background image

The Reliable Automatic Sprinkler Co., Inc.,

 

103 Fairview Park Drive, Elmsford, New York 10523

Model F1FR56 QREC Series
Quick Response
Extended Coverage Spray

Bulletin 028 

Rev
.

 B

Bulletin 028 

Rev.

 B

A complete line of UL Listed and FM Approved 
quick response extended coverage sprinklers 
for light hazard applications.

Horizontal Sidewall Sprinklers are approved 
for installation 4” to 12” (102mm - 305mm)

Model F1FR56 QREC Sprinkler Types

Pendent
Horizontal Sidewall EC-8

Model F1FR56 QREC Recessed Sprinkler Types

Recessed Extended Coverage Pendent F1/F2/FP
Recessed Extended coverage Horizontal Sidewall

Model F1FR56 QREC Concealed

Extended Coverage Pendent

Approval Organizations

Listed by Underwriters Laboratories, Inc. and 

    

Certified for Canada (cULus)
Factory Mutual Approvals (FM)

UL Listing Category

Sprinklers, Automatic & Open
Quick Response Extended Coverage Sprinkler (VNIV)

Product Description 

Reliable Models F1FR56 QREC and F1FR56 QREC Re-

cessed Sprinklers are quick response sprinklers which 
combine the durability for a standard sprinkler with the at-
tractive low profile of a decorative sprinkler.

The Models F1FR56 QREC and F1FR56 QREC Recessed 

Automatic Sprinklers utilize a 3.0mm frangible glass bulb.  
These sprinklers have demonstrated response times in 
laboratory tests which are five times faster than standard 
response sprinklers. This quick response enables these 
sprinklers to apply water to a fire much faster than stan-
dard sprinklers of the same temperature rating.

Model F1FR56 QREC Quick Response Extended Cover-

age Concealed Sprinkler is an attractive, low profile con-
cealed sprinkler assembly.  This sprinkler assembly uti-
lizes a Model F1FR56 QREC pendent sprinkler in a Model 
CCP cup and push-on thread-off cover plate assembly. 
The cup is securely factory threaded on the sprinkler’s in-
let end. The assembly is shipped with a protective cap. 
The sprinkler and cup are easily installed into the sprinkler 
fitting using the Model RC1 Sprinkler Wrench.  The cover 
plate assembly is attached to the sprinkler cup using a 
flexible tooth threaded engagement.  The cover plate is 
attached to the skirt using 135°F (57°C) ordinary tempera-
ture classification solder.

1.

2.

Recessed Extended

Coverage Pendent F1/F2

Extended Coverage

Pendent

When the ceiling temperature rises, the solder holding 

the cover plate melts, allowing the release of this part and 
thus exposing the Model F1FR56 QREC sprinkler inside to 
the rising ambient temperature. 

The Temperature rating of the sprinkler identified by the 

color of the glass bulb.

The glass bulb consists of an accurately controlled 

amount of special fluid hermetically sealed inside a pre-
cisely manufactured glass capsule. This glass bulb is spe-
cially constructed to provide fast thermal response.  

Application 

Quick response sprinklers are used in fixed fire protection 

systems: Wet, Dry, Deluge or Preaction. Care must be exer-
cised that the orifice size, temperature rating, deflector style 
and sprinkler type are in accordance with the latest published 
standards of the National Fire Protection Association or the ap-
proving authority having jurisdiction. Quick response sprinklers 
are intended for installation as specified in NFPA 13.

Extended Coverage

Pendent Concealed

Extended Coverage

Horizontal Sidewall EC-8

Recessed Extended

Coverage Horizontal

Sidewall EC-8

Summary of Contents for F1FR56 QREC Series

Page 1: ...n attractive low profile con cealed sprinkler assembly This sprinkler assembly uti lizes a Model F1FR56 QREC pendent sprinkler in a Model CCP cup and push on thread off cover plate assembly The cup is securely factory threaded on the sprinkler s in let end The assembly is shipped with a protective cap The sprinkler and cup are easily installed into the sprinkler fitting using the Model RC1 Sprinkl...

Page 2: ...ion Data Nominal Orifice Thread Size K Factor Sprinkler Length Approval Organizations Temperature Rating Sprinkler Identification Numbers SIN US Metric F C 15mm NPT R1 2 5 6 80 2 25 57mm 1 135 155 57 68 RA2845 Installation Data Nominal Orifice Thread Size K Factor Sprinkler Length Approval Organizations Temperature Rating Sprinkler Identification Numbers SIN US Metric F C 15mm NPT R1 2 5 6 80 2 25...

Page 3: ...d Coverage Light Hazard Occupancy Installation Data Nominal Orifice Thread Size K Factor Sprinkler Length Approval 2 Organizations Temperature 1 Rating Sprinkler Identification Number SIN US Metric 15mm NPT R 5 6 80 2 86 73mm 1 2 135 F 57 C 155 F 68 C 175 F 79 C RA2865 1 FM Approval of recessed sprinkler 135 F 57 C only 2 Refer to escutcheon data table for approvals and dimensions COVERAGE AREA Fl...

Page 4: ...56 Recessed QREC Sprinklers are to be installed as shown The Model F1 or F2 Escutcheons il lustrated are the only recessed escutcheons to be used with the Model F1FR56 EC Sprinklers The use of any other recessed escutcheon will void all approvals and negate all warranties When installing Model F1FR56 QREC Sprinklers use the Model D Sprinkler Wrench When installing Model F1FR QREC Recessed Pendent ...

Page 5: ...EC Sprinkler The sprinkler is then tightened into the pipe fitting When inserting or removing the wrench from the sprinkler cup assembly care should be taken to prevent damage to the sprinkler DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER The cover plate assembly is then pressed into the cup Final adjustment is made by turning the cover plate until the skirt flange makes full contact with the c...

Page 6: ...throughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electri...

Reviews: