Controller
Fillcontrol Auto
—
22.09.2020 - Rev. C
English
—
13
Indication on the
display
Meaning
With water meter.
YES
•
YES: FQIRA+ contact water meter is installed, see
chapter 4.6 "Optional equipment and accessories"
on page 5 .
This is the prerequisite for the make-up volume
monitoring and the operation of a softening
system.
•
NO: A contact water meter is not installed
(standard model).
Make-up volume
000020 l
Only displayed if "YES" has been set in the "With water
meter" menu option.
•
Press "OK" to delete the counter.
•
Press "YES" to reset the value displayed to "0".
•
Press "NO" to retain the displayed value.
Max. make-up
volume
000100 l
This value is only displayed if "YES" has been set in the
"With water meter" menu option.
•
When the set volume is exceeded, the system
interrupts the make-up process and returns the
error message "Max. make-up volume exceeded".
With softening
YES
This value is only displayed if "YES" has been set in the
"With water meter" menu option.
•
YES: Further queries follow about softening.
•
NO: The system does not offer more queries
regarding the softening process.
Disable make-up?
YES
This value is only displayed if "YES" has been set in the
"With softening" menu option.
•
YES: The system stops the make-up process when
the set soft water capacity is exceeded.
•
NO: The system does not stop the make-up
process. The system displays the "Softening"
message.
Hardness reduction
10 °dH
This value is only displayed if "YES" has been set in the
"With softening" menu option.
•
Hardness reduction is calculated from the
difference of the overall water hardness GH
actual
and the target water hardness GH
target
.
Hardness reduction = GH
actual
-GH
target
l °dH
Enter the value in the controller. Consult the
manufacturer information for third-party products.
Cap. soft water
05000 l
This value is only displayed if "YES" has been set in the
"With softening" menu option.
The attainable soft water capacity is calculated from the
type of softening used and the specified hardness
reduction.
•
Fillsoft I, soft water capacity ≤ 6000/hardness red. l
•
Fillsoft II, soft water capacity ≤ 12000/hardness
red. l
Enter the value in the controller. Consult the
manufacturer information for the values of third-party
products.
Remaining cap. soft
w.
000020 l
This value is only displayed if "YES" has been set in the
"With softening" menu option.
•
Available soft water capacity.
Replacement
18 months
This value is only displayed if "YES" has been set in the
"With softening" menu option.
•
Manufacturer specification for the replacement
interval of the softening cartridges, regardless of
the calculated soft water capacity. The system
displays the "Softening" message.
Next maintenance
012 months
Recommended maintenance messages.
•
Off: Without maintenance recommendation.
•
001
–
060: Maintenance recommendation in
months.
Floating fault
contact
YES
For the output of messages to the floating contact, see
chapter 9.3 "Messages" on page 14 .
•
YES: Output of all messages.
•
NO: Output of all messages identified with
"xxx"
("01", for example).
Indication on the
display
Meaning
Fault memory
˃
Switch to the "Fault memory" sub-menu.
•
Press "OK" to open the menu.
•
Use the "
▼▲
" buttons to open the sub-menu.
ER 01…xx
The last 20 alarms are stored with fault type, date, time,
and fault code.
See the chapter "Messages" for more information about
the ER... messages.
Parameter
memory
˃
Switch to the "Parameter memory" sub-menu.
•
Press "OK" to open the menu.
•
Use the "
▼▲
" buttons to open the sub-menu.
P0 = xx.x bar
Date | Time
The last 10 entries of the minimum working pressure are
stored with date and time.
V0.60
Information about the software version
9.2.1
Customer menu
The device controller is shipped with the following default settings. Use the
Customer menu to adjust these values to local conditions. In special cases, it is
possible to further adjust the values in the Service menu.
Parameter
Setting
Comment
Language
EN
Display language
Fillcontrol XX
Magcontrol For systems with diaphragm-type
expansion vessel
Minimum operating
pressure P
0
1.5 bar
Only Magcontrol
see chapter 7.2 "Determining the P
minimum operating pressure for
the controller" on page 9
Safety valve, pressure
3.0 bar
Tripping pressure for the safety
valve at the heat generator in the
system
Next maintenance
12 months
Time left to the next due
maintenance
Volt-free contact
NO
Only the messages marked in the
"Messages" list
Make-up
Maximum make-up volume 5000 litres
Only if controller with "With water
meter yes"
Maximum make-up time
20 minutes Magcontrol
Maximum make-up cycles 3 cycles
within 2
hours
Magcontrol
Softening (Only if "With softening yes")
Shut off make-up
NO
In the event of soft water residual
capacity = 0
Hardness reduction
8°dH
= Setpoint
–
Actual
Maximum make-up volume 0 litres
Attainable make-up quantity
Soft water capacity
0 litres
Attainable water capacity
Cartridge replacement
18 months
Replace cartridge