background image

General Description

Reliable Single Interlock Preaction Systems are de-

signed for water-sensitive areas that require protection
from inadvertent water flow into the sprinkler system pip-
ing.

Sprinkler piping in single interlock systems can effec-

tively

be supervised by means of a Reliable Model A-2

Pressure Maintenance Device and a tank-mounted air
compressor. Loss of supervising pneumatic pressure,
due to a damaged sprinkler or sprinkler pipe will not
cause water to flow through the Model DDX Deluge
Valve and into the system piping. A significant loss of
pneumatic pressure will activate a trouble-annunciating
device when the system pressure falls below a predeter-
mined pressure level.

When one electrical detector senses the presence of

fire, the electrical releasing control panel activates fire
alarm devices and energizes the two redundant, nor-
mally-closed solenoid valves in the open position (

Note

:

Arranging detectors in a cross-zoned pattern will require
operation of two detectors before the solenoid valves
can open). These solenoid valves, when closed, retain
sufficient AIR pressure in the Model LP Pilot Line Actua-
tor, which in turn preserves sufficient WATER pressure in
the push rod chamber of the Model DDX Deluge Valve in
order to maintain it closed.

Energizing the solenoid valves relieves the air pressure

in the Model LP Dry Valve Actuator (see Fig. 8), thereby
releasing the water pressure that it was retaining. This is
turn relieves the pressure in the push rod chamber of the
Model DDX Deluge Valve. Venting this push rod cham-
ber will open the Model DDX Deluge Valve and allow wa-
ter to flow into the sprinkler system.

T

o fully operate a cross-zoned single interlock system,

two electrical detectors must activate and a sprinkler
head must open. During the early stages of a fire, smoke
or heat activates the first detector, which causes the con-
trol panel to produce a local alarm and an alarm at the
main fire alarm panel. Electrical relays inside the releas-
ing control panel can be used to shut down airmoving
equipment or activate security doors and other electrical
devices. Subsequent activation of a second, nearby or
adjacent detector will cause the panel to energize the
solenoid valves open and release water into the sprinkler
system piping. Water flowing into the sprinkler system
piping will simultaneously produce water pressure that
causes the transfer of contacts in the pressure switch
mounted in the trim. This pressure switch can electrically
initiate the shutdown or startup of equipment, such as
computers or other second alarm devices. This flow of
water into the sprinkler system piping effectively con-
verts the dry system into a wet pipe system. In the event
that the fire subsequently produces sufficient heat to op-
erate a sprinkler head, water will flow from that sprinkler,
controlling or suppressing the fire.

The major benefits of a single interlock preaction sys-

tem, when compared with a wet pipe (deluge) system
are as follows:

A.

A fire alarm sounds prior to the operation of a

sprinkler head, which may enable extinguishing
the fire by handheld means before the actual oper-
ation of any sprinklers and subsequent water dam-
age.

B.

A trouble annunciator signals whenever the in-

tegrity of the piping or sprinklers is accidentally or
intentionally disturbed; however, no water flow or
water damage will occur at that time.

C.

Speedy detection and an early fire alarm are

provided by fire detectors, without the delay asso-
ciated with water delivery time in the event of a fire.

Note:

with a wet pipe system, the fire alarm is de-

layed until after water has begun flowing from an
operated sprinkler head.

At the heart of Reliable’s Single Interlock Preaction Sys-

tem is the Model DDX Deluge Valve. This Deluge Valve is
a hydraulically operated, straight-through-design, differ-
ential-type valve (see Fig. 1). System maintenance is
simplified since priming water is not required and the
deluge valve can be reset externally without cover re-
moval. This is accomplished by pushing in and turning
the external reset knob at the rear of the deluge valve
(see Fig. 1). This feature provides a significant sys-
tem-restoration time advantage.

The Reliable Single Interlock Preaction System trim set

(see Fig. 2) provides all of the necessary equipment for
connections to the Model DDX Deluge Valve’s pushrod
chamber inlet and outlet ports, the 2” (50mm) main
drain, alarm devices, air supply, water supply, and re-
quired pressure gauges. This trim set is available in indi-
vidual parts, in time-saving, segmentally assembled kit
forms, or fully assembled to the Model DDX Deluge
Valve.

Listing & Approvals

The

4” (100mm), 6’ (150mm) and 165mm Single Inter-

lock Preaction Systems shown in this bulletin must only
be used in the combination described herein to be Loss
Prevention Certification Board (LPCB) approved. Instal-
lation of these systems must be according the require-
ments of Technical Bulletin TB21:1994:1.

The

majority of the system’s components are individu-

ally Listed by Underwriters Laboratories Inc. and Fac-
tory Mutual Approved.

2.

Summary of Contents for Single Interlock Preaction System

Page 1: ...10523 Instructions for Installation Operation Care and Maintenance For Single Interlock Preaction Systems With Dual Solenoid Actuation Of Pneumatic Pilot Release 4 100mm 6 150mm 165mm Sizes with Trim...

Page 2: ...ressure switch mountedinthetrim Thispressureswitchcanelectrically initiate the shutdown or startup of equipment such as computers or other second alarm devices This flow of water into the sprinkler sy...

Page 3: ...PCB certifica tion 6 Pre action systems shall be electrically monitored to demonstrate that they are in a ready to operate state at all times 7 Clear dry air shall be used Compressor tank must have pr...

Page 4: ...Fig 2 3...

Page 5: ...43226 NIPPLE STEEL 1 4 X 1 1 2 21 37 98543225 NIPPLE STEEL 1 4 X 2 1 2 1 38 98543244 NIPPLE STEEL 1 4 X 2 1 39 98543220 NIPPLE STEEL 1 4 X 3 2 40 98543243 NIPPLE STEEL 1 4 X 4 1 41 98543227 NIPPLE STE...

Page 6: ...6 is also available and can be provided as an op tion Whenever ambient temperature conditions are high the water temperature in the Model DDX Deluge Valve s pushrod chamber could possibly increase the...

Page 7: ...Fire Alarm Panel can be found on Figure 5 of this bulletin System Air Pressure Requirements When a Reliable Single Interlock Preaction System is utilized the sprinkler system piping requires a minimum...

Page 8: ...Fig 4 8...

Page 9: ...Fig 5 9...

Page 10: ...res sure in the pushrod chamber of the Deluge Valve 5 With Valve F Fig 7 open push in the plunger of ball drip valve valve G Fig 7 to force the ball from its seat and drain any water in the alarm line...

Page 11: ...atic pressure check the Model LP Dry Valve Actuator s air pressure gauge Fig 7 and water supply pressure gauge Fig 7 for confor mance to Table A 6 Releasing device Model LP Dry Valve Actuator Fig 7 Ve...

Page 12: ...17 96216066 Pin Locking Seat Not Shown 2 18 95106006 Piston 1 19 95200038 Plug Socket 3 8 18 NPT Not Shown 2 20 95506006 Pushrod 1 21 93916006 Pushrod Guide 1 Item No PartNumber Description No Req d 4...

Page 13: ...13 Fig 7...

Page 14: ...semble If the seat 2 Fig 6 is damaged or it is sus pected that the leakage is through the lower O ring 11 Fig 6 the seat clapper subas sembly is easily removed as a unit as follows Using a 5 16 Allen...

Page 15: ...nt surfaces it is not bi directional It will fail if installed backwards Roll the diaphragm so that the smooth surface the pressure side conforms to the inside of the push rod chamber cover and re ass...

Page 16: ...mm Valve 165mm Valve Fully Assembled to Model DDX Valve 6505040400 6505060400 6505065400 Segmentally Assembled Model DDX Valve Sold Separately 6502071710 Individual Parts Model DDX Valve Sold Separate...

Page 17: ...17 Fig 9...

Page 18: ...ented in this bulletin is to be installed in accordance with the latest pertinent Standards of the Na tional Fire Protection Association Factory Mutual Research Corporation or other similar organizati...

Reviews: