Using Explicit Messaging
7-9
Ladder Logic Rung Example
Example Source Data
In this example, the Set Attribute Single message writes 100, the
value in the source tag named ParameterWriteValue, to parameter
39 (Accel Time 1) in the MD65 drive.
10.0 seconds is written to the parameter.
Figure 7.8 – Set Attribute Single Message Example
Explicit Messaging Example
Writing a single parameter (Set Attribute Single command)
14
PerformParameterWrite
EN
DN
ER
Type - CIP Generic
Message Control
ParameterWriteMessage ...
MSG
Writing a single parameter (Set Attribute Single command)
Figure 7.9 – Example of Source Data from Set Attribute Single Message