Manual C
ORRIGO
U-
SERIE
2002-09
Commissioning protocol U20
Control HS2
Factory setting Commiss. setting
Man. offset
0
_______________
Setpoint room
20.0°C
_______________
Nightreduction / Standby
-1.0 / -2.0
_______ / ______
Outdoor plot 1
-20.0°C / 65.0°C
_______ / ______
Outdoor plot 2
-10.0°C / 55.0°C
_______ / ______
Outdoor plot 3
-5.0°C / 50.0°C
_______ / ______
Outdoor plot 4
±0.0°C / 43.0°C
_______ / ______
Outdoor plot 5
+5.0°C / 35.0°C
_______ / ______
Outdoor plot 6
+10.0°C / 30.0°C
_______ / ______
Outdoor plot 7
+20.0°C / 20.0°C
_______ / ______
PBand / I-time
60K / 120 s
_______ / ______
Runtime HS2-CV1
180 s
_______________
Control HW / THW
HW Setpoint
60°C
_______________
HW P / I / D
60°C / 60 s / 0.0
_____/_____/____
THW Setpoint
55°C
_______________
THW P / I / D
60°C / 60 s / 0.0
_____/_____/____
Scheduler
NRed 1 HS1
-------- 00:00-00:00
_______________
NRed 2 HS1
-------- 00:00-00:00
_______________
Standby HS1
-------- 00:00-00:00
_______________
NRed 1 HS2
-------- 00:00-00:00
_______________
NRed 2 HS2
-------- 00:00-00:00
_______________
Standby HS2
-------- 00:00-00:00
_______________
TO1 Per. 1
-------- 00:00-00:00
_______________
TO1 Per. 2
-------- 00:00-00:00
_______________
TO1 Per. 3
-------- 00:00-00:00
_______________
TO2 Per. 1
-------- 00:00-00:00
_______________
TO2 Per. 2
-------- 00:00-00:00
_______________
TO2 Per. 3
-------- 00:00-00:00
_______________
Alarm settings
1. Control alarm HS1
5K / 5 min
_____/_____/____
2. Control alarm HS1
5K / 5 min
_____/_____/____
3. Control alarm HW
5K / 5 min
_____/_____/____
4. Control alarm THW
5K / 5 min
_____/_____/____
5. Sum-alarm output active
Mo-Su 00:00 - 24:00 _______________
Settings
1 C-factor HS1 room
2.0
_______________
2 Outdoor comp. night red. HS1
No
_______________
3 C-factor HS2 room
2.0
_______________
4 Outdoor comp. night red. HS2
No
_______________
5 Pumpstop HS1
15°C / 30 min
_______ / ______
6 Pumpstop HS2
15°C / 30 min
_______ / ______
7 Show AI min/max
No
_______________
Installation
System
Commiss.date
Commiss. by
Page 2