Electrical connections/Operating modes
OVERRIDE
SAFEGATE allows you to configure two different types of override; (See paragraph
for the description of the following function).
Î
The OVERRIDE activation condition for the “L” Muting type requires only the light curtain occupation,
while for the “T” Muting type the occupation of light curtain and at least one sensor is required.
OVERRIDE1 (pin 10)
OVERRIDE2 (pin 9)
SELEZIONE
0
0
Override with Hold-To-Run Control
0
1
Override with Pulse Control
1
0
Wrong configuration
1
1
OVERRIDE WITH HOLD-TO-RUN CONTROL
The function starts with the simultaneous activation of the two OVERRIDE inputs according to the following
table:
The function starts only if the signals are activated (24VDC) at the same time (within a maximum delay of
400 ms) and the control is kept active for at least 400 ms.
OVERRIDE WITH PULSE CONTROL
The function starts with the simultaneous activation of the two OVERRIDE inputs according to the following
table:
The function starts only if the signals are activated at the same time (within a maximum delay of 400 ms)
and the control is kept active for at least 400 ms.
OVERRIDE1 (pin 10)
OVERRIDE2 (Pin 9)
0
0
1
1
OVERRIDE1 (pin 10)
OVERRIDE2 (Pin 9)
0
1
1
0