HZ42ST Regency Horizon
TM
Gas Fireplace
18
INST
ALLA
TION
INSTALLATION
VENTING INTRODUCTION
The HZ42 uses the "balanced fl ue" technology Co Axial system. The inner liner vents products of combustion to the outside while the outer liner
draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room
air up the chimney.
Note: These
fl ue pipes must not be connected to any other appliance.
The gas appliance and vent system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid
fuel or gas burning appliance. Each direct vent gas appliance must use it's own separate vent system. Common vent systems are prohibited.
VENTING ARRANGEMENTS
ALLOWABLE HORIZONTAL TERMINATIONS FOR HZ42 ST
The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 45
º
and one 90
º
(two 45
o
elbows equal to one
90
o
) for direct horizontal runs with horizontal termination use only one 45
º
elbow.
Note: Must use optional rigid pipe adapter (Part# 510-994) when using Rigid Pipe Venting Systems.
VENT RESTRICTOR SETTING:
Vent restrictor factory set, no adjustment required unless otherwise indicated.
Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting of Set 0 to Set 1 or Set 2 if required.
Note: Regency
®
Direct Vent System (Flex) is only approved for horizontal terminations.
• Maintain clearances to combustibles as listed in "Clearances" section
• Horizontal vent must be supported every 3 feet.
• Firestops are required at each fl oor level and whenever passing through a wall.
•
A wall thimble is mandatory for all horizontal terminations due to high temperatures.
• Flex system can only be used up to 10 feet - otherwise rigid venting must be used.
Please note the minimum centerline for
basic install shown above.