background image

9.

Upon seeing a solid flow of water from the drain tub-
ing, and the cessation of the “gurgling” sound at the
drip cup, H (Fig. 7), close valve D (Fig. 7) then rapidly
apply compressed air or nitrogen into the to chamber
of the Model LP Dry Valve Actuator until the pressure
conforms to Table A levels as indicated on the air
pressure gauge. The Model LP Dry Valve Actuator
will close during this pressurizing process and the
water will stop flowing into the drip cup. At this point,
the pressure gauge which indicates push-rod cham-
ber pressure (Fig. 7) will equalize to the available wa-
ter supply pressure.

Note:

It may be necessary to

isolate the various pressure gauges in the trim during
system set-up by closing the ¼” 3-way valves (#68
Fig. 2) that they are connected to. During set-up,
pressure fluctuations may occur that can be poten-
tially damaging to the gauges.

10.

De-energize the solenoid valve(s). This is accom-
plished by resetting the solenoid-release pull station
and/or the detectors that were activated in Step #8
above.

Note:

All detection devices must be reset be-

fore the releasing/control panel can be reset.

11.

Open valve F (Fig. 7). Open slightly the main valve
controlling water supply (Fig. 7) to the deluge valve,
closing drain valve B (Fig. 7) when water flows. Ob-
serve if water leaks through the ball drip valve, valve
G (Fig. 7), into the drip cup, H (Fig. 7). If no leak oc-
curs, the seluge valve’s clapper is sealed. Open
slowly, and verify that the main valve controlling water
supply is fully opened

and properly monitored.

12. Verify that valve A (Fig. 7) and valve F (Fig. 7) are

open.

13. Secure the handle of the Model B Manual Emergency

Station, valve D (Fig. 7), in the OFF position with a ny-
lon tie (#64, Fig. 2).

Inspection and Testing

Refer to Figs. 2, 6, and 7.

1.

Water supply

— be sure the valve(s) controlling water

supply to the Deluge Valve are opened fully and
properly monitored.

2.

Alarm line

—be sure that valve F (Fig. 7) is opened

and remains in this position.

3.

Other trimming valves

— check that valve A (Fig. 7) is

open as well as all of the pressure gauge’s ¼” 3-way
valves. Valves C, D, and E (Fig. 7) should be closed.

4.

Ball drip valve,

valve G (Fig. 7)—make sure that valve

F (Fig. 7) is open. Push in on the plunger to be sure
the ball check is off its seat. If no water appears, the
deluge valve’s water seat is tight. Inspect the bleed
hole (see Fig. 7) on the underside of the deluge
valve’s push rod chamber for leakage.

5.

System pneumatic pressure

— check the Model LP

Dry Valve Actuator’s air pressure gauge (Fig. 7) and
water supply pressure gauge (Fig. 7) for confor-
mance to Table A.

6.

Releasing device

- Model LP Dry Valve Actuator (Fig.

7). Verify that the outlet is not leaking water. Check the
Model LP Dry Valve Actuator’s air pressure gauge
(Fig. 7) for proper pressure settings. Verify that the
tubing line from the actuator is not pinched or
crushed, which could prevent proper operation of the
deluge valve.

7.

Testing alarms

— make sure that valve F (Fig. 7) is

open. Open valve C (Fig. 7) permitting water from the
supply to flow to alarm portion of the trim. Typical de-
vices that are connected to this section of the trim are
pressure switches and/or a mechanical sprinkler
alarms (water motor). After

testing has been com-

pleted, close this valve securely. Push in on the
plunger of ball drip valve G (Fig. 7) until all of the water
has drained from the alarm line.

8.

Operational test

— Open the Model B Manual Emer-

gency Station, valve D (Fig. 7).

Note:

An

operational

test will cause the

deluge valve to openand flow water

into the sprinkler system.

9.

Secure

the Model B Manual Emergency Station,

valve D (Fig. 7), in the OFF position with a nylon tie
(#64, Fig. 2) after the deluge valve is reset.

Testing the Model DDX Deluge Valve
without Flowing Water

Refer to Fig. 7

1.

Close the valve controlling water supply to deluge
valve and open the main drain valve B.

2. Verify that valve A is open, allowing water to enter the

push rod chamber.

3. Operate detection system – energize the solenoid

valve(s) by operating a detector or manual pull sta-
tion.

4.

Operation of the detection system will result in a sud-
den drop of water pressure in the push rod chamber.

5. Reset

the detection system — reverse the operations

performed in step three above and then proceed ac-
cording to the directions listed in the “Resetting the
Single

Interlock Preaction System” section of this bul-

letin for

resetting the Deluge Valve.

Draining Excess/Condensate Water from
the System

Refer to Fig. 7

1.

Close the main valve controlling water supply to de-
luge valve. Also, close valve A and open the main
drain valve B.

2. Open

the condensate drain valve E until all of the wa-

ter has drained. Close valve E.

Note:

Be sure not to

keep valve E open for an extended period of time be-
cause that will cause enough system air to bleed off,
thereby causing an undesirable activation of a trou-
ble/alarm-annunciating device.

3. Close

the main drain valve B. If system contains pres-

surized air, allow the air pressure to come back up to
specification. Open valve A first, and then open the
main valve controlling the water supply to the deluge
valve.

11.

Summary of Contents for Single Interlock Preaction System

Page 1: ...10523 Instructions for Installation Operation Care and Maintenance For Single Interlock Preaction Systems With Dual Solenoid Actuation Of Pneumatic Pilot Release 4 100mm 6 150mm 165mm Sizes with Trim...

Page 2: ...ressure switch mountedinthetrim Thispressureswitchcanelectrically initiate the shutdown or startup of equipment such as computers or other second alarm devices This flow of water into the sprinkler sy...

Page 3: ...PCB certifica tion 6 Pre action systems shall be electrically monitored to demonstrate that they are in a ready to operate state at all times 7 Clear dry air shall be used Compressor tank must have pr...

Page 4: ...Fig 2 3...

Page 5: ...43226 NIPPLE STEEL 1 4 X 1 1 2 21 37 98543225 NIPPLE STEEL 1 4 X 2 1 2 1 38 98543244 NIPPLE STEEL 1 4 X 2 1 39 98543220 NIPPLE STEEL 1 4 X 3 2 40 98543243 NIPPLE STEEL 1 4 X 4 1 41 98543227 NIPPLE STE...

Page 6: ...6 is also available and can be provided as an op tion Whenever ambient temperature conditions are high the water temperature in the Model DDX Deluge Valve s pushrod chamber could possibly increase the...

Page 7: ...Fire Alarm Panel can be found on Figure 5 of this bulletin System Air Pressure Requirements When a Reliable Single Interlock Preaction System is utilized the sprinkler system piping requires a minimum...

Page 8: ...Fig 4 8...

Page 9: ...Fig 5 9...

Page 10: ...res sure in the pushrod chamber of the Deluge Valve 5 With Valve F Fig 7 open push in the plunger of ball drip valve valve G Fig 7 to force the ball from its seat and drain any water in the alarm line...

Page 11: ...atic pressure check the Model LP Dry Valve Actuator s air pressure gauge Fig 7 and water supply pressure gauge Fig 7 for confor mance to Table A 6 Releasing device Model LP Dry Valve Actuator Fig 7 Ve...

Page 12: ...17 96216066 Pin Locking Seat Not Shown 2 18 95106006 Piston 1 19 95200038 Plug Socket 3 8 18 NPT Not Shown 2 20 95506006 Pushrod 1 21 93916006 Pushrod Guide 1 Item No PartNumber Description No Req d 4...

Page 13: ...13 Fig 7...

Page 14: ...semble If the seat 2 Fig 6 is damaged or it is sus pected that the leakage is through the lower O ring 11 Fig 6 the seat clapper subas sembly is easily removed as a unit as follows Using a 5 16 Allen...

Page 15: ...nt surfaces it is not bi directional It will fail if installed backwards Roll the diaphragm so that the smooth surface the pressure side conforms to the inside of the push rod chamber cover and re ass...

Page 16: ...mm Valve 165mm Valve Fully Assembled to Model DDX Valve 6505040400 6505060400 6505065400 Segmentally Assembled Model DDX Valve Sold Separately 6502071710 Individual Parts Model DDX Valve Sold Separate...

Page 17: ...17 Fig 9...

Page 18: ...ented in this bulletin is to be installed in accordance with the latest pertinent Standards of the Na tional Fire Protection Association Factory Mutual Research Corporation or other similar organizati...

Reviews: