Figure 2-104 Dimensions of the power supply casing UPS HS 505/350-500kVA
The table below contains the mass of the above devices:
Power UPS
Weight
HS 105/100kVA
210 kg
HS 205/150kVA
305 kg
HS 205/200kVA
350 kg
HS 305/250kVA
445 kg
HS 305/300kVA
490 kg
HS 505/350kVA
765 kg
HS 505/400kVA
810 kg
HS 505/450kVA
855 kg
HS 505/500kVA
900 kg
2.7.
Service space
On the side walls of the power supply unit there are no ventilation openings, therefore there is
no need for ventilation space on the side. For access to the device on each side, it is
recommended to keep min. 50 cm service area.
It is necessary to provide adequate space from the front of the power supply for easy operation
and the ability to draw cold air from the environment. Recommended 80 cm front space.
Due to the required access to the back of the power supply and free air discharge and
circulation, the recommended back space of the power supply is a minimum of 50 cm.