Ventilation Openings
Regency's patented Cool Wall system releases warmth at ceiling level. This
system reduces excessive radiant heat in front of the fireplace so you can
enjoy your fireplace more often.
•
Design your own chase vent solution to suit your home
•
Use optional front or left & right side chase vent grills
•
Release warmth into the room discreetly
Front Exit
The ventilation opening may be placed in front ensuring it meets the 1161cm
2
opening & is located 0 - 51mm from the enclosure ceiling.
SIde Exit (Left/Right)
Ventilation openings, when placed on both sides, must be of the same size.
They must be have an equal split (50/50) free air opening to balance air flow.
A ventilation opening may never be on one side only.
The ventilation openings cannot be any smaller than 152mm wide to equal
the total area of 1161cm
2
of free open area.
The ventilation openings must be located 0 - 51mm from the enclosure ceiling.
Top Exit
The ventilation opening may be short of the ceiling as shown below.
Minimum opening height must be 44mm measured from top of enclosure
to the ceiling and must be in open in front and both sides to meet the
minimum 1161cm
2
free open air requirement.
Ventilation Opening Locations
The following are examples of how the ventilation openings may be placed
above the fireplace.
If using the optional heat wave kit, this does not reduce the size of the
ventilation opening. The ventilation opening(s) must be a minimum 1161cm
2
regardless.
The air travelling through the heat exchanger is heated by the fireplace and
then directed out the back of the fireplace. The combined warmed air is then
vented back into the room.
The ventilation opening may be fully open at the top of the enclosure. This
type of ventilation opening would be used when the top of the enclosure
is not visible from above and where the ceiling within the room is higher
than normal. When creating this type of ventilation opening, measures
should be into place to avoid having objects of any type falling or be
thrown into the ventilation opening. Mesh screen or other preventative
measures should be put into place.
The ventilation opening may be placed on top ensuring it meets the
1161cm
2
opening. This type of ventilation opening would be used when
the top of the enclosure is visible from above and where the ceiling
within the room is higher than normal.