background image

Coverage Area

Flow Rate

Pressure

psi (bar)

Max. Enclosure Area 

Width x Length

ft. x ft. (m x m)

gpm (L/m)

K=5.6 (80)

26 (98.4)

33 (125.0)
40 (151.4) 

21.6 (1,5)
34.7 (2,4)
51.0 (3,5)

16 x 16 (4.9 x 4.9)
18 x 18 (5.5 x 5.5)

20 x 20

(1)

 (6.0 x 6.0)

(1)

(1)

 135°F (57°C) Only

Note:

 1 bar = 100 kPa

Thread

Size

Model

Temp. Rating

Max. Ceiling 

Temp.

Bulb

Color

Sprinkler

Cover

1/2” NPT

(R1/2)

F1FR

QREC

135°F

57°C

135°F

57°C

100°F

38°C

Orange

1/2” NPT

(R1/2)

F1FR

QREC

155°F

68°C

135°C

57°C

100°F

38°C

Red

Technical Data:

Nominal

Ori

fi

 ce

Thread

Size

“K” Factor

Approval

Organizations

Sprinkler

Identi

fi

 cation

Number (SIN)

US

Metric

1/2” 

(15mm)

1/2”

(R1/2)

5.6

80

1

RA2845

Model F1FR56 Quick Response Extended Coverage Concealed Pendent Sprinkler

Installation Wrench: 

Model RC1 Sprinkler Wrench

 

Approval Type: 

Quick Response

 

Extended Coverage - Light Hazard Occupancy

4.

Installation Aid:

A protective cap is included for use during installation.

Installation

Quick response sprinkler are intended for installation as 

specified in NFPA 13. Quick response sprinklers and stan-
dard response sprinklers should not be intermixed.

The Model F1FR56 Recessed QREC Sprinklers are to be 

installed as shown. The Model F1 or F2 Escutcheons il-
lustrated are the only recessed escutcheons to be used 
with the Model F1FR56 EC Sprinklers. The use of any other 
recessed escutcheon will void all approvals and negate all 
warranties.

When installing Model F1FR56 QREC Sprinklers, use the 

Model D Sprinkler Wrench. When installing Model F1FR 
QREC Recessed Pendent or Sidewall Sprinklers, use the 
Model GFR2 Sprinkler Wrench. Any other type of wrench 
may damage these sprinklers.

Model F1FR56 QREC Concealed Sprinklers use 135°F 

(57°C) or 155°F (68°C) Model F1FR QREC Pendent Sprin-
klers with a threaded Model CCP cup which is factory at-
tached to the sprinkler. The assembly is completed by the 
installation of the attractive, low profile, 135°F (57°C) rated 
cover plate assembly.  The cover plate and sprinkler cup 
are joined using a flexible tooth threaded engagement. A 
choice of two cover plate assemblies provides either ½” 
(13mm) or 

5

/

8

” (8mm) of cover adjustment.

Do not install these sprinklers in ceilings which have pos-

itive pressure in the space above.

The sprinkler cup is factory attached to the Model F1FR56 

QREC Sprinkler. A Teflon*-based thread sealant should be 
applied to the sprinkler threads only.

* DuPont Registered Trademark.

Fig. 4

Fig. 5

Summary of Contents for F1FR56 QREC Series

Page 1: ...n attractive low profile con cealed sprinkler assembly This sprinkler assembly uti lizes a Model F1FR56 QREC pendent sprinkler in a Model CCP cup and push on thread off cover plate assembly The cup is securely factory threaded on the sprinkler s in let end The assembly is shipped with a protective cap The sprinkler and cup are easily installed into the sprinkler fitting using the Model RC1 Sprinkl...

Page 2: ...ion Data Nominal Orifice Thread Size K Factor Sprinkler Length Approval Organizations Temperature Rating Sprinkler Identification Numbers SIN US Metric F C 15mm NPT R1 2 5 6 80 2 25 57mm 1 135 155 57 68 RA2845 Installation Data Nominal Orifice Thread Size K Factor Sprinkler Length Approval Organizations Temperature Rating Sprinkler Identification Numbers SIN US Metric F C 15mm NPT R1 2 5 6 80 2 25...

Page 3: ...d Coverage Light Hazard Occupancy Installation Data Nominal Orifice Thread Size K Factor Sprinkler Length Approval 2 Organizations Temperature 1 Rating Sprinkler Identification Number SIN US Metric 15mm NPT R 5 6 80 2 86 73mm 1 2 135 F 57 C 155 F 68 C 175 F 79 C RA2865 1 FM Approval of recessed sprinkler 135 F 57 C only 2 Refer to escutcheon data table for approvals and dimensions COVERAGE AREA Fl...

Page 4: ...56 Recessed QREC Sprinklers are to be installed as shown The Model F1 or F2 Escutcheons il lustrated are the only recessed escutcheons to be used with the Model F1FR56 EC Sprinklers The use of any other recessed escutcheon will void all approvals and negate all warranties When installing Model F1FR56 QREC Sprinklers use the Model D Sprinkler Wrench When installing Model F1FR QREC Recessed Pendent ...

Page 5: ...EC Sprinkler The sprinkler is then tightened into the pipe fitting When inserting or removing the wrench from the sprinkler cup assembly care should be taken to prevent damage to the sprinkler DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER The cover plate assembly is then pressed into the cup Final adjustment is made by turning the cover plate until the skirt flange makes full contact with the c...

Page 6: ...throughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electri...

Reviews: