background image

RCF-230TD

2

button. Comfort/Economy is selected via the parameter list.

Economy (Standby):

 “Standby” is shown in the display. The heat-

ing and cooling setpoints are freely adjustable. Factory settings: 
heating=15°C, cooling=30°C.

Off:

 The controller does not heat or cool and the fan stops (unless 

mould protection has been selected or the cool-down function for the 
electric heater is running, in which case the fan will still run).

Window: 

 

 is shown in the display, the controller is off and the fan 

stops (unless mould protection has been selected or the cool-down 
function for the electric heater is running, in which case the fan will 
still run). The window contact is connected to the DI and must be 

configured.

Occupancy detection/window contact

Parameter 3 determines if the DI is window contact input or 
occupancy detection input. An occupancy detector can be connected 
to the DI in order to switch between Comfort and Economy mode. A 
window contact can also be connected to the UI1 input.

Setpoint

The setpoint displacement is set using the INCREASE and DE-
CREASE buttons. Parameter 24 determines what is shown in the 
display. Refer to the parameter list for details. The basic setpoint is 
set via parameter 64.

Fan control

The fan can be controlled via RCF-230TD with the following modes: 
Low speed, Medium speed, High speed, Auto. The current fan speed 
in the Auto mode depends on the heating or cooling demand and the 
settings for each speed. 
When using automatic control, ”AUTO” is shown in the display.
The number of fan speed steps can be selected via parameter 30. If 

the parameter is set to 1, the first fan speed step will be used for fan 

control. 
Via parameter 31, it is possible to set the fan to the lowest speed 
level when Auto mode is selected. If this parameter is set to 1, the fan 

will run in all operating modes except Off and Window (unless mould 

protection is active or the cool-down function for the electric heater is 
running, in which case the fan will run in these modes as well).
When utilising an electric heater, parameter 1 set to 4, the fan has a 
cool-down period of 2 minutes. Fan kickstart can be utilised. The fan 
will then run at 100 % for a set time when starting up (0...10 seconds).

Manual control of the fan speed

By pressing the fan button, you change the fan speed according to 
the sequence I

à

II

à

III

à

AUTO. When using manual control, ”MAN” is 

shown in the display. 

If the fan has been configured not to be affected by the heating or cooling 

demand, ”AUTO” will not be shown when pressing the fan button.

Blocking of manual fan control

When the fan has been configured not to run via parameter 25, it is pos

-

sible to also prevent it from being controlled manually. Activation takes 
place via parameter 66.

Example: 

If the fan is configured to run only during cooling demand and 

this function has been activated, it will not be controllable during heating 
demand.

Indications

The display has the following indications:
HEAT   Heating control
COOL   Cooling control

       The open window symbol is shown if this function has  

 

been configured and a window is open. 

OFF   The controller does not heat or cool

On/Off button

By pressing the On/Off button, RCF-230TD will switch between Off mode 

and Comfort/Economy mode.

Blocking of buttons

The buttons of the controller can be blocked in order to prevent the set-
tings from being changed by unauthorized individuals. It is possible to 
either block only some buttons or, if desired, all of them. Activation takes 
place via parameter 65. 
The INCREASE and DECREASE button combination will always remain 

active in order for the configuration menu to be reachable.

Function for control of an electric heater

RCF-230TD has a function for pulse/pause control of an electric heater 
in sequence with a water heater, similar to control of a thermal actuator. 
When using an electric heater, the fan will continute to run for 2 minutes 

after the heater has been switched off in order to cool down the heater.

When using an electric heater, an external unit (e.g. PULSER-ADD or a 
solid state relay) is to be connected between RCF-230TD and the battery.

Note:

 RCF-230TD does not indicate fan breakdown or overheating of the 

heating coil. Therefore, all connections must be made externally. An over-
heating protection or similar can be used to disconnect the supply voltage.

Parameter list

When the controller is in Comfort mode or Window mode, different param

-

eter values can be set in a parameter list. 

Hold the INCREASE and DECREASE buttons depressed simultane-
ously for about 5 seconds until the Service symbol is displayed and 
then press the INCREASE button twice.
First the display will show parameter 1. Use the INCREASE and 
DECREASE buttons to scroll between the parameters and press the 

On/Off button to select the desired parameter. The parameter number 

will then be replaced by the parameter value. The value can be 
changed using the INCREASE and DECREASE buttons. If a button is 

held depressed the value will start scrolling, first slowly and then with 

increasing speed.
To exit the parameter list and go back to the basic display, press the 
INCREASE button until “EXIT” is shown (one step before parameter 

1) and press the On/Off button. You can also exit the parameter list by 

pressing down the INCREASE and DECREASE buttons simultane-
ously.

Parameters

The following parameters can be changed in the parameter list.

Nº = parameter number
FS = factory setting
NO = normally open
NC = normally closed

Description

FS

1

Control mode:
2=2-pipe system 
3=4-pipe system 

 

4=Electric heater

3

2

Change-over mode: 
0=Heating control, 1=Cooling control, 2=Automatic 
change-over depending on analogue temperature 
sensor or digital input

2

3

Operating mode when activating digital input 1:
0=Economy mode (occupancy detector)

1=Off mode (window contact)

0

4

Mould protection:
0=Not active
1=Active (fan never stops)

0

5

Deadband at Comfort mode. If the deadband is 
2 K, the heating setpoint is equal to the setpoint 
minus 1 and the cooling setpoint is equal to the 
setpoint plus 1.

2 K

6

Heating setpoint when unoccupied

15°C

7

Cooling setpoint when unoccupied

30°C

8

P-band for the room controller

10 K

9

I-time for the room controller

300 s

Summary of Contents for RCF-230TD

Page 1: ...e all connections must be made externally An over heating protection or similar can be used to disconnect the supply voltage Disconnection RCF 230TD should be connected to a switch or circuit breaker...

Page 2: ...open window symbol is shown if this function has been configured and a window is open OFF The controller does not heat or cool On Off button By pressing the On Off button RCF 230TD will switch between...

Page 3: ...re compensation on AI1 0 K 33 Temperature compensation for the internal room sensor 0 K 34 Highest permitted setpoint offset upwards Set table value 0 13 K Starting point 22 C 13 K 35 Highest permitte...

Page 4: ...5 for cooling actuators If the installation is a 2 pipe installation and the change over function is used the actuator should be connected to DO4 When connecting 3 point actuators DO4 is used for incr...

Page 5: ...F lj alltid de anvisade s kerhetsf reskrifterna i dokumentationen f r att f rebygga risken f r brand elst t och personskador INSTRUKTION RCF 230TD SV Rumsregulator f r styrning av fan coil enheter RCF...

Page 6: ...F nster visas i displayen regulatorn r i fr nslaget l ge och fl kten stannar f rutom om m gelskydd har valts eller nedkylning av elv rmaren r aktiv d forts tter fl kten att g F nsterkontakten ansluts...

Page 7: ...min 12 Tillslagsf rdr jning f r Komfortl ge 0 min 13 Givare ansluten till AI1 0 Intern givare 1 Extern rumsgivare 11 Begr n sningsgivare f r tilluft 0 14 Givare ansluten till UI1 0 Ingen 1 Change over...

Page 8: ...under inst lld tid 0 10 sekunder 0 s 70 Maxbegr nsning f r tilluftstemperatur vid kaskadreglering och v rmereglering 35 C 71 Minbegr nsning f r tilluftstemperatur vid kaskadreglering och v rmereglerin...

Page 9: ...31 DO4 Digital utg ng 4 f r v rme kyl signal eller ppna med 3 punktsst ll don Digital utg ng 230 V AC max 300 mA Max 2 A under 20 ms 32 CDO45 Gemensam DO4 5 Gemensam anslutning f r digital utg ng 4 oc...

Page 10: ...rbeiten an Fan Coil und Stellantrieben ist der Regler grund s tzlich mit Hilfe des Schutzschalters von der Versorgungsspannung zu trennen Einstellungen Regelmodi RCF 230TD verf gt ber die Regelmodi He...

Page 11: ...instellungen von unbefugten Personen ge ndert werden Dabei ist es m glich entweder nur bestimmte Tasten oder ggf auch alle Tasten zu blockieren Die entsprechende Aktivierung erfolgt ber Parameter 65 D...

Page 12: ...NO 1 NG 1 39 NO NG Digitalausgang 5 0 NO 1 NG 1 40 Hand Automatik Stellsignal Heizen 0 Aus 1 Hand 2 Auto 2 41 Hand Automatik Stellsignal K hlen 0 Aus 1 Hand 2 Auto 2 42 Stellsignal Heizen in Handbetri...

Page 13: ...der Verwendung thermischer Stellantriebe wird DO4 f r Heizstel lantriebe und DO5 f r K hlstellantrieb eingesetzt Bei einer 2 Rohr System Installation und der Verwendung der Change Over Funktion muss...

Page 14: ...ls de INSTRUCTION i Instruction pour les produits ayant la version 1 4 ou plus Veuillez lire cette instruction avant de proc der l installation et au raccordement du produit RCF 230TD FR Afin d viter...

Page 15: ...ue le mode refroidissement est configur la s quence de fonction nement repr sentera une s quence normale de chauffage refroidisse ment au cours de laquelle DO4 et DO5 s ouvrent en fonction des besoins...

Page 16: ...r les boutons AUGMENTER ET DIMINUER jusqu ce que l indication SER VICE apparaisse l cran environs 5 s puis appuyer deux fois sur la touche AUGMENTER Le param tre 1 s affiche en premier Le param tre 1...

Page 17: ...auto 0 arr t 1 Manuel 2 Auto 2 41 Signal de sortie refroidissement manuel auto 0 arr t 1 Manuel 2 Auto 2 42 Commande manuelle du signal de sortie chauf fage 0 43 Commande manuelle du signal de sortie...

Page 18: ...Raccordement de diff rents actionneurs Avec des actionneurs thermiques utiliser DO4 pour commander l actionneur du chauffage et DO5 pour commander l actionneur de refroidissement Lorsque la fonction c...

Page 19: ...tact libre de potentiel pour un contact de fen tre ou un d tecteur de pr sence Configurable sur NO NF 41 Agnd Commun analo gique 42 AI Entr e analogique Sonde d ambiance PT1000 externe la place de la...

Reviews: