23
1500
MIN.
300
MIN.
300
10
MIN. 400
MIN. 1800
5 - POSITIONING
Technical Dept. - All rights reserved - Reproduction is prohibited
REQUIREMENTS FOR INSTALLATION OF THE PLANT - POSITIONING
The most important thing to do before installation of the boiler is to set aside a suitable area that meets the minimum requirements for
installation.
•
the minimum clearance in front of the product
to allow suitable access for cleaning, maintenance, etc. must be
400 mm
;
• the minimum permissible distance between the back of the product and a wall must be
10 mm
;
• the minimum distance between the top of the product and the ceiling must be
600 mm
to ensure easy access to the heat exchanger
for the purpose of cleaning and maintenance (e.g. for removing ash);
• the minimum clearance between the product and the wall (side) must be
300 mm
.
COMPACT SLIM 15 BOILER MINIMUM REQUIREMENTS