Reflex Fillcontrol Auto Operating Manual Download Page 13

 

Controller 

 

 

 

Fillcontrol Auto 

 22.09.2020 - Rev. C 

 

English  

 13 

 

Indication on the 
display 

Meaning 

With water meter. 
YES 

 

YES: FQIRA+ contact water meter is installed, see 
chapter 4.6 "Optional equipment and accessories" 
on page 5 .  
This is the prerequisite for the make-up volume 
monitoring and the operation of a softening 
system. 

 

NO: A contact water meter is not installed 
(standard model). 

Make-up volume 
000020 l 

Only displayed if "YES" has been set in the "With water 
meter" menu option. 

 

Press "OK" to delete the counter. 

 

Press "YES" to reset the value displayed to "0". 

 

Press "NO" to retain the displayed value. 

Max. make-up 
volume 
000100 l 

This value is only displayed if "YES" has been set in the 
"With water meter" menu option. 

 

When the set volume is exceeded, the system 
interrupts the make-up process and returns the 
error message "Max. make-up volume exceeded". 

With softening 
YES 

This value is only displayed if "YES" has been set in the 
"With water meter" menu option. 

 

YES: Further queries follow about softening. 

 

NO: The system does not offer more queries 
regarding the softening process. 

Disable make-up? 
YES 

This value is only displayed if "YES" has been set in the 
"With softening" menu option. 

 

YES: The system stops the make-up process when 
the set soft water capacity is exceeded. 

 

NO: The system does not stop the make-up 
process. The system displays the "Softening" 
message. 

Hardness reduction 
10 °dH 

This value is only displayed if "YES" has been set in the 
"With softening" menu option. 

 

Hardness reduction is calculated from the 
difference of the overall water hardness GH

actual

 

and the target water hardness GH

target

Hardness reduction = GH

actual

-GH

target

l °dH 

Enter the value in the controller. Consult the 
manufacturer information for third-party products. 

Cap. soft water 
05000 l 

This value is only displayed if "YES" has been set in the 
"With softening" menu option. 
The attainable soft water capacity is calculated from the 
type of softening used and the specified hardness 
reduction. 

 

Fillsoft I, soft water capacity ≤ 6000/hardness red. l

 

 

Fillsoft II, soft water capacity ≤ 12000/hardness 

red. l 

Enter the value in the controller. Consult the 
manufacturer information for the values of third-party 
products. 

Remaining cap. soft 
w. 
000020 l 

This value is only displayed if "YES" has been set in the 
"With softening" menu option. 

 

Available soft water capacity. 

Replacement 
18 months 

This value is only displayed if "YES" has been set in the 
"With softening" menu option. 

 

Manufacturer specification for the replacement 
interval of the softening cartridges, regardless of 
the calculated soft water capacity. The system 
displays the "Softening" message. 

Next maintenance 
012 months 

Recommended maintenance messages. 

 

Off: Without maintenance recommendation. 

 

001 

 060: Maintenance recommendation in 

months. 

Floating fault 
contact 
YES 

For the output of messages to the floating contact, see 
chapter 9.3 "Messages" on page 14 . 

 

YES: Output of all messages. 

 

NO: Output of all messages identified with 

"xxx"

 

("01", for example). 

Indication on the 
display 

Meaning 

Fault memory

˃

 

Switch to the "Fault memory" sub-menu. 

 

Press "OK" to open the menu. 

 

Use the "

▼▲

" buttons to open the sub-menu. 

ER 01…xx

 

The last 20 alarms are stored with fault type, date, time, 
and fault code. 
See the chapter "Messages" for more information about 
the ER... messages. 

Parameter 
memory

˃

 

Switch to the "Parameter memory" sub-menu. 

 

Press "OK" to open the menu. 

 

Use the "

▼▲

" buttons to open the sub-menu. 

P0 = xx.x bar 
Date | Time 

The last 10 entries of the minimum working pressure are 
stored with date and time. 

V0.60 

Information about the software version 

 

9.2.1

 

Customer menu 

The device controller is shipped with the following default settings. Use the 
Customer menu to adjust these values to local conditions. In special cases, it is 
possible to further adjust the values in the Service menu.

 

 

Parameter 

Setting 

Comment 

Language 

EN  

Display language 

Fillcontrol XX 

Magcontrol  For systems with diaphragm-type 

expansion vessel 

Minimum operating 
pressure P

1.5 bar 

Only Magcontrol 
see chapter 7.2 "Determining the P

0

 

minimum operating pressure for 
the controller" o
n page 9  

Safety valve, pressure  

3.0 bar 

Tripping pressure for the safety 
valve at the heat generator in the 
system 

Next maintenance 

12 months 

Time left to the next due 
maintenance 

Volt-free contact 

NO 

Only the messages marked in the 
"Messages" list 

Make-up 
Maximum make-up volume  5000 litres 

Only if controller with "With water 
meter yes" 

Maximum make-up time  

20 minutes  Magcontrol 

Maximum make-up cycles  3 cycles 

within 2 
hours  

Magcontrol 

Softening (Only if "With softening yes") 
Shut off make-up 

NO 

In the event of soft water residual 
capacity = 0 

Hardness reduction 

8°dH 

= Setpoint 

 Actual 

Maximum make-up volume  0 litres 

Attainable make-up quantity 

Soft water capacity 

0 litres 

Attainable water capacity 

Cartridge replacement 

18 months 

Replace cartridge 

 

Summary of Contents for Fillcontrol Auto

Page 1: ...Fillcontrol Auto 22 09 2020 Rev C GB Operating manual Original operating manual...

Page 2: ...cal connection 8 6 5 1 Terminal diagram 8 6 5 2 RS 485 interface 9 6 6 Installation and commissioning certificate 9 7 Commissioning 9 7 1 Requirements for initial commissioning 9 7 2 Determining the P...

Page 3: ...ult in death or severe irreversible injuries WARNING Serious damage to health The sign in combination with the signal word Warning indicates imminent danger failure to observe the safety information c...

Page 4: ...stems Solar circuits The device is used in combination with a user supplied open system separator tank Note An application without system separator tank is possible For customised design and adjustmen...

Page 5: ...For calculating the filling pressure into the system circuit see chapter 7 2 Determining the P0 minimum operating pressure for the controller on page 9 Adding water to system circuits with a pressuris...

Page 6: ...possible transport damage 2 Document any damage 3 Contact the forwarding agent to register your complaint 6 2 Preparatory work Preparing the device installation Frost free well ventilated room Room te...

Page 7: ...n open system separator tank Make up temperatures up to 70 C Pipeline lengths see chapter 6 3 1 Floor mounting on page 6 Outlet from the system separator tank at least 100 mm above the intake connecti...

Page 8: ...electric shock Some parts of the device s circuit board may still carry 230 V voltage even with the device physically isolated from the power supply Before you remove the covers completely isolate the...

Page 9: ...ng and the annual maintenance 7 1 Requirements for initial commissioning The device will be ready for initial commissioning when the tasks described in the Installation chapter have been completed Not...

Page 10: ...h Magcontrol make up variant Calculation of the minimum operating pressure see chapter 7 2 Determining the P0 minimum operating pressure for the controller on page 9 Safety valve pressure Enter the va...

Page 11: ...operation can be started after initial commissioning The following prerequisites must be met for automatic operation P0 minimum working pressure is entered in the controller The device is filled with...

Page 12: ...sioning the factory settings must first be adjusted for the system specific conditions Note For a description of the operation see chapter 9 1 Operator panel on page 12 All grey marked menu items must...

Page 13: ...ble soft water capacity Replacement 18 months This value is only displayed if YES has been set in the With softening menu option Manufacturer specification for the replacement interval of the softenin...

Page 14: ...an the dirt trap Replace the float valve 04 1 Pump YES Pump does not start PU pump is stuck Pump motor defective 10 A fuse defective Contractor Klixon tripped Manually turn the pump to start Replace t...

Page 15: ...ons Ensure that installation work for the electric connection of the device is carried out by an electrician and in compliance with electrical engineering regulations CAUTION Risk of injury due to pre...

Page 16: ...ore you remove the covers completely isolate the device controller from the power supply Verify that the main circuit board is voltage free CAUTION Risk of burns Escaping hot medium can cause burns Ma...

Page 17: ...Installation and commissioning certificate This device has been installed and commissioned in accordance with the instructions provided in the operating manual The settings in the controller match th...

Page 18: ...SI1415enC 11 20 Reflex Winkelmann GmbH Gersteinstra e 19 59227 Ahlen Germany 49 0 2382 7069 0 49 0 2382 7069 9546 www reflex winkelmann com...