16
UP 0, UP 1, UP 2, UP 2.4, UP 2.5
Protective terminal:
Upon start-up in operation - at equipment installation:
- for safe use of the actuator it is necessary to connect the outside and inside grounding terminal. The position
of the outside and inside grounding terminal can be seen in Fig. 1c and Fig. 1d. HP3 insulated eyelet crimping
pliers should be used to crimp wire to the outside grounding terminal (
fy CEMBRE
).
- a power switch/circuit-breaker must be installed on the power supply cable, as close as possible to the device,
easily accessible to the operator and identified as the actuator disconnecting device.
Outside and inside, mutually interconnected and identified with a protective grounding symbol.
The electric connection should be made according to wiring diagrams pasted into the top cover of the EA.
Product protection
We recommend to use fuses for protection of product.
Table 4:
Fuse values and characteristics
Type
Order code
Voltage
F
requen
cy
(H
z)
Electric
motor
Power /
Power input
(W)
max.
curent
EA (A)
Fuse values
F3
340.X-0XXXX/YY
230 VAC
340.X-LXXXX/YY
220 VAC
50
0,22
T 0,500 A / 250 V
U
P
0
340
340.X-3XXXX/YY
24 VAC
50/60
13,8/31
2,2
T 3,15 A / 250 V
341.X-0XXXX/YY
230 VAC
341.X-LXXXX/YY
220 VAC
50
40/90
0,8
T 1,6 A / 250 V
341.X-9XXXX/YY
3x400 VAC
3x415 VAC
UP
1
341
341.X-MXXXX/YY
3x380 VAC
50
73/110
0,42
T 0,8 A / 250 V
34X.X-0XXXX/YY
230 VAC
34X.X-LXXXX/YY
220 VAC
50
20/75
0,45
T 1 A / 250 V
34X.X-0XXXX/YY
230 VAC
34X.X-LXXXX/YY
220 VAC
50
60/120
0,86
T 1,6 A / 250 V
34X.X-9XXXX/YY
34X.X-2XXXX/YY
3x400 VAC
3x415 VAC
34X.X-MXXXX/YY
34X.X-NXXXX/YY
3x380 VAC
50
90/150
0,56
T 1,0 A / 250 V
34X.X-0XXXX/YY
230 VAC
34X.X-LXXXX/YY
220 VAC
50
120/228
1,3
T 1,6 A / 250 V
34X.X-9XXXX/YY
34X.X-2XXXX/YY
3x400 VAC
3x415 VAC
34X.X-MXXXX/YY
U
P
2
, U
P
2.
4
U
P
2.5
342
,343
,344
34X.X-NXXXX/YY
3x380 VAC
50
180/300
0,82
T 1,6 A / 250 V
Summary of Contents for UP 0
Page 10: ...8 UP 0 UP 1 UP 2 UP 2 4 UP 2 5 5 9 Fig 1a Fig 1b ...
Page 11: ...UP 0 UP 1 UP 2 UP 2 4 UP 2 5 9 Fig 1c UP 2 5 with controller ...
Page 42: ...40 UP 0 UP 1 UP 2 UP 2 4 UP 2 5 7 Enclosures 7 1 Wiring diagrams UP 1 UP 2 UP 2 4 UP 2 5 ...
Page 43: ...UP 0 UP 1 UP 2 UP 2 4 UP 2 5 41 ...
Page 44: ...42 UP 0 UP 1 UP 2 UP 2 4 UP 2 5 Wiring diagrams UP 0 ...
Page 51: ...UP 0 UP 1 UP 2 UP 2 4 UP 2 5 49 Electric part turn actuators Unimact UP 2 4 UP 2 5 ...