General
The purpose of the customer menu is to enter and change the key ’variomat’ operating
parameters. Some of these will already have been processed within the start routine during
initial start-up. Further parameter changes are possible here. Press the “menu” button to get
to the customer menu. Here you can change operating parameters or view current statuses.
Press the “menu” button to access the customer menu. Press to exit the customer menu
immediately.
This display appears after the menu button is pressed.
You are now in the customer menu.
Select the language using the country code,
for instance “GB” for the English language,
and confirm with “ok”.
Start by setting the current hour (in this
case: 18) with the arrow buttons and confirm
with “ok”. Continue with the minutes (in this
case: 46) and the seconds (in this case: 29).
Start by setting the current day (in this
case: 29) with the arrow buttons and confirm
with “ok”. Continue with the month (in this
case: 11) and the year (in this case: 01).
A check is performed as to whether the signal
issued by the level gauge at the foot of the VG
basic vessel corresponds to the vessel set in
the controller (
→
p. 9).
Set the minimum operating pressure
according to the static height of your system
(
→
chart on p. 15) and confirm with “ok”.
Select the degassing program here
(
→
p. 20) and confirm with “ok”.
Select the time for continuous degassing.
Recommended: 12 h with system capacities
≤
20 m³/h
24 h with system capacities
> 20 m³/h
Confirm with “ok”.
Press
to get to the language selection:
Change
menu item
Select
parameter
Confirm
parameter
Exit
menu
Select or change
parameter (flashing values
or symbols)
Customer menu
Country: GB
D GB F NL PL
Time:
18:46:29
Date:
29.11.01
00% 2.1
bar
Auto-zero?
Min.oper.press.
P0 =
1.8 bar
Degassing prog.
Continuous deg.
Cont. degas time
ED =
012.0 h
ok
ok
ok
ok
ok
ok
ok
ok
ok
quit
ok
ok
ok
ok
ok
quit
backward
forward
Change menu item
reflex ’variomat’
Operation
21
Customer menu