Reliance Water Heaters RUF 100 199 Installation And Operation Manual Download Page 31

31

CHECKLIST AND SERVICE INFORMATION

IMPORTANT

The installer may be able to observe and correct certain problems which 

might  arise  when  the  unit  is  put  into  operation  or  when  it  is  re-fired 

after a prolonged shutdown. HOWEVER, it is recommended that only 

qualified servicemen, using appropriate test equipment, be allowed to 

service the heater.

BE SURE TO TURN OFF THE ELECTRICITY WHENEVER POSSIBLE OR 

APPROPRIATE WHILE CHECKING EQUIPMENT.

 WARNING

FAILURE  TO  FOLLOW  THESE  INSTRUCTIONS  CAN  RESULT  IN 

SERIOUS PERSONAL INJURY OR DEATH.

CAUTION:    LABEL ALL  WIRES  PRIOR TO  DISCONNECTION  WHEN 

SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER 

AND DANGEROUS OPERATION. 

VERIFY PROPER OPERATION AFTER SERVICING.

BURNER OPERATIONAL PROBLEMS

  1.  Refer to TROUBLESHOOTING.

NOT ENOUGH OR NO HOT WATER

  1.  Be certain the electrical disconnect switch serving the water heater  

is in the ON position.

  2.  Check the fuses.

 

•  The electrical disconnect switch usually contains fuses.

  3.  The capacity of the heater may have been exceeded by a large demand 

for hot water.

 

•  Large  demands  require  a  recovery  period  to  restore  water 

temperature.

  4.  Colder incoming water temperature will lengthen the time required to 

heat water to the desired temperature.

 

•  If the heater was installed when incoming water temperature was  

warm, colder water creates the effect of less hot water.

  5.  Look for hot water wastage and leaking or open hot water faucets.

  6.  Sediment or lime scale may be affecting water heater operation.  Refer 

to MAINTENANCE for details.

  7.  Burner may not be firing at proper rate.

 

•  Check gas pressure. Adjust to obtain required manifold pressure.

  8.  Burner fan wheel may be dirty.

 

•  Clean fan wheel with a stiff brush.

  9.  Condensate hose may be blocked where it connects to the exhaust 

elbow.

 

•  Verify the condensate drains from the unit without restriction.

WATER IS TOO HOT

  1.  Refer to WATER TEMPERATURE CONTROL.

WATER HEATER MAKES SOUNDS

  1.  Sediment or lime scale accumulations cause rumbling and pounding 

noises when the heater is operating.

 

•  The sounds are normal, however, the tank bottom should be cleaned.  

Refer to MAINTENANCE for details.

  2. Some of the electrical components of the water heater make sounds 

which are normal.

 

•  Contacts click or snap as the heater starts and stops.

 

•  Transformers often hum.

WATER LEAKAGE IS SUSPECTED

  1. Check to see if the water heater drain valve is tightly closed. Also    

check the cleanout opening for leakage.

  2. The apparent leakage may be condensation which forms on cool    

  surfaces of the heater and piping.

  3. If the outlet of the relief valve is leaking it may represent:

 

•  Excessive water pressure.

 

•  Excessive water temperature.

 

•  Faulty relief valve.

Excessive water pressure is the most common cause of relief valve leakage. 

It is often caused by a “closed system”. If a check valve is in the inlet system 

it will not permit the expanded hot water volume to equalize pressure with 

the main. The relief valve must release this water or the water heater or 

plumbing system will be damaged. Refer to MAINTENANCE-RELIEF VALVE 

section in this manual.

When such a condition is encountered, local codes or inspection agency 

should be consulted to determine which system is acceptable in your area.  

See CLOSED SYSTEM section in this manual also.

TROUBLE-SHOOTING

1.  Verify that the allowable vent length has not been exceeded and that the 

blower inlet screen has been removed if direct venting.

2.  Verify that the condensation, which WILL be present in the heater and 

 

exhaust vent, will drain.

3.  Check supply wire polarity - hot to hot and neutral to neutral and no 

 

"stray" current in neutral.

4.  Heater is properly grounded.

Checking these four (4) items first will often result in a timely solution to the 

service call.

 WARNING

JUMPING  OUT  COMPONENTS  AND/OR  CIRCUITS  DURING 

TROUBLESHOOTING  CAN  CAUSE  SERIOUS  PROBLEMS  WITH THE 

UNIT’S OPERATING SEQUENCE AND IGNITION SAFETY. IF YOU DO 

NOT HAVE THE PROPER TEST EQUIPMENT, I.E. A VOLT-OHM METER 

AND A MICROAMMETER, DO NOT ATTEMPT TO TROUBLESHOOT OR 

REPAIR STATE EQUIPMENT.

ALTERING  THE  CONTROLLER AND/OR  CONTROLLER  WIRING  IN 

ANY WAY COULD RESULT IN INTERNAL DAMAGE TO THE MODULE 

CIRCUITS, POSSIBLY ALTERING THE IGNITION SEQUENCE ALLOWING 

GAS VALVES TO OPEN BEFORE THE HOT SURFACE IGNITER IS UP TO 

IGNITION TEMPERATURE.

NOTE:  ANY BYPASS OR ALTERATION OF THE UNITS SAFETIES WILL 

RESULT IN VOIDING THE APPLIANCE WARRANTY.

Before performing any troubleshooting familiarize yourself with the particular 

appliance.

Refer  to  the  connection  diagram  located  on  page  15  before 

continuing.

Make sure the appliance is connected to a 120V AC power supply, manual 

gas valve is in the ON position, and all electrical connections are secure 

before continuing to troubleshoot this appliance.

 

CAUTION

THE  WATER  HEATER  IS  POLARITY  SENSITIVE.  BEFORE APPLYING 

ELECTRICITY TO THIS HEATER BE CERTAIN THAT SUPPLY HEATED 

WIRE TO GROUND CHECK INDICATES ZERO VOLTAGE.

Summary of Contents for RUF 100 199

Page 1: ...RVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store...

Page 2: ...wed in all cases Authorities having jurisdiction should be consulted before installations are made In the absence of local codes the installation must comply with the current editions of the National...

Page 3: ...ch are not listed in this section WATER TEMPERATURE CONTROL TABLE OF CONTENTS ROUGH IN DIMENSIONS 2 FOREWORD 2 FEATURES 3 4 Water Temperature Control 3 High Limit Switch E C O 4 Dishwashing Machine Re...

Page 4: ...pa and 173 Kpa Flow pressures above 25 pounds per square inch 173 Kpa or below 15 pounds per square inch 103 Kpa will result in improperly sanitized dishes Where pressures are high a water pressure re...

Page 5: ...sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detec...

Page 6: ...ER ISOLATION PIPE HANGERS ARE USED THIS PREVENTS ANY VIBRATIONS FROM BEING TRANSMITTED INTO THE LIVING SPACES HARD WATER Where hard water conditions exist water softening or the threshold type of wate...

Page 7: ...tally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The st...

Page 8: ...INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS RECOMMENDED FIGURE 6 U S DIRECT VENT CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE...

Page 9: ...1 The intake vent terminal and the exhaust vent terminal must terminate on the same exterior wall and must be located at a minimum of 24 61cm from the vertical centerline of the exhaust vent terminal...

Page 10: ...the same side of roof 4 The center line of the intake vent termination and the center line of the exhaust vent termination must be no closer than 24 61cm 5 The intake vent terminal and the exhaust ve...

Page 11: ...r ABS cement to join PVC or CPVC pipe and fittings SAFETY PRECAUTION PRIMERS AND CEMENTS ARE EXTREMELY FLAMMABLE AND MUST NOT BE STORED OR USED NEAR HEAT OR OPEN FLAME ALSO USE ONLY IN A WELL VENTILAT...

Page 12: ...s that the electrical contacts on this air flow switch be open before it will allow the blower to come on BLOCKED OUTLET PROVER SWITCH SEE FIGURE 12 The Blocked Outlet Prover Switch is set up to shut...

Page 13: ...T BE READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING CONDITIONS INSTALL IN ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS REFER TO THE NATIONAL FUEL GAS CODE FIGURE 13 CONNECTION OF GAS PIPE...

Page 14: ...This heater is equipped with an approved temperature and pressure relief valve ASME ratings cover pressure relief CSA ratings cover release rate with temperature actuation FOR SAFE OPERATION OF THE WA...

Page 15: ...al Supply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit 3 This unit may never be connected to any existing heating system or component s previously...

Page 16: ...he desktop screen if there are no active fault or alert conditions An example of this screen is shown to the right The first temperature on this screen is the temperature of the water inside the tank...

Page 17: ...u DISPLAY ACTION From the Main Menu press Select to enter the Temperatures screen DISPLAY 2 Operating States In the main desktop screen there are some specific Operating States that are indicated on t...

Page 18: ...that can occur during operation These are Alerts and Faults Alerts This is a non safety related condition that the control has detected that may cause the water heater to operate in a less than optima...

Page 19: ...on about the water heater and the current status of specific conditions can be found INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIE...

Page 20: ...he unit is installed and filled with water and the inlet pressures confirmed simply turn the switch on and observe operation Cycle the unit off and on several times to ensure proper operation OPERATIN...

Page 21: ...45kpa Nominal Gas Supply Pressure 7 0 WC 1 74Kpa 11 0 WC 2 74Kpa Minimum Gas Supply Pressure 4 8 WC 1 18Kpa 8 5 WC 2 08 Kpa Manifold Pressure 0 WC OKpa 0 WC OKpa HIGH ALTITUDE INSTALLATIONS WARNING T...

Page 22: ...GAS TO APPLIANCE FOR YOUR SAFETY READ BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life OP...

Page 23: ...onnect switch 2 Close the cold water inlet valve to heater 3 Open a nearby hot water faucet to vent the system 4 Open the heater drain valve 5 If the heater is being drained for an extended shutdown i...

Page 24: ...sly it may be due to thermal expansion of water in a closed water supply system or it may be due to a faulty relief valve Thermal expansion is the normal response of water when it is heated In a close...

Page 25: ...OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED NOTE CONNECT RETURN LINE FROM HOT WATER CIRCULATING LOOP IF USED TO COLD WATER INLET LINE PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES I...

Page 26: ...PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW P...

Page 27: ...TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN...

Page 28: ...TH LOCAL CODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER...

Page 29: ...HOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 5 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Page 30: ...nits with the higher water flow may have a shortened life Dimensions shown are for minimum space occupied by the water heaters assemblies Space for the venting system and unit servicing must be added...

Page 31: ...er drain valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the heater and piping 3 If the outlet of the rel...

Page 32: ...at a positive manifold pressure reading of approximately 1 5 38 kPa W C is normal during the prepurge portion of the ignition cycle due to the location of the gas orifice MOTOR RUNS BURNER LIGHTS MOME...

Page 33: ...33 NOTES...

Page 34: ...34 NOTES...

Page 35: ...ranty shall be void and shall have no effect if the design or structure of the water heater is or is attempted to be modified or altered in any way including but not limited to by attaching non compan...

Page 36: ...36...

Reviews: