74 |
Grandview® G600EC Gas Fireplace
installation
G600EC -NG System Data
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes:
#46
Max. Input Rating
Btu/h 21,000 6.15 kWh
Min. Input Rating
Btu/h 11,500 3.37 kWh
Supply Pressure
min. 5.0" (127 mm) w.c.
max. 14.0" (356 mm) w.c.
Manifold Pressure
(High)
3.8" (97 mm) w.c.
Manifold Pressure
(Low)
1.1" (28 mm) w.c.
Gas Pipe Pressure Testing
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-
off valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should
be checked using the valve pressure
ports on the valve.
1. Make sure the valve is in the "OFF" position.
2. Loosen the "IN" and/or "OUT" pressure tap(s),
turning counterclockwise with a 1/8" (3 mm)
wide flat screwdriver.
3. Attach manometer to "IN" and/or "OUT" pressure
tap(s) using a 5/16" (8 mm) ID hose.
4. Light the pilot and turn the valve to "ON" position.
5. The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
6. When finished reading manometer, turn off
the gas valve, disconnect the hose and tighten
the screw (clockwise) with a 1/8" (3 mm) flat
screwdriver.
Note: Screw should be snug,
but do not over tighten.
High Elevation
This unit is approved in Canada for altitude to
4500 ft. (CAN/CGA-2.17-M91). For Natural Gas
installations above 4500 ft. follow current CAN/
CGA-B149.1.
G600EC - LP System Data
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes:
# 55
Max. Input Rating
Btu/h 20,500 6 kWh
Min. Input Rating
Btu/h 16,500 4.84 kWh
Supply Pressure
min.11.0" (279 mm) w.c.
max. 14.0" (356 mm) w.c.
Manifold Pressure
(High)
10" (254 mm) w.c.
Manifold Pressure
(Low)
6.4" (163 mm) w.c.
885 S.I.T. Valve Description
1. 6 Stage flame adjustment
2. Pilot adjustment
3. Inlet Pressure Tap
4. Outlet Pressure Tap
5. Pilot Outlet
6. Main Gas Outlet
7. Main Gas Inlet
1
2
3
4
6
5
7
1
2
3
4
6
5
7
Pilot Adjustment
Periodically check the pilot flames. Correct
Note: If you have an incorrect flame
pattern, contact your Regency
®
dealer for further instructions.
Incorrect flame pattern will have small,
probably yellow flames, not coming into
proper contact with the rear burner or flame
sensor.
Burner
FlameSensor
Pilot
Ignitor
flame pattern has two strong blue flames:
1 flowing around the flame sensor and 1
flowing across the burner (it does not have
to be touching the burner).
Ignitor
Pilot
Flame Sensor
Burner