8
|
Regency I2500M
|
8
installation
Clearance diagram for installations
Side and Top facing is a maximum of 1-1/2" (38mm)
thick.
MASONRY AND FACTORY BUILT FIREPLACE CLEARANCES
The minimum required clearances to combustible materials when installed into a masonry or factory built fireplace are listed below.
F
G
*Floor Protection
Floor thermal insulation/protection with a R value of 2.8 is required if the unit is raised 0 - 3"
(0-76mm) (measured from the bottom of the appliance).
Thermal floor protection is not required when unit is raiser greater than 3" (76mm) (measured
from the bottom of the appliance).
Please check to ensure that your floor protection and hearth will meet the standards for clear-
ance to combustibles. Your hearth extension must be made from a non-combustible material.
Extending 16" for US and 18" for Canada—measured from the fuel loading door.
Side View
12" (305mm) Mantel
3-1/2" (89mm) Mantel
22-1/2"
(572mm)
17-1/4"
(438mm)
2
0
12
6
4
8
10
2
0
12
6
16
4
14
8
18
10
Top of
Unit
20
22
24
Clearances are critical.
**
Mantel can be installed anywhere in shaded area
or higher using the above scale.
Note: Ensure the paint that is used on the
mantel and the facing is "heat resistant"
or the paint may discolour.
Unit
I2500
Adjacent
Side Wall
(to Side)
A
Mantle **
(to Top of
Unit)
B
Top
Facing
(to Top of Unit)
C
Side
Facing
D
Minimum
Hearth
Extension*
E
Minimum
Hearth Side
Extension*
F
To Top of Unit
G
12" (305mm)
17-1/4"(438mm)
for 3-1/2" (89mm)
mantel
16" (406mm)
1/2"(13mm)
to side surround
16" (406mm) USA
8" (203mm)
20" (508mm)
18"(457mm) Canada
22-1/2"(572mm)
for 12" (305mm)
mantel