2. CONECTION VARIANTS

The heat pump is part of the energy system of the house. The correct design of a heat pump 

depends on the energy needs of the building and should be carried out by a specialist. These 

methods of connection are the most commonly used and serve as a basis for the project. If project 

documentation exists, follow it.

2.1. 

Direct connection to a heating system, DHW heating in a hot water storage tank

The accessory is represented by an additional heat 

source in the form of an in line heater (code 16166) 

equipped with an electric heating element of up to 7.5 

kW output and an optional indirect heated hot water 

storage tank with a heat exchanger surface of 

min. 1.5 

m

2

 (e.g. 

Regulus RDC 300 – code 12759

). The larger 

the heat exchange area of the HW storage tank, the 

faster the DHW heating will be and the heat pump will 

be able to prepare hot water more economically, or it will 

be able to heat DHW to a higher temperature.

In this direct connection to the heating system, it is necessary to keep the minimum flow through 

the heat pump at the level of min. 

1335 l/h (0.37 l/s)

 with sufficient heat supply for defrosting, i.e. it 

is necessary to have a part of the heating system without shut-off valves installed, e.g. thermostatic 

valves. Approximately it is at least 5 radiators of normal size (e.g. 0.6 x 0.9 m), or at least 30 m

2

 of 

underfloor heating without the possibility to be shut off.

For system control, it is necessary to use an 

IR 14 RTC

 smart controller which controls the 

entire heating and hot water system. It is equipped with an integrated web server permitting 

control through a web browser, or via a smartphone or tablet with the IR Client application 

(for Android and iOS).

2.2. Connection with a thermal store (combination with other renewable heat sources)

The accessories consist of a thermal store for heating only 

(Regulus PS series), or a combination thermal store with 

immersed DHW tank (Regulus DUO series), or a thermal store 

with stainless steel tube DHW exchanger (Regulus HSK series).
TThis connection is suitable for combining a heat pump with 

other heat sources, such as biomass boilers, fireplace inserts 

and stoves with a hydronic heat exchanger, solar thermal 

systems, solar photovoltaic systems, etc. The thermal store 

shall be sized depending on the selected type and output of the 

combined heat source, e.g. for combination with PV panels, the 

total volume of the thermal store can be calculated using the 

relationship 180 l / 1 kWp PV output. For example, for an array 

of PV panels with a peak output of 5 kWp, the tank volume shall be 900 litres. Always have the size 

and type of the thermal store determined by a specialist!

For system control, it is necessary to use an 

IR 14 RTC

 smart controller which controls the 

entire heating and hot water system. It is equipped with an integrated web server permitting 

control through a web browser, or via a smartphone or tablet with the IR Client application 

(for Android and iOS).

Summary of Contents for 17448

Page 1: ...www regulus eu RTC 12i RTC 12i EN RTC 12i Heat Pump Installation and Operation Manual ...

Page 2: ... water storage tank 4 2 2 Connection with a thermal store combination with other renewable heat sources 4 3 CONSTRUCTION READINESS INSTALLATION 4 3 1 Scope of supply 5 3 2 Installation preparation and transport 5 3 3 Minimum distances 6 3 4 Placement of the heat pump 7 3 5 Condensate drain 8 3 6 Pipe installation 9 3 7 Electrical wiring 9 4 COMMISSIONING 10 4 1 Initial start up 10 4 2 Troubleshoot...

Page 3: ...maged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard This device can be used by children from the age of eight years and above and by people with reduced physical sensory or mental ability or lack of experience or knowledge if they have been taught either with supervision or with the instructions provided how to use the device sa...

Page 4: ...of underfloor heating without the possibility to be shut off For system control it is necessary to use an IR 14 RTC smart controller which controls the entire heating and hot water system It is equipped with an integrated web server permitting control through a web browser or via a smartphone or tablet with the IR Client application for Android and iOS 2 2 Connectionwithathermalstore combinationwi...

Page 5: ...2 G 1 M nipples incl gaskets 3 2 Installation preparation and transport The installation must be carried out by a qualified person in accordance with the applicable stan dards and all regulations concerning occupational safety must be observed The heat pump shall be transported and stored in an upright position only Check that the product has not been damaged in transit Report any transport damage...

Page 6: ...roof If the product is placed in an area where it will be exposed to particularly harsh weather conditions or if there is a risk of damage from snow falling from a roof the product can be installed underneath a small awning Follow the recommendations below when choosing a heat pump location Location make sure that the heat pump does not disturb you or your surroundings with noise avoid installatio...

Page 7: ...e wall it is important to verify its load bearing capacity Depending on the composition and thickness of the wall it is recommended to use a chemical anchor or a through wall anchor for installation The brackets are galvanized and the complete support is supplied including steel ropes ensuring its spatial rigidity Follow the instructions for the wall mounting brackets Prior to placing the heat pum...

Page 8: ... cable to the drain pipe is not included in supply and can be ordered as an optional accessory code 18491 The drain pipe can be run a to the ground to a frost free depth the outlet and the space around the pipe must be filled with crushed stone to ensure sufficient condensate drain the underground section of the pipe can be perforated b into the building in its sewage system the through wall passa...

Page 9: ...g pipeline and possibly also to the house structure it is recommended to run the braided hose loose in a slight bend When installing compensators and braided hoses follow the instructions in the separate Installation Manuals that will come with these products Continue after the braided hose with copper stainless steel or other pipes of suitable size The appropriate dimension of the pipe is prescri...

Page 10: ...erial or design defect the installation company will contact the supplier and repair the defect Always report the serial number of the heat pump indicated on the label on the back of the heat pump Air in system If you hear a raspy sound from the heat pump make sure that it is completely air bled If necessary top up the system to operating pressure If the problem persists call a technician to deter...

Page 11: ...5 Fan motor 18 Wiring box cover 31 Heating element 6 Connecting part 19 Electric wiring box 32 Condenser heating element 7 Rear of fan housing 20 Side cover panel 33 Four way valve 8 Support 21 Refrigerant collector 34 Electronic expansion valve sensor 9 Installation box 22 Bottom cover panel 35 High pressure sensor 10 Top cover panel 23 Liquid refrigerant sensor 36 Low pressure sensor 11 Finned h...

Page 12: ...sor hot gas sensor low pressure switch high pressure switch green yellow green yellow flow switch temperature sensor return temperature sensor flow temperature sensor suction gas sensor outdoor temperature sensor temperature sensor hot gas sensor low pressure sensor high pressure sensor PFC power factor correction red blue black condenser heater compressor heater 4 way valve transformer Compressor...

Reviews: