UP 0, UP 1, UP 2, UP 2.4, UP 2.5
15
•
number of controller operation hours
•
frequency of relay switching in direction "opening"
•
frequency of relay switching in direction "closing"
Supply voltage:
................................................................................... terminal 61 (L1) -1(N) - 230 V AC ±10%
Frequency:
................................................................................................................................... 50/60 Hz ±2%
Input control signals - analogue:
...................................................................................................... 0 - 20 mA
........................................................................................................................................................ 4 - 20 mA
............................................................................................................................................................ 0 - 10 V
Input resistance for signal 0/4 - 20 mA
..................................................................................................... 250
Ω
Input resistance for signal 0/2 - 10 V
....................................................................................................... 50k
Ω
(Actuator opens at rising of control signal.)
Controller linearity:
.................................................................................................................................... 0.5 %
Controller insensitiveness:
.............................................................................................. 1 - 10% (adjustable)
Feedback (position transmitter):
.......................................................................... resistive 100 up to 10,000
Ω
current 4 up to 20 mA
Power outputs:
.................................................................................................................. 2x relay 5A/250V AC
Digital outputs:
............4x LED (supply, error, adjustment, "opening", "closing" - with two-colour LED)
Error status:
....................................................................................................... control switch 24 V, 2W - POR
Reaction at error situation:
transmitter error - error message LED
Control signal missing:
...................................................................................................... error message LED
SYS mode:
........................................................................................................................... error message LED
Adjusters:
................................................................................................................... communication connector
................................................................................................................. 2x calibrating and adjusting button
Lubricators
:
- see chapter Maintenance - extent and periodicity.
2.2.1 Mechanical connection
−
flange (ISO 5211)
Basic and connecting dimensions are given in dimensional drawings.
2.2.2 Electrical connection
Terminals (X) for EA
UP 0
- max. 24 screw-less terminals
with connecting wire cross-section of 0,08 to 1,5 mm
2
Terminals (X) for EA
UP 1, UP 2, UP 2.4, UP 2.5
- max. 32 screw-less terminals
with connecting wire cross-section of 0,08 to 2,5 mm
2
Cable glands:
For version without local control:
- 3 cable glands - 3xM16 – diameter cable 9 to 13 mm – for UP 0
- 3 cable glands - 3xM20 – diameter cable 8 to 14,5 mm – for UP 1, UP 2 – UP 2,5
For version with local control:
- 2 cable glands - 2xM16 – diameter cable 9 to 13 mm – for UP 0
- 2 cable glands - 2xM20 – diameter cable 8 to 14,5 mm – for UP 1, UP 2 – UP 2,5
The electric connection should be made according to wiring diagrams pasted into the top cover of the EA.
Wire stripping lenght of the wires for screwless terminals is from 8 to 9mm.
Summary of Contents for UP 0
Page 10: ...8 UP 0 UP 1 UP 2 UP 2 4 UP 2 5 5 9 Fig 1a Fig 1b ...
Page 11: ...UP 0 UP 1 UP 2 UP 2 4 UP 2 5 9 Fig 1c UP 2 5 with controller ...
Page 42: ...40 UP 0 UP 1 UP 2 UP 2 4 UP 2 5 7 Enclosures 7 1 Wiring diagrams UP 1 UP 2 UP 2 4 UP 2 5 ...
Page 43: ...UP 0 UP 1 UP 2 UP 2 4 UP 2 5 41 ...
Page 44: ...42 UP 0 UP 1 UP 2 UP 2 4 UP 2 5 Wiring diagrams UP 0 ...
Page 51: ...UP 0 UP 1 UP 2 UP 2 4 UP 2 5 49 Electric part turn actuators Unimact UP 2 4 UP 2 5 ...