-15-
Released 2018-01-12
Drawing No. LP0932
COdE
1
to
125
HIDDEN LOOP
w/CONFIGURATION
LOOP ACCESSIBLE
PARAMETER
LOOP
P
P
P
MAIN
DISPLAY LOOP
D
*
If PLOC is active, the Configuration Loop is not accessible.
D
Hold
P
Hold
IF Code =
1 to 125
IF Code =
0
IF Code =
-1 to -125
HIDDEN
LOOP
COdE
-1
to
-125
P
CONFIGURATION
LOOP
*
*
P
DISPLAY LOOP
At power up, all display segments light, and then the programmed
input type and the controller’s software version will flash. Then the
Temperature/Process Value is shown in the top display, and the bottom
display will show the first Display Loop parameter configured as
dIP
in
Configuration Module 3.
Pressing the
=
key advances the bottom display to the next Display
Loop parameter. After viewing the last parameter, the display loops back
to the beginning of the Display Loop. If the bottom display is blank, it is
because there are no parameters enabled for display in the Display Loop.
Changes made to parameters are effective immediately. Parameters
that can be displayed in the Display Loop include:
P
C1
OP1
OP2
PrP
PId
r-
P
r-i
dV
P1
P2
Pressing the
:
key advances the bottom display to the Parameter
Loop.
PARAMETER LOOP
Pressing the
:
key, while in the Display Loop, will advance the bottom
display to the Parameter Loop. Applicable items configured as
PArA
in
Configuration Module 3 will be displayed in the Parameter Loop. Each
press of the
:
key will advance the bottom display to the next Parameter
Loop parameter. After viewing the last parameter the display will loop
back to the beginning of the Parameter Loop. Pressing the
:
key while
parameters are not configured as
PArA
in Module 3, will cause the bottom
display to remain in the Display Loop and advance to the first Display
Loop parameter.
Pressing the
=
key will return the display to the Display Loop. To
accept a parameter change, the
:
key must be pressed prior to
pressing the
=
key.
The unit will automatically exit to the Display Loop after approximately
one minute of no key presses.
Parameters that can be displayed in the Parameter Loop include:
P
C1
OP1
OP2
PrP
PId
r-
P
r-i
ProF
Pg
OPOF
ProP
In
dR
dIn
AL-1
AL-2
AL-3
ALr
PL
P1
P2
HIDDEN LOOP
Press and Hold the
:
key for 3 seconds to enter the Hidden Loop. If
a lockout code 1 thru 125 has been configured in Module 3 (
COd
), the
correct access code will need to be entered prior to gaining access to the
Hidden Loop. If a User Input is configured for
PLOC
(program disable), the
User Input will need to be de-activated prior to gaining access to the
Hidden Loop. Factory programmed setting for Code = 0, and the User
Inputs are not configured.
After accessing the Hidden Loop, each consecutive press of the
:
button will advance the bottom display through the applicable parameters
selected as
id
in Module 3. The last item in the Hidden Loop is either
COd
or
CNFP
. If a lockout code -1 thru -125 has been configured in Module
3 (
COd
), the correct access code will need to be entered prior to gaining
access to the Configuration Loop. Pressing
:
while
CNFP
is selected as
NO
will exit to the first parameter in the Display Loop.
To accept a parameter change, the
:
key must be pressed prior to
pressing the
=
key. Pressing the
=
key will return the display to the
Display Loop.
The unit will automatically exit to the Display Loop after approximately
one minute of no key presses.
Parameters that can be displayed in the Hidden Loop include:
P
C1
OP1
OP2
PrP
PId
r-
P
r-i
ProF
Pg
OPOF
ProP
In
dR
dIn
AL-1
AL-2
AL-3
ALr
PL
N
CrL
P
rnF
P1
P2
ACCESS CODE
If the Access Code is set from 1 to 125, in Lockout Module
3-LC
,
Cod
will appear prior to gaining access to the Hidden Loop. By entering the
proper code, access to the Hidden Loop is permitted. With the factory
setting of 0,
Cod
will not appear in the Hidden Loop.
If the Access Code is set from -1 to -125, in Lockout Module
3-LC
,
Cod
will appear as the last Hidden Loop item. By entering the proper code,
access to the Configuration Loop is permitted (with a negative code
value, the Hidden Loop can be accessed without the use of a code). With
an active User Input configured for Program Lock (
PLOC
),
Cod
will not
appear. An active user input configured for Program Lock (
PLOC
) always
locks out the Configuration Loop, regardless of Access Code.
0
Cod
1
to
125
0
Cod
-1
to
-125