![Reliable Controls SS-CO2-H-UD User Manual Download Page 72](http://html1.mh-extra.com/html/reliable-controls/ss-co2-h-ud/ss-co2-h-ud_user-manual_1436213072.webp)
63
The SS Worksheet
U
SER
G
UIDE
SOFTWARE PROGRAMMING
SMART-S
ENSOR
™
2004 – 2014 Reliable Controls
®
Corporation. All rights reserved.
Off/Auto/
Manual
No icon is displayed when value = 0
Icon is displayed when value = 1
Icon is displayed when value = 2
Fan Speed
No icon is displayed when value = 0
Icon is displayed when value = 1
Icon is displayed when value = 2
Icon is displayed when value = 3
User Edit
Toggles between
Can Change
, indicating that the value may be
modified by an operator and/or the SS; and
Display Only
, meaning
that the value cannot be changed by an operator or by the SS.
Tag
Six character descriptive name that will be displayed on the LCD
screen together with the present value when the operator scrolls
to the point. If this column field is left empty, the row number will
be displayed. Typing the value “
_ND
“
in the Tag field will cause
that point to be suppressed on the LCD, but that point’s data will
still be available from the
SMART-Sensor
worksheet.
If a point is configured with the Type set to
State
, an icon is selected, and the User Edit field
is set to
Display Only,
the icon will be displayed, according to the value of the point, in
Idle
mode but the point will not appear separately by scrolling through the points using the
button.
New points may not be created in an SS. Every point used on an SS must already exist in a
MACH-System controller.
T
ABLE
12: SS W
ORKSHEET
C
OLUMNS
Column