The hose set
3
enclosed with the VF secondary vessel must be assembled
at the outlet of the VG basic vessel intended for this purpose and individually
connected to the piping provided on site.
Only two R1 connection nipples are available on the flange of the VG basic
vessels above 1000 l Ø 1000 mm. In this case the hose set of the VF secondary
vessel has to be assembled at the connection
2
using the T-piece.
(Diagram on p. 7.)
Vessel up to
∅
740 mm
Vessel above
∅
1000 mm
Exploded
view
→
see also diagram on p. 7
26
Exploded
view
26
28
Assemble
without cap!
Assemble
without cap!
on site
reflex ’variomat’
Assembly
8
Installation of the VF secondary vessel
Dipstick-tube degassing, venting of the diaphragm compartment
(compensating bend)
The add-on pieces are affixed to the vessel foot and packed in a PE bag.
With VG and VF vessels up to Ø 740 mm:
– Evacuation device with ventilation protection (26)
– Reducing sleeve Rp ½ x Rp ⅜
With VG and VF vessels above Ø 1000 mm:
– Evacuation device with ventilation protection (26)
– Reducing sleeve R 1 x Rp ⅜
These parts must be sealed, assembled and mounted in the middle vessel
connection on the vessel. The plastic cap of the ventilation protection must be
removed.
Assemble the supplied compensating bend (28) with the clamping ring connection
at the vessel connector for evacuation and ventilation of the diaphragm
compartment.
Attention!
The compensating bend (28) must not be sealed! A draining facility
must be provided on site, for example via a funnel.
Assembly of the add-on parts for VG
and VF vessels