background image

7.

Pressurizing Line Connection

The water supply for the push-rod chamber must be

provided by connection of its inlet pressurizing line to the
water supply piping. Pressurizing lines for multiple
Model DDX Deluge Valve push-rod chambers must
never be manifolded together, having only a single tap
on the water supply piping. Each Model DDX Deluge
Valve must have its own push-rod chamber pressurizing
line connection. This connection must be made on the
supply side of the main water supply control valve. This
can be accomplished by:

a.

Using a tapped connection directly below or next to

the main water supply control valve using a welded
outlet or the appropriate mechanical fittings. A
grooved-end outlet coupling is one way to achieve
this.

b.

Using a water supply control valve that has an avail-

able threaded (NPT) supply-side tap design to allow
for a direct water supply connection to the Model DDX
Deluge Valve’s push-rod chamber.

Caution:

Reliable’s Model DDX Deluge Valve is de-

signed with an inlet restriction built into the pushrod
chamber. It is important not to introduce additional re-
strictions into the direct water supply connection or the
discharge from the pushrod chamber by installing addi-
tional valves or improperly installing the copper lines
used in the trim of the valve.

System Design Considerations

The automatic sprinklers, air compressor, releasing de-

vices, electric releasing control equipment, fire detec-
tion devices, manual pull stations, and signaling devices
which are utilized with this Reliable Single Interlock
Preaction System must be Loss Prevention Certification
Board (LPCB) approved, as applicable.

The

deluge valve and all interconnecting piping must

be located in a readily visible and accessible location
and in an area that can be maintained at a minimum tem-
perature of 40°F (4°C).

Note:

Heat tracing is not permit-

ted.

The redundant solenoid valves are operated and su-

pervised by an electrical releasing/control panel. Details
on the electrical connections and the

Prescient Pre-Ac-

tion Sprinkler Extinguishing Fire Alarm Panel can be
found on Figure 5 of this bulletin.

System Air Pressure Requirements

When a Reliable Single Interlock Preaction System is

utilized, the sprinkler system piping requires a minimum
of 7 psi (0,5 bar) supervisory pneumatic pressure. The
Model A-2 Pressure Maintenance Device, along with an
additional air pressure regulator, are used to maintain
the system’s pneumatic pressure between 7 and 10 psi
(0,5 and 0,7 bar) where a dry nitrogen gas supply or a
clean, dependable, and continuous (24 hours per day, 7
days per week) compressed air source is available.

The sections of the preaction trim that contains the two

redundant normally-closed solenoid valves, and the up-
per portion of the Model LP Dry Valve Actuator, require
pneumatic pressure settings per Table A. When estab-
lishing the preaction system for service, refer to Table A of
this bulletin for the correct pneumatic pressure settings for
a corresponding water supply pressure.

Note:

During

the initial system set-up, a higher pneumatic pressure
may be required in order to properly seat the internal dia-
phragm of Model LP Dry Valve Actuator.

Refer to Reliable Bulletin 251 and/or Fig. 3 of this bulletin

for instructions on how to modify these pressure

settings.

System Electrical Requirements

All releasing, alarm and detection devices in this Reliable

Single Interlock Preaction System are supervised by the

Prescient Pre-Action Sprinkler Extinguishing Fire Alarm
Panel

. Connect these devices as shown in Fig. 5. The

power supply, the standby emergency power supply, bat-
tery charger, and the rectifier circuitry are all contained
within this panel. For additional and detailed wiring infor-
mation, refer to the manufacturer’s literature included with
the Prescient Releasing Control Panel.

Caution:

Repairs

or disassembly of the solenoid valves should only be
done by a trained technician. An improperly repaired or
partially assembled solenoid valve could result in failure of
the valve to operate.

Water Pressure

psi (bar)

Pneumatic Pressure to be Pumped

into Sprinkler System, psi (bar)

Maximum

Not Less Than

Not More Than

20

(1,4)

10 (0,7)

14 (0,9)

50

(3,4)

12 (0,8)

16 (1,1)

75

(5,2)

13 (0,9)

17 (1,2)

100

(6,9)

15 (1,0)

19 (1,3)

125

(8,6)

16 (1,1)

20 (1,4)

150

(10,3)

17 (1,2)

21 (1,4)

175

(12,1)

18 (1,2)

22 (1,5)

Table A

Summary of Contents for Single Interlock Preaction System

Page 1: ...10523 Instructions for Installation Operation Care and Maintenance For Single Interlock Preaction Systems With Dual Solenoid Actuation Of Pneumatic Pilot Release 4 100mm 6 150mm 165mm Sizes with Trim...

Page 2: ...ressure switch mountedinthetrim Thispressureswitchcanelectrically initiate the shutdown or startup of equipment such as computers or other second alarm devices This flow of water into the sprinkler sy...

Page 3: ...PCB certifica tion 6 Pre action systems shall be electrically monitored to demonstrate that they are in a ready to operate state at all times 7 Clear dry air shall be used Compressor tank must have pr...

Page 4: ...Fig 2 3...

Page 5: ...43226 NIPPLE STEEL 1 4 X 1 1 2 21 37 98543225 NIPPLE STEEL 1 4 X 2 1 2 1 38 98543244 NIPPLE STEEL 1 4 X 2 1 39 98543220 NIPPLE STEEL 1 4 X 3 2 40 98543243 NIPPLE STEEL 1 4 X 4 1 41 98543227 NIPPLE STE...

Page 6: ...6 is also available and can be provided as an op tion Whenever ambient temperature conditions are high the water temperature in the Model DDX Deluge Valve s pushrod chamber could possibly increase the...

Page 7: ...Fire Alarm Panel can be found on Figure 5 of this bulletin System Air Pressure Requirements When a Reliable Single Interlock Preaction System is utilized the sprinkler system piping requires a minimum...

Page 8: ...Fig 4 8...

Page 9: ...Fig 5 9...

Page 10: ...res sure in the pushrod chamber of the Deluge Valve 5 With Valve F Fig 7 open push in the plunger of ball drip valve valve G Fig 7 to force the ball from its seat and drain any water in the alarm line...

Page 11: ...atic pressure check the Model LP Dry Valve Actuator s air pressure gauge Fig 7 and water supply pressure gauge Fig 7 for confor mance to Table A 6 Releasing device Model LP Dry Valve Actuator Fig 7 Ve...

Page 12: ...17 96216066 Pin Locking Seat Not Shown 2 18 95106006 Piston 1 19 95200038 Plug Socket 3 8 18 NPT Not Shown 2 20 95506006 Pushrod 1 21 93916006 Pushrod Guide 1 Item No PartNumber Description No Req d 4...

Page 13: ...13 Fig 7...

Page 14: ...semble If the seat 2 Fig 6 is damaged or it is sus pected that the leakage is through the lower O ring 11 Fig 6 the seat clapper subas sembly is easily removed as a unit as follows Using a 5 16 Allen...

Page 15: ...nt surfaces it is not bi directional It will fail if installed backwards Roll the diaphragm so that the smooth surface the pressure side conforms to the inside of the push rod chamber cover and re ass...

Page 16: ...mm Valve 165mm Valve Fully Assembled to Model DDX Valve 6505040400 6505060400 6505065400 Segmentally Assembled Model DDX Valve Sold Separately 6502071710 Individual Parts Model DDX Valve Sold Separate...

Page 17: ...17 Fig 9...

Page 18: ...ented in this bulletin is to be installed in accordance with the latest pertinent Standards of the Na tional Fire Protection Association Factory Mutual Research Corporation or other similar organizati...

Reviews: