background image

9

Manual C

ORRIGO

 U-

SERIE

  2002-09

AI Analogue inputs

C

ORRIGO

 has analogue inputs AI for connecting temperature sensors. PT1000 type

temperature sensors must be used. The function of some of the inputs varies
depending on the choice of model and configuration.

AI-inputs must always use the signal neutral of the AI terminal block as reference.
(terminals 24, 27, 30 or 33).

AI1 Outdoor temperature sensor. Must always be installed.

AI2 HS1 Outgoing water temperature. The temperature at the sensor is controlled

by the controlvalve HS1-CV1 so that the calculated setpoint is held. The set-
point depends on the set control curve and the outdoor temperature. The sensor
should be placed so that it senses the outgoing-water temperature in the
radiator circuit after the controlvalve.

AI3 HS1 Room temperature or HWC

A room temperature sensor should be placed at a location with a representative
temperature. The temperature signal is used to give a room temperature
dependant displacement of the radiator-water setpoint.
The K-factor governing the ratio between room temperature offset and water
temperature displacement is set in the menu ”Settings”.
A HWC (Hot water circulation) sensor is not used in any control-function but
only for data acquisition.

AI4 HS1 return temperature or HP1 (Heating, primary)

The sensor reading is not used in any control-function but only for data
acquisition.

AI5 HW Outgoing temperature or HP1 return

The temperature at the sensor is controlled by the controlvalve HW-CV1 so that
the setpoint is held.
A HP1 return sensor is not used in any control-function but only for data
acquisition.

AI6 THW outgoing temperature

The temperature at the sensor is controlled by the controlvalve THW-CV1 so
that the setpoint is held.

AI7 HS2 Outgoing temperature.The temperature at the sensor is controlled by the

controlvalve HS1-CV1 so that the calculated setpoint is held. The setpoint
depends on the set control curve and the outdoor temperature. The sensor
should be placed so that it senses the outgoing-water temperature in the
radiator circuit after the controlvalve.

AI8 HS2 room temperature or VS2 return

A room temperature sensor should be placed at a location with a representative
temperature. The temperature signal is used to give a room temperature
dependant displacement of the radiator-water setpoint.
The K-factor governing the ratio between room temperature offset and water
temperature displacement is set in the menu ”Settings”.
A HS2 return sensor is not used in any control-function but only for data
acquisition.

Wiring

(C

ORRIGO

 U20 only)

(C

ORRIGO

 U20 only)

Summary of Contents for Corrigo U10 Series

Page 1: ...U10 20 User manual...

Page 2: ...nt of a cabinet The required functions are selected with the help of questions in normal script or by means of a code under the configuration menu depending on the type of application CORRIGO U series...

Page 3: ...lashing LED and relay output 1A 24V DC AC The alarm output can be blocked to prevent unprioritised alarms activating the alarm relay during the night or during holidays This product conforms with the...

Page 4: ...g control of one radiator system HS1 using one control valve HS1 CV1 Also control of tap hot water using either one or two separate control circuts HW and THW or a single control circuit with two sequ...

Page 5: ...valve THW CV1 AO3 Control valve THW CV1 or Control valve THW CV2 AO4 Control valve HS2 CV1 AO5 Control valve HS1 CV2 AO6 Control valve HS2 CV2 Digital outputs DO1 Control output pump HS1 DO2 Three po...

Page 6: ...ts The controller has common poles for signal neutral to transmitters AI 1 8 and a common pole for digital input signals Terminal 22 common for digital input signals is not the same as signal neutral...

Page 7: ...S1 P DI8 Not connected DI7 Not connected DI6 Not connected DI5 Not connected DI4 External alarm DI3 Alarm expansion vessel DI2 Monitor pump HWC P DI1 Monitor pump HS1 P Common DI1 DI8 AI1 Temperature...

Page 8: ...I7 Not connected DI6 Monitor pump HS2 P DI5 Not connected DI4 External alarm DI3 Alarm expansion vessel DI2 Monitor pump HWC P DI1 Monitor pump HS1 P Common DI1 DI8 AI1 Temperature outdoor Signal neut...

Page 9: ...ny control function but only for data acquisition AI4 HS1 return temperature or HP1 Heating primary The sensor reading is not used in any control function but only for data acquisition AI5 HW Outgoing...

Page 10: ...tuator See under Configuration AO5 Control valve HS1 CV2 C20 only AO5 is only active if HS1 has been configured for two actuators in sequence See Configuration AO6 Control valve HS2 CV2 C20 only AO5 i...

Page 11: ...r 24 V AC See figure in the margin DO1 Control of circulation pump HS1 DO2 3 point output HS1 CV1 increase DO3 3 point output HS1 CV1 decrease DO2 and DO3 are only active if HS1 CV1 has been configure...

Page 12: ...d active and non acknowledged alarms will be displayed in the menu window The LED for alarms placed above the alarm button is lit when there are alarms in the queue If there are multiple alarms use an...

Page 13: ...isplays shown above will alternate at three second intervals Main menu Press the OK button The information menu will stop and the main menu will open immediately The main menu consists of a number of...

Page 14: ...ed by a steady AL and a steady red light on the alarm signals Arrows on the right hand side show when there are more alarms in the queue Login CORRIGO has four different login levels to prevent the us...

Page 15: ...er level 2 2222 User level 3 3333 Changing codes The codes for the three user levels can easily be changed in user level 3 Enter the login menu The arrow means that there are menus below press the arr...

Page 16: ...s are to be configured in the same way The first thing to be shown when the configuration menu is opened is the setting of the control function Using the arrow up button the two configuration codes wi...

Page 17: ...curve to compensate the supply water temperature for any offset in room temperature the K factor determining the room temperature influence on the setpoint must be set in the menu Settings 2 HWC Retur...

Page 18: ...om sensor is configured the controller will calculate the lowering of the water temperature using the current outdoor temperature and the set K factor for the room J Room compensation HS1 0 No 1 Yes I...

Page 19: ...he pump control are set in the menu Settings Stopped pump is exercised daily T Pump control HS2 CORRIGO U20 only 0 No 1 Yes U Pump indication HWC 0 No 1 Yes Absence of signal from HWC P on DI2 will tr...

Page 20: ...put Only shown if HS1 is configured with 2 sequences 3 Manual offset Actual setpoint The control curve can be offset 30K Setpoint including offset 4 Setpoint Room Actual Room Room compensation Display...

Page 21: ...e the applicable sensor input press Adjust the display value using or When completed confirm using OK Bear in mind that CORRIGO is always supplied with factory calibrated inputs This applies also to s...

Page 22: ...is configured as 3 point See Configuration point K DO3 3 point output HS1 decrease Only shown if HS1 CV1 type is configured as 3 point See Configuration point K DO4 Control pump HS2 CORRIGO U20 only...

Page 23: ...U20 each have 1 period for standby Standby lowering of the room temperature is utilised at longer periods of vacancy St lls in p motsvarande s tt som f r natts nkningsperiod 1och 2 ovan Vid verlappand...

Page 24: ...THW Should the actual temperature differ from the setpoint by more than the set value an alarm will be activated after a set time Only active if THW has been configured 5 Alarm HWC P 0 No 1 Yes 6 Ala...

Page 25: ...t values encountered since the last activation of the function are stored and will be displayed for each input under the menu Analogue in LEDs The LEDs are connected to the functions of certain in and...

Page 26: ...control HS1 active T Pump control HS2 active U Pump monitor HWC P active V Daylight saving time active Factory settings U10 Configuration Factory setting Config code 1 1100 1100 0000 Config code 2 000...

Page 27: ...for U10 0 Code must be 0 Q Control THW 0 1 sequence _______________ R Control HW 1 Yes _______________ S Control HS1 P 1 Yes _______________ T Not available for U10 0 Code must be 0 U Indication HWC...

Page 28: ...settings 1 Control alarm HS1 5K 5 min ______ _______ 2 Control alarm HW 5K 5 min ______ _______ 3 Control alarm THW 5K 5 min _______________ 4 Sum alarm output active Mo Su 00 00 24 00 _______________...

Page 29: ...____________ O HS2 CV1 Type 0 0 10 V DC _______________ P VS2 SV2 0 Nej _______________ Q Control THW 0 1 sequence _______________ R Control HW 1 Yes _______________ S Control HS1 P 1 Yes ____________...

Page 30: ...0 00 00 _______________ Standby HS1 00 00 00 00 _______________ NRed 1 HS2 00 00 00 00 _______________ NRed 2 HS2 00 00 00 00 _______________ Standby HS2 00 00 00 00 _______________ TO1 Per 1 00 00 00...

Page 31: ...D Function sensor AI4 0 Input not active 0 1 HS1 Return 1 2 HP Outgoing 2 E Function sensor AI5 0 Input not active 0 1 HW Outgoing 1 2 HP Return 2 F Function sensor AI6 0 Input not active 0 1 THW Out...

Page 32: ...U10 0 Not active Do not change 0 O Not available to Corrigo U10 0 Not active Do not change 0 P Not available to Corrigo U10 0 Not active Do not change 0 Q Control THW 0 1 sequence 0 1 2 sequences 1 R...

Page 33: ...turn 2 D Function sensor AI4 0 Input not active 0 1 HS1 Return 1 2 HP Outgoing 2 E Function sensor AI5 0 Input not active 0 1 HW Outgoing 1 2 HP Return 2 F Function sensor AI6 0 Input not active 0 1 T...

Page 34: ...Yes 1 N Room compensation HS2 0 No 0 1 Yes 1 O HS2 CV1 type 0 0 10 V DC 0 1 3 point 1 P HS2 CV2 0 No 0 1 Yes 1 Q Control THW 0 1 sequence 0 1 2 sequences 1 R Control HW 0 No 0 1 Yes 1 S Pump control...

Page 35: ...35 Manual CORRIGO U SERIE 2002 09...

Page 36: ...ate while at the same time utilizing energy in the most cost effective way possible The product range consists of Regin s own products as well as products from leading manufacturers V r aff rsid r att...

Reviews: