background image

Technical Data

Reliable Single Interlock Preaction Systems, with asso-

ciated trim, sizes 4” (100mm), 6” (150mm) and 165mm
are rated for use at minimum water supply pressure of 20
psi (1,4 bar) and maximum supply pressure of 250 psi
(17,2 bar). Water supplied to the inlet of the valve and to
the pushrod chamber must be maintained between 40°F
(4°C) and 140°F (60°C).

The following list of technical bulletins pertains to valves

and devices that may be used in this preaction system:

Valve Description

1. Rated working pressure:

Valve & System - 175 psi (12,1 bar)

2. Factory tested to a hydrostatic pressure of 500 psi

(34,5 bar). (Valve only)

3. End and trim connections:

ANSI/AWWA C606 grooved inlet and outlet

Threaded openings Per ANSI B 2.1

4. Face to face dimensions:

4" (100 mm) — 14” (355 mm)

6" (150 mm) & 165 mm — 16” (406 mm)

5. Shipping weight:

6. Friction loss (Expressed in equivalent length of

Schedule 40 pipe, based on Hazen & Williams

Maintenance

Reliable Single Interlock Preaction Systems and asso-

ciated equipment shall periodically be given a thorough
inspection and test. NFPA 25, Inspection, Testing and
Maintenance of Water Based Fire Protection Systems,
provides minimum maintenance requirements. System
components shall be tested, operated, cleaned, and in-
spected at least annually, and parts replaced as re-
quired.

Resetting the Single Interlock Preaction
System

Refer to Figs. 2,

6, and 7.

1.

Close the main valve controlling water supply (Fig.
7) to the Deluge Valve and close off the air supply to
the sprinkler system at the air supply’s source.

2.

Close the pushrod chamber supply valve, valve A
(Fig. 7).

3. Open the

main drain valve, valve B (Fig. 7), and

drain system.

4. Open

all drain valves and vents at low points

throughout the system, closing them when flow of
water has stopped. Open valve D (Fig. 7).

Note:

The above steps accomplish the relieving of

pres-

sure in the pushrod chamber of the Deluge

Valve.

5.

With Valve F (Fig. 7) open, push in the plunger of ball
drip valve, valve G (Fig. 7), to force the ball from its
seat, and drain any water in the alarm line.

6. With the Model B Manual Emergency Station, valve

D (Fig. 7

), open, push in and rotate the deluge

valve’s external reset knob

(#38, Fig. 6

) clockwise

until you hear a distinct clicking noise, indicating that
the clapper has closed.

Note:

The reset knob can

be rotated only after pressure in the pushrod cham-
ber has been reduced to atmospheric conditions (0
psig).

7.

Inspect and replace any portion of the sprinkler sys-

tem subjected to fire conditions.

8. Close valve F (Fig. 7). Activate a solenoid-release

pull station (Or other means of electric detection.) to
energize the solenoid valve(s). Silence any alarms
or audible tones on the releasing/control panel.
Open valve A (Fig. 7) to begin pressurizing the
push-rod chamber and its associated piping, while
simultaneously venting any entrapped air.

Note:

This venting of the air from the actuation piping is
very important to ensure proper system operation
and avoidance of falsely tripping the Deluge Valve.

10.

Deluge Valve

Reliable 510/511

Hydraulic Emergency Station (Model A)

Reliable 506

Solenoid Valve

Reliable 707

Mechanical Sprinkler Alarm

Reliable 612/613

Pressure Maintenance Device

Reliable 252

Air Compressor

Reliable 707/708

Electric Emergency Station

Reliable 707

Thermal/Smoke Detectors

Reliable 707

Fire Alarm Devices

Reliable 707

Waterflow Pressure Alarm Switch

Bailey & Mackey Ltd.
Model 1381V

Groove Dimensions

Valve

Size

Outlet

Diameter

Groove

Diameter

Groove

Width

Outlet Face

to Groove

4"

(100mm)

4.500"

(114mm)

4.334"

(110)

3

8

"

(10mm)

5

8

"

(16mm)

165mm

6.500"

(165mm)

6.330"

(161mm)

6"

(150mm)

6.625

(168mm)

6.455"

(164mm)

Valve Size

Weight

4" (100 mm)

6" (150 mm) & 165mm

64 lb. (29 kg)

95 lb. (43 kg)

Valve Size

Color

4" (100mm)
6" (150mm)

Black

165mm

Red

formula with C=120 and a flow velocity of 15ft/sec
(4.6 m/sec)):

7. Installation position: Vertical

Valve Size

Equivalent Length

4" (100mm)

6" (150mm) & 165mm

14' (4.27 m)

29.4' (9 m)

Summary of Contents for Single Interlock Preaction System

Page 1: ...10523 Instructions for Installation Operation Care and Maintenance For Single Interlock Preaction Systems With Dual Solenoid Actuation Of Pneumatic Pilot Release 4 100mm 6 150mm 165mm Sizes with Trim...

Page 2: ...ressure switch mountedinthetrim Thispressureswitchcanelectrically initiate the shutdown or startup of equipment such as computers or other second alarm devices This flow of water into the sprinkler sy...

Page 3: ...PCB certifica tion 6 Pre action systems shall be electrically monitored to demonstrate that they are in a ready to operate state at all times 7 Clear dry air shall be used Compressor tank must have pr...

Page 4: ...Fig 2 3...

Page 5: ...43226 NIPPLE STEEL 1 4 X 1 1 2 21 37 98543225 NIPPLE STEEL 1 4 X 2 1 2 1 38 98543244 NIPPLE STEEL 1 4 X 2 1 39 98543220 NIPPLE STEEL 1 4 X 3 2 40 98543243 NIPPLE STEEL 1 4 X 4 1 41 98543227 NIPPLE STE...

Page 6: ...6 is also available and can be provided as an op tion Whenever ambient temperature conditions are high the water temperature in the Model DDX Deluge Valve s pushrod chamber could possibly increase the...

Page 7: ...Fire Alarm Panel can be found on Figure 5 of this bulletin System Air Pressure Requirements When a Reliable Single Interlock Preaction System is utilized the sprinkler system piping requires a minimum...

Page 8: ...Fig 4 8...

Page 9: ...Fig 5 9...

Page 10: ...res sure in the pushrod chamber of the Deluge Valve 5 With Valve F Fig 7 open push in the plunger of ball drip valve valve G Fig 7 to force the ball from its seat and drain any water in the alarm line...

Page 11: ...atic pressure check the Model LP Dry Valve Actuator s air pressure gauge Fig 7 and water supply pressure gauge Fig 7 for confor mance to Table A 6 Releasing device Model LP Dry Valve Actuator Fig 7 Ve...

Page 12: ...17 96216066 Pin Locking Seat Not Shown 2 18 95106006 Piston 1 19 95200038 Plug Socket 3 8 18 NPT Not Shown 2 20 95506006 Pushrod 1 21 93916006 Pushrod Guide 1 Item No PartNumber Description No Req d 4...

Page 13: ...13 Fig 7...

Page 14: ...semble If the seat 2 Fig 6 is damaged or it is sus pected that the leakage is through the lower O ring 11 Fig 6 the seat clapper subas sembly is easily removed as a unit as follows Using a 5 16 Allen...

Page 15: ...nt surfaces it is not bi directional It will fail if installed backwards Roll the diaphragm so that the smooth surface the pressure side conforms to the inside of the push rod chamber cover and re ass...

Page 16: ...mm Valve 165mm Valve Fully Assembled to Model DDX Valve 6505040400 6505060400 6505065400 Segmentally Assembled Model DDX Valve Sold Separately 6502071710 Individual Parts Model DDX Valve Sold Separate...

Page 17: ...17 Fig 9...

Page 18: ...ented in this bulletin is to be installed in accordance with the latest pertinent Standards of the Na tional Fire Protection Association Factory Mutual Research Corporation or other similar organizati...

Reviews: