City Series ACV60E
|
47
installation
Vertical Terminations - Rigid/Flex Pipe 127mm x 203mm
The minimum components required for a basic vertical termination are:
1 Vertical Termination Cap
1 Rigid Pipe Adaptor (Dura Vent only)
1 Length of pipe to adequately penetrate roof
1 Flashing (as required per AS/NZS 5601-2013, to be supplied
by installer).
Wall thickness is measured from the back standoffs to the inside
mounting surface of the termination cap. For siding other than vn=inyl
furring strips may be used, instead of the vinyl siding standoff, to
create a level surface to mount the vent terminal. The terminal must
not be recessed into the wall cladding. Measure the wall thickness
including the wall cladding.
Roof Pitch
Meters
flat to 7/12
0.61
over 7/12 to 8/12
0.61
over 8/12 to 9/12
0.61
over 9/12 to 10/12
0.76
over 10/12 to 11/12
0.99
over 11/12 to 12/12
1.22
over 12/12 to 14/12
1.52
over 14/12 to 16/12
1.83
over 16/12 to 18/12
2.13
over 18/12 to 20/12
2.29
over 20/12 to 21/12
2.44
Pipe Length
Vertical Terminal
Flashing
(not supplied)
Rigid Pipe Adapter
(Use only with Simpson Dura Vent)
WARNING:
Do not combine venting components from different venting systems.
However use of the the AstroCap
TM
is acceptable with all systems.
*Unit is not exactly as shown.