UP 0, UP 1, UP 2, UP 2.4, UP 2.5
13
UP 2, UP 2.4, UP 2.5:
Heating power for range temperature from -50 °C: ............................................................... cca 40 W/55 °C
Switching resistor .......................................................................................................................thermal switch
Thermal switch of space heater (F2)
Supply voltage: ................................ corresponding with motor supply voltage (max. 250V AC, 5 A)
Switching-off temperature:................ +30°C ± 4K
Switching-on temperature:................ +20°C ± 3K
Manual control:
By handwheel after unscrewing the locking screw (except UP 0). Rotate the handwheel clockwisely to move the
output shaft in the direction „Z“(except UP 0)..
Position transmitters
Resistive position transmitter RP 19:
Resistance (single
B1
)
..................................................................................................................... 100; 2 000
Ω
(double
B2
)
.......................................................................................................... 2x100
Ω
, 2x2000
Ω
Operating life of transmitter
........................................................................................................... 1.10
6
cycles
Load capacity
................................................................................ 0,5 W do 40 °C, (0 W/125
°
C)
Maximum current of sliding contact ....................................................................................................... max.35 mA
Maximum supply voltage............................................................................................................. PxR V DC/AC
Potentiometer linearity error ......................................................................................................................
±
2,5 [%]
1)
Potentiometer hysteresis
...............................................................................................................max. 2,5 [%]
1)
Potentiometer values at limit positions: ............................................... “O“ (open)......
≥
93%, ”Z“ (closed).......
≤
5%
Resistive position transmitter PL 240:
Resistance (single
B1
)
....................................................................................................................... 5 k
Ω
±
20%
Operating life of transmitter
........................................................................................................... 1.10
6
cycles
Maximum current of sliding contact ........................................................................................................ max.10mA
Maximum supply voltage ................................................................................................................................ 18 V
Potentiometer linearity error ......................................................................................................................
±
2,5 [%]
1)
Potentiometer hysteresis
...............................................................................................................max. 2,5 [%]
1)
Potentiometer values at limit positions .....................................................................................................................
.... “O“ (open)......
≥
93%, ”Z“ (closed).......
≤
5% from the real value of the resistance
Capacitive (B3): non-contact, life 10
8
cycles
2-wire connection
with built-in power supply or without built-in power supply
The current signal
4
÷
20 mA
(DC) is acquired from the capacitive transmitter supplied from the internal or an
external voltage supply source. The electronics of the transmitter is protected against eventual wrong polarity
and current overloading. The entire transmitter is galvanic insulated so several transmitters can be connected to
one external voltage source.
Power supply voltage (with power supply) ................................................................................................ 24 V DC
Power supply voltage (without power supply).................................................................................. 18 to 28 V DC
Ripple voltage .........................................................................................................................................max. 5%
Max power input ............................................................................................................................................ 0,6 W
Load resistance ...................................................................................................................................... 0 to 500
Ω
Load resistance can be single side grounded.
Influence of resistance on output current ...........................................................................................0,02%/100
Ω
Influence of voltage on output current..................................................................................................... 0,02%/1V
Temperature dependency
.......................................................................................................... 0.5% / 10
°
C
Output signal values at limit positions:
“O“............. 20 mA (terminals 81; 82)
“Z“ ............... 4 mA (terminals 81; 82)
Values tolerance of output signal of EPV
“Z“ ............ +0,2 mA
“O“ ............
±
0,1 mA
DCPT3M – current transmitter (B3)
- 2-wire connection
without built-in power supply or with built-in power supply
Current signal ............................................................... 4 ÷ 20 mA (DC) with optional mirroring (20 ÷ 4 mA)
Mode of operation ...................................................................................... contactless, magnetic resistance
Transmitter increments without gears................................................................................................. 0.352 °
Loading resistor:....................................................................................................................0 through 500
Ω
Summary of Contents for UP 0
Page 10: ...8 UP 0 UP 1 UP 2 UP 2 4 UP 2 5 5 9 Fig 1a Fig 1b ...
Page 11: ...UP 0 UP 1 UP 2 UP 2 4 UP 2 5 9 Fig 1c UP 2 5 with controller ...
Page 42: ...40 UP 0 UP 1 UP 2 UP 2 4 UP 2 5 7 Enclosures 7 1 Wiring diagrams UP 1 UP 2 UP 2 4 UP 2 5 ...
Page 43: ...UP 0 UP 1 UP 2 UP 2 4 UP 2 5 41 ...
Page 44: ...42 UP 0 UP 1 UP 2 UP 2 4 UP 2 5 Wiring diagrams UP 0 ...
Page 51: ...UP 0 UP 1 UP 2 UP 2 4 UP 2 5 49 Electric part turn actuators Unimact UP 2 4 UP 2 5 ...