Manual C
ORRIGO
U-
SERIE
2002-09
C
ORRIGO
- U20
Analogue inputs - Temperature sensors
AI1 Outdoor temperature
AI2 HS1 Supply temperature
AI3 HS1 Roomtemperature or
HWC Return temperatur tap hot-water
AI4 HS1 Return temperature radiator system or
HP1 Supply or
HWC Return temperature tap hot-water
AI5 HW Supply or
HP1 Return
AI6 THW Supply
AI7 HS2 Supply temperature
AI8 HS2 Roomtemperature or
HS2 Return temperature radiator system
Digital inputs - runtime and alarm indication
DI1 Indication circulation pump HS1
DI2 Indication circulation pump HWC
DI3 Alarm from expansion vessel
DI4 External alarm
DI5 Not used
DI6 Indication cirkulation pump HS2
DI7 Not used
DI8 Not used
Analogue outputs - output signal 0...10 V
AO1 Control valve HS1-CV1
AO2 Control valve HW-CV1 or
Control valve THW-CV1
AO3 Control valve THW-CV1 or
Control valve THW-CV2
AO4 Control valve HS2-CV1
AO5 Control valve HS1-CV2
AO6 Control valve HS2-CV2
Digital outputs
DO1 Control output, pump HS1
DO2 Three-position output VS1 increase
DO3 Three-position output VS1 decrease
DO4 Control output, pump HS2
DO5 Three-position output VS2 increase or
Timer output TO1
DO6 Three-position output VS2 decrease or
Timer output TO2
DO7 Alarm output
8 analogue sensor inputs Pt1000
5 digital inputs
6 analogue outputs 0...10 V
7 digital outputs
The controller has outdoor temperature dependant heating control of two radiator systems HS1and HS2 using
for each one or two control valves (HS1-CV1, HS1-CV2 and HS2-CV1, HS2-CV2). Also control of tap hot-water
using either one or two separate control circuts HW and THW or a single control circuit with two sequences
THW-CV1 and THW-CV2. Also two independent timer outputs TO1 and TO2 for controlling external functions
such as door locks, lighting etc.