Table 18 describes the configuration parameters that can be accessed using the MSet
Setup Tool in each controller.
T
ABLE
18: SS-L O
NBOARD
MS
ET
S
ETUP
T
OOL
C
ONFIGURATION
P
ARAMETERS
Parameter
Range
Selection
ADDR
1–124
RCP Controller Address (BACnet
®
MAC address)
BAUD
9600, 192,
384, 768
9600
EIA-485 network baud = 9.6 kbps
192
EIA-485 network baud = 19.2 kbps
384
EIA-485 network baud = 38.4 kbps
768
EIA-485 network baud = 76.8 kbps
SUBNET
No, Yes
No
home network = main network
Yes
home network = subnetwork
LAST
----, Last
----
not highest physical address on RCP network
Last
highest physical address on RCP network
BACNET
Yes, No
Yes
communication protocol = BACnet
®
No
communication protocol = RCP
UPDATE
No, Yes
No
configuration maintained in SS-L buffer only
Yes
configuration sent to controller