kpa will result in improperly sanitized dishes Where pressures are high a water pressure re...

Page 5: ...sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detec...

Page 6: ...ER ISOLATION PIPE HANGERS ARE USED THIS PREVENTS ANY VIBRATIONS FROM BEING TRANSMITTED INTO THE LIVING SPACES HARD WATER Where hard water conditions exist water softening or the threshold type of wate...

Page 7: ...tally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The st...

Page 8: ...INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS RECOMMENDED FIGURE 6 U S DIRECT VENT CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE...

Page 9: ...1 The intake vent terminal and the exhaust vent terminal must terminate on the same exterior wall and must be located at a minimum of 24 61cm from the vertical centerline of the exhaust vent terminal...

Page 10: ...the same side of roof 4 The center line of the intake vent termination and the center line of the exhaust vent termination must be no closer than 24 61cm 5 The intake vent terminal and the exhaust ve...

Page 11: ...r ABS cement to join PVC or CPVC pipe and fittings SAFETY PRECAUTION PRIMERS AND CEMENTS ARE EXTREMELY FLAMMABLE AND MUST NOT BE STORED OR USED NEAR HEAT OR OPEN FLAME ALSO USE ONLY IN A WELL VENTILAT...

Page 12: ...s that the electrical contacts on this air flow switch be open before it will allow the blower to come on BLOCKED OUTLET PROVER SWITCH SEE FIGURE 12 The Blocked Outlet Prover Switch is set up to shut...

Page 13: ...T BE READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING CONDITIONS INSTALL IN ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS REFER TO THE NATIONAL FUEL GAS CODE FIGURE 13 CONNECTION OF GAS PIPE...

Page 14: ...This heater is equipped with an approved temperature and pressure relief valve ASME ratings cover pressure relief CSA ratings cover release rate with temperature actuation FOR SAFE OPERATION OF THE WA...

Page 15: ...al Supply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit 3 This unit may never be connected to any existing heating system or component s previously...

Page 16: ...he desktop screen if there are no active fault or alert conditions An example of this screen is shown to the right The first temperature on this screen is the temperature of the water inside the tank...

Page 17: ...u DISPLAY ACTION From the Main Menu press Select to enter the Temperatures screen DISPLAY 2 Operating States In the main desktop screen there are some specific Operating States that are indicated on t...

Page 18: ...that can occur during operation These are Alerts and Faults Alerts This is a non safety related condition that the control has detected that may cause the water heater to operate in a less than optima...

Page 19: ...on about the water heater and the current status of specific conditions can be found INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIE...

Page 20: ...he unit is installed and filled with water and the inlet pressures confirmed simply turn the switch on and observe operation Cycle the unit off and on several times to ensure proper operation OPERATIN...

Page 21: ...45kpa Nominal Gas Supply Pressure 7 0 WC 1 74Kpa 11 0 WC 2 74Kpa Minimum Gas Supply Pressure 4 8 WC 1 18Kpa 8 5 WC 2 08 Kpa Manifold Pressure 0 WC OKpa 0 WC OKpa HIGH ALTITUDE INSTALLATIONS WARNING T...

Page 22: ...GAS TO APPLIANCE FOR YOUR SAFETY READ BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life OP...

Page 23: ...onnect switch 2 Close the cold water inlet valve to heater 3 Open a nearby hot water faucet to vent the system 4 Open the heater drain valve 5 If the heater is being drained for an extended shutdown i...

Page 24: ...sly it may be due to thermal expansion of water in a closed water supply system or it may be due to a faulty relief valve Thermal expansion is the normal response of water when it is heated In a close...

Page 25: ...OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED NOTE CONNECT RETURN LINE FROM HOT WATER CIRCULATING LOOP IF USED TO COLD WATER INLET LINE PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES I...

Page 26: ...PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW P...

Page 27: ...TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN...

Page 28: ...TH LOCAL CODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER...

Page 29: ...HOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 5 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Page 30: ...nits with the higher water flow may have a shortened life Dimensions shown are for minimum space occupied by the water heaters assemblies Space for the venting system and unit servicing must be added...

Page 31: ...er drain valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the heater and piping 3 If the outlet of the rel...

Page 32: ...at a positive manifold pressure reading of approximately 1 5 38 kPa W C is normal during the prepurge portion of the ignition cycle due to the location of the gas orifice MOTOR RUNS BURNER LIGHTS MOME...

Page 33: ...33 NOTES...

Page 34: ...34 NOTES...

Page 35: ...ranty shall be void and shall have no effect if the design or structure of the water heater is or is attempted to be modified or altered in any way including but not limited to by attaching non compan...

Page 36: ...36...

Reviews: