4.3 Complete power off procedure
To completely switch off the UPS and powered receivers, proceed to step 4.2.4 to Bypass service
and then disconnect the UPS from the power switchboard.
4.4
Emergency shutdown with EPO
The UPS Emergency Power Button is located on the front panel of the UPS and is used for
emergency shutdown in the event of a flood, fire, etc. The EPO circuit breaker immediately
extinguishes the rectifier, inverter and disconnects the UPS output and stops charging or
discharging the battery.
To start the UPS for normal operation after using EPO, restore the emergency stop to its normal
position and supply the UPS voltage. The power supply will start normal operation
automatically.
EPO BUTTON
4.5
Battery test
Battery tests in the power supply can be carried out in two ways:
Method 1: It consists in manually turning on the battery test. To do this, go to the OPERATE
menu shown in the figure below and then click the "Battery maintenance" icon
.
UPS will switch to battery mode. The discharge process will end automatically when the battery
reaches 20% capacity or low battery voltage is reached. The discharge process can also be
terminated by touching the "Stop Test" icon.
.