48
|
City Series ACV60E
installation
Vertical Terminations - Rigid/Flex Pipe 127mm x 203mm
• Two 45
o
elbows equal to one 90
o
elbow. Maximum of six 45
o
elbows allowed.
• Vent must be supported at offsets.
• Minimum distance between elbows is 0.3 m.
• Maintain clearances to combustibles as listed in the "Clearances" section.
• Horizontal vent must be supported every 0.9 m.
• Firestops are required at each floor level and whenever passing through a wall.
• Must use optional rigid pipe adaptor (Part# 770-994 when using rigid pipe vent systems
)
Vertical Venting with Three (3) 90
o
Elbows
One 90
o
elbow = Two 45
o
elbows.
V
H1
H
V1
Option
V
H + H1
V + V1
With these
options, max
total pipe length
is 9.1 m with
max 2.4 m total
horizontal.
Please note
min. 0.3m
between 90
o
elbows is
required.
A)
0.3 m Min. 0.6 m Max. 0.9 m Min.
B)
0.6 m Min. 0.9 m Max. 1.2 m Min.
C)
0.9 m Min. 1.2 m Max. 1.8 m Min.
D)
1.2 m Min. 1.5 m Max. 2.1 m Min.
E)
1.5 m Min. 1.8 m Max. 2.4 m Min.
F)
1.8 m Min. 2.1 m Max. 2.7 m Min.
G)
2.1 m Min. 2.4 m Max.
3 m Min.
Lengths do not include elbow indicated
Restrictor Set 0 - Factory Setting