19
Manual C
ORRIGO
U-
SERIE
2002-09
O. HS2-CV1 typ (C
ORRIGO
U20 only)
0.
0...10V DC
Controls the actuator using an analogue 0...10 V DC signal on output AO1.
Control parameters are set in the menu ”Control HS2”.
1.
3-point
Controls the actuator using increase/decrease signals on the outputs DO5 and
DO6. Control parameters are set in the menu ”Control HS2”.
N.B. 3-point control of HS2-CV1 can not be combined with the use of the timer
outputs TO1 and TO2.
P. HS2-CV2 (C
ORRIGO
U20 only)
See corresponding function for HS1 under point L.
0.
No
1.
Yes
Q. Control THW
0.
1 sequence
1.
2 sequences
R. Control HW
0.
No
1.
Yes
Not shown if THW is set to 2 sequences
S. Pump control HS1
0.
No
1.
Yes
Parameters for the pump control are set in the menu ”Settings”.
Stopped pump is exercised daily.
T. Pump control HS2 (C
ORRIGO
U20 only)
0.
No
1.
Yes
U. Pump indication HWC
0.
No
1.
Yes
Absence of signal from HWC-P on DI2 will trigger an alarm.
V. Daylight saving time
0.
No
1.
Yes
Yes means automatic setting to summertime at 02:00 the last Sunday in
March. Reverts to normal time at 03:00 the last Sunday in October.
X.
Basic settings
Use this function to reset to factory settings. Press the ”change” button,
choose ”Yes” and confirm with OK.
To abort at the ”change” stage, press Esc.
All parameters and settings revert to the original factory settings if the
command ”Basic Settings” is used.
This command should only be used by the commissioning engineer.
When the configuration is done and the configuration menu is exited using Esc an
automatic restart withthe new parameters will occur.
The login level is reset to 0.