3
│
Regulus CSE2 MIX F W 1F - www.regulus.eu
1.
INTRODUCTION
CSE2 MIX F W 1F twin-line pump station is designed for mixed heating circuits. It
provides flow through the heating system, mixes to the outlet temperature using a
motorized mixing valve (controlled by an external controller). The pump station includes
a filter with magnet, so it is also suitable for older steel pipe systems. It can be easily
mounted on a wall or on a manifold for multiple heating circuits.
2.
PUMP STATION DESCRIPTION AND DATA
Main Features
Description
The pump station consists of:
● Wilo Para 25/8 SC pump
● 2 ball valves w. sensor sheath
● check valve
● filter with strainer&magnet
● LK 840 actuated mixing valve
● thermometers, insulation
Working fluid
water, antifreeze heat-transfer fluid for heating systems
Installation
vertically on a wall or manifold (125 mm pitch)*
Connections
4 x G 1“ F
Code
17937
* A set of manifold connecting fittings can be purchased as optional accessories (see chapter 6)
Data for CSE2 MIX F W 1F Pump Station
Fluid working temperature
5 - 95 °C
Max. working pressure
6
bar
Ambient temperature
0 - 40 °C
Max. relative humidity
95%, non condensing
Pump power supply
1 ~ 230 V, 50 - 60 Hz
Mixing valve power supply 230 V, 50 Hz; from external controller w. 3-point control
Insulation material
EPP RG 60 g/l
Overall dimensions
360 x 133 x 245 mm
Total weight
6.7 kg